cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider ACTI9 IC60N Circuit breaker - ACTI9 IC60, 40A, 4P, C

Schneider Electric · Electrical Components · Moulded Case Circuit Breakers · France · se.com
Part Number
A9F04440  ·  HS 8536.20
Schneider ACTI9 IC60N Circuit breaker - ACTI9 IC60, 40A, 4P, C

Schneider Acti9 iC60N Circuit breaker. Circuit breakers (Electrical Engineering / Components for panels and boxes). Principal data: series Acti9 iC60, current rating 40 A, number of poles 4P, tripping characteristic C. Supplied under manufacturer part number A9F04440, EAN 3606480440854, HS code 8536.20, country of origin Bulgaria.

Technical Specifications

Product typeCircuit breakers
Product groupComponents for panels and boxes
SeriesActi9 iC60
Current rating40 A
Number of poles4P
Tripping characteristicC
REACH SVHC substance above 0.1%Lead
Carbon footprint (EPD)0.8350 kg CO2e per pcs
Environmental declarationPEP ECO Passport
Country of originBulgaria
Customs tariff code (EU CN)85362010
HS code8536.20
Manufacturer part numberA9F04440
GTIN (EAN)3606480440854
RangeActi9
Product nameActi9 iC60
Product or component typeMiniature circuit-breaker
Device short nameIC60N
Device applicationDistribution
Poles description4P
Number of protected poles4
[In] rated current40 A
Network typeDC; AC
Trip unit technologyThermal-magnetic
Curve codeC
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Suitability for isolationYes conforming to EN/IEC 60898-1; Yes conforming to EN/IEC 60947-2
StandardsEN/IEC 60947-2; EN/IEC 60898-1
Network frequency50/60 Hz
[Ue] rated operational voltage12...133 V AC 50/60 Hz; 220...240 V AC 50/60 Hz; 380...415 V AC 50/60 Hz; 440 V AC 50/60 Hz; <= 250 V DC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 10 kA Icu at <= 250 V DC conforming to EN/IEC 60947-2; 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
[Ics] rated service breaking capacity27 kA 75 % x Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 75 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 7.5 kA 75 % x Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 4.5 kA 75 % x Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 10 kA 100 % x Icu at <= 250 V DC conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
Contact position indicatorYes
Control typeToggle
Local signallingTrip indicator
mounting modeClip-on; Removable comb busbar installed
Mounting support35 mm DIN rail
Connection pitch18 mm between phases
9 mm pitches8
Height91 mm
Width72 mm
Depth78.5 mm
Product weight0.5 kg
ColourWhite
Mechanical durability20000 cycles
Electrical durability10000 cycles
Connections - terminalsDouble terminal (top or bottom) , for 1 cable(s) , 1…35 mm², rigid, copper; Double terminal (top or bottom) , for 3.0 cable(s) , 16 mm², rigid, copper, with accessory; Double terminal (top or bottom) , for 1.0 cable(s) , 50 mm², rigid, aluminium, with accessory; Double terminal (top or bottom) , for 1.0 cable(s) , 1…25 mm², flexible, copper; Double terminal (top or bottom) , for 1.0 cable(s) , 1…25 mm², flexible with ferrule, copper; Double terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory; Double terminal (top or bottom) , for 3 cable(s) , 10 mm², flexible, copper, with accessory
Wire stripping length14 mm for top or bottom connection
Tightening torque3.5 N.m top or bottom
Earth-leakage protectionSeparate block
IP degree of protectionIP20 conforming to IEC 60529; IP40 in modular enclosure (Insulation class II) conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Overvoltage categoryIV
Tropicalisation2 conforming to IEC 60068-1
Relative humidity95 % at 55 °C
Ambient air temperature for operation-35…70 °C
Ambient air temperature for storage-40…85 °C
Warranty (in months)18

Properties

MOQ1

Cross-References