| Product type | Circuit breakers |
| Product group | Components for panels and boxes |
| Series | Acti9 iC60 |
| Current rating | 32 A |
| Number of poles | 3P |
| Tripping characteristic | B |
| REACH SVHC substance above 0.1% | Lead |
| Carbon footprint (EPD) | 0.8350 kg CO2e per pcs |
| Environmental declaration | PEP ECO Passport |
| Country of origin | Bulgaria |
| Customs tariff code (EU CN) | 85362010 |
| HS code | 8536.20 |
| Manufacturer part number | A9F03332 |
| GTIN (EAN) | 3606480439957 |
| Range | Acti9 |
| Product name | Acti9 iC60 |
| Product or component type | Miniature circuit-breaker |
| Device short name | IC60N |
| Device application | Distribution |
| Poles description | 3P |
| Number of protected poles | 3 |
| [In] rated current | 32 A |
| Network type | AC; DC |
| Trip unit technology | Thermal-magnetic |
| Curve code | B |
| Utilisation category | Category A conforming to EN/IEC 60947-2 |
| Suitability for isolation | Yes conforming to EN/IEC 60898-1; Yes conforming to EN/IEC 60947-2 |
| Standards | EN/IEC 60947-2; EN/IEC 60898-1 |
| Network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 12...133 V AC 50/60 Hz; 220...240 V AC 50/60 Hz; 380...415 V AC 50/60 Hz; 440 V AC 50/60 Hz; <= 180 V DC |
| Magnetic tripping limit | 4 x In +/- 20 % |
| Breaking capacity | 36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 10 kA Icu at <= 180 V DC conforming to EN/IEC 60947-2; 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
| [Ics] rated service breaking capacity | 27 kA 75 % x Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 75 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 7.5 kA 75 % x Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 4.5 kA 75 % x Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 10 kA 100 % x Icu at <= 180 V DC conforming to EN/IEC 60947-2 |
| Limitation class | 3 conforming to EN/IEC 60898-1 |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-2 |
| Contact position indicator | Yes |
| Control type | Toggle |
| Local signalling | Trip indicator |
| mounting mode | Clip-on; Removable comb busbar installed |
| Mounting support | 35 mm DIN rail |
| Connection pitch | 18 mm between phases |
| 9 mm pitches | 6 |
| Height | 91 mm |
| Width | 54 mm |
| Depth | 78.5 mm |
| Product weight | 0.375 kg |
| Colour | White |
| Mechanical durability | 20000 cycles |
| Electrical durability | 10000 cycles |
| Connections - terminals | Double terminal (top or bottom) , for 1 cable(s) , 1…35 mm², rigid, copper; Double terminal (top or bottom) , for 3.0 cable(s) , 16 mm², rigid, copper, with accessory; Double terminal (top or bottom) , for 1.0 cable(s) , 50 mm², rigid, aluminium, with accessory; Double terminal (top or bottom) , for 1.0 cable(s) , 1…25 mm², flexible, copper; Double terminal (top or bottom) , for 1.0 cable(s) , 1…25 mm², flexible with ferrule, copper; Double terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory; Double terminal (top or bottom) , for 3 cable(s) , 10 mm², flexible, copper, with accessory |
| Wire stripping length | 14 mm for top or bottom connection |
| Tightening torque | 3.5 N.m top or bottom |
| Earth-leakage protection | Separate block |
| IP degree of protection | IP20 conforming to IEC 60529; IP40 in modular enclosure (Insulation class II) conforming to IEC 60529 |
| Pollution degree | 3 conforming to EN/IEC 60947-2 |
| Overvoltage category | IV |
| Tropicalisation | 2 conforming to IEC 60068-1 |
| Relative humidity | 95 % at 55 °C |
| Ambient air temperature for operation | -35…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Warranty (in months) | 18 |