cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider ACTI9 IC60N Circuit breaker - ACTI9 IC60, 13A, 1P + N, B

Schneider Electric · Electrical Components · Moulded Case Circuit Breakers · France · se.com
Part Number
A9F03613  ·  HS 8536.20
Schneider ACTI9 IC60N Circuit breaker - ACTI9 IC60, 13A, 1P + N, B

Schneider Acti9 iC60N Circuit breaker. Circuit breakers (Electrical Engineering / Components for panels and boxes). Principal data: series Acti9 iC60, current rating 13 A, number of poles 1P + N, tripping characteristic B. Supplied under manufacturer part number A9F03613, EAN 3606480440113, HS code 8536.20, country of origin Bulgaria.

Technical Specifications

Product typeCircuit breakers
Product groupComponents for panels and boxes
SeriesActi9 iC60
Current rating13 A
Number of poles1P + N
Tripping characteristicB
Width36 mm
REACH SVHC substance above 0.1%Lead
Carbon footprint (EPD)0.8350 kg CO2e per pcs
Environmental declarationPEP ECO Passport
Country of originBulgaria
Customs tariff code (EU CN)85362010
HS code8536.20
Manufacturer part numberA9F03613
GTIN (EAN)3606480440113
RangeActi9
Product nameActi9 iC60
Product or component typeMiniature circuit-breaker
Device short nameIC60N
Device applicationDistribution
Poles description1P + N
Number of protected poles1
Neutral positionLeft
[In] rated current13 A
Network typeDC; AC
Trip unit technologyThermal-magnetic
Curve codeB
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Suitability for isolationYes conforming to EN/IEC 60898-1; Yes conforming to EN/IEC 60947-2
StandardsEN/IEC 60947-2; EN/IEC 60898-1
Network frequency50/60 Hz
[Ue] rated operational voltage12...60 V AC 50/60 Hz; 100...133 V AC 50/60 Hz; 220...240 V AC 50/60 Hz
Magnetic tripping limit4 x In +/- 20 %
Breaking capacity36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2; 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
[Ics] rated service breaking capacity27 kA 75 % x Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 75 % x Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 7.5 kA 75 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
Contact position indicatorYes
Control typeToggle
Local signallingTrip indicator
mounting modeClip-on; Removable comb busbar installed
Mounting support35 mm DIN rail
Connection pitch18 mm between phase and neutral
9 mm pitches4
Height91 mm
Depth78.5 mm
Product weight0.25 kg
ColourWhite
Mechanical durability20000 cycles
Electrical durability10000 cycles
Connections - terminalsDouble terminal (top or bottom) , for 1 cable(s) , 1…25 mm², rigid, copper; Double terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible, copper; Double terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible with ferrule, copper; Double terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory
Wire stripping length14 mm for top or bottom connection
Tightening torque2 N.m top or bottom
Earth-leakage protectionSeparate block
IP degree of protectionIP20 conforming to IEC 60529; IP40 in modular enclosure (Insulation class II) conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Overvoltage categoryIV
Tropicalisation2 conforming to IEC 60068-1
Relative humidity95 % at 55 °C
Ambient air temperature for operation-35…70 °C
Ambient air temperature for storage-40…85 °C
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents