Schneider Acti9 iC40 MCD AFDD Zigbee Spark detector. Circuit breakers (Electrical Engineering / Components for panels and boxes). Principal data: series Acti9 iC40, current rating 10 A, number of poles 1P + N, tripping characteristic B. Supplied under manufacturer part number A9TPDD610, EAN 3606481906175, HS code 8536.20, country of origin Spain.

Technical Specifications

Product typeCircuit breakers
Product groupComponents for panels and boxes
SeriesActi9 iC40
Current rating10 A
Number of poles1P + N
Tripping characteristicB
Width36 mm
REACH SVHC substance above 0.1%Lead, Diboron-trioxide, Lead-monoxide
Carbon footprint (EPD)3.2500 kg CO2e per pcs
Environmental declarationPEP ECO Passport
Country of originSpain
Customs tariff code (EU CN)85362010
HS code8536.20
Manufacturer part numberA9TPDD610
RangeActi9
Product nameActi9 Active ARC iC40
Product or component typeActive arc fault detection circuit breaker
Product specific applicationArc fault detection
StandardsEN/IEC 60898-1; EN/IEC 60947-2; EN/IEC 62606
Device short nameiC40N ARC
Poles description1P + N
[In] rated current10 A
Curve codeB
Breaking capacity3000 A Icn1 at 230 V AC 50 Hz conforming to EN/IEC 60898-1; 10 kA Icu at 230 V AC 50 Hz conforming to EN/IEC 60947-2; 6000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 60898-1
Network typeAC
Neutral positionLeft
Electrical data recordingDate and time; Maintenance indicators
Concentrator compatibilityEcoStruxure Panel Server Advanced; EcoStruxure Panel Server Entry; EcoStruxure Panel Server Universal
Event managementOvervoltage; Earth leakage; Overload
Type of measurementVoltage; Active power; Current; Power factor
AccuracyVoltage: +/- 2 %; Current: +/- 2 %; Power: +/- 5 %
Suitability for isolationYes
Trip unit technologyThermal-magnetic
Number of protected poles1
Network frequency50 Hz
[Ue] rated operational voltage230 V AC 50 Hz
Device location in systemOutgoer
Magnetic tripping limit3...5 x In
[Ics] rated service breaking capacity6000 A conforming to EN/IEC 60898-1; 7.5 kA conforming to EN/IEC 60947-2
Limitation class3
Threshold tripping voltage275 V for +/- 5 V
[Uimp] rated impulse withstand voltage4 kV
[Ui] rated insulation voltage250 V AC
Contact position indicatorYes
Control typeToggle
Local signallingON, OFF, fault trip; LED arc fault diagnostic
mounting modeClip-on
Mounting supportDIN rail
ColourWhite (RAL 9003)
Mechanical durability20000 cycles
Electrical durability10000 cycles
Locking options descriptionPadlocking device
cable entryTop and bottom
Connections - terminalsTunnel type terminal 1…10 mm² flexible; Tunnel type terminal 1…16 mm² rigid
Wire stripping length14 mm
Tightening torque2 N.m
9 mm pitches4
Height91 mm
Depth73 mm
Product weight210 g
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree2
TropicalisationSeverity B conforming to IEC 60068-2-30 for 28 d
Operating altitude2000 m
Ambient air temperature for operation-25…40 °C
Ambient air temperature for storage-40…80 °C
Warranty (in months)18
EAN3606481906175