Schneider ACTI9 IC40 MCB AFDD Spark detector - ACTI9 IC40, 25A, 1P + N, C

Schneider Electric · Electrical Components · Miniature Circuit Breakers · France · se.com
Part Number
A9TPE4625  ·  HS 8536.20
Schneider ACTI9 IC40 MCB AFDD Spark detector - ACTI9 IC40, 25A, 1P + N, C

Schneider Acti9 iC40 MCB AFDD Spark detector. Circuit breakers (Electrical Engineering / Components for panels and boxes). Principal data: series Acti9 iC40, current rating 25 A, number of poles 1P + N, tripping characteristic C. Supplied under manufacturer part number A9TPE4625, EAN 3606481906380, HS code 8536.20, country of origin Spain.

Technical Specifications

Product typeCircuit breakers
Product groupComponents for panels and boxes
SeriesActi9 iC40
Current rating25 A
Number of poles1P + N
Tripping characteristicC
Breaking capacity6 kA
Width36 mm
REACH SVHC substance above 0.1%Lead, Diboron-trioxide, Lead-monoxide
Carbon footprint (EPD)3.2500 kg CO2e per pcs
Environmental declarationPEP ECO Passport
Country of originSpain
Customs tariff code (EU CN)85362010
HS code8536.20
Manufacturer part numberA9TPE4625
RangeActi9
Product nameActi9 iC40 ARC
Product or component typeArc fault detection circuit breaker
Product specific applicationArc fault detection
StandardsEN/IEC 60898-1; EN/IEC 60947-2; EN/IEC 62606
Device short nameiC40 ARC
Poles description1P + N
[In] rated current25 A
Curve codeC
Network typeAC
Neutral positionLeft
Suitability for isolationYes
Trip unit technologyThermal-magnetic
Number of protected poles1
Network frequency50 Hz
[Ue] rated operational voltage230 V AC 50 Hz
Device location in systemOutgoer
Magnetic tripping limit5...10 x In
[Ics] rated service breaking capacity6000 A conforming to EN/IEC 60898-1; 7.5 kA conforming to EN/IEC 60947-2
Limitation class3
Threshold tripping voltage275 V for +/- 5 V
[Uimp] rated impulse withstand voltage4 kV
[Ui] rated insulation voltage250 V AC
Contact position indicatorYes
Control typeToggle
Local signallingON, OFF, fault trip; LED arc fault diagnostic
mounting modeClip-on
Mounting supportDIN rail
ColourWhite (RAL 9003)
Mechanical durability20000 cycles
Electrical durability20000 cycles
Locking options descriptionPadlocking device
cable entryTop and bottom
Connections - terminalsTunnel type terminal 1…10 mm² flexible; Tunnel type terminal 1…16 mm² rigid
Wire stripping length14 mm
Tightening torque2 N.m
9 mm pitches4
Height91 mm
Depth73 mm
Product weight210 g
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree2
TropicalisationSeverity B conforming to IEC 60068-2-30 for 28 d
Operating altitude2000 m
Ambient air temperature for operation-25…40 °C
Ambient air temperature for storage-40…80 °C
Quality labelsAENOR; OVE
Warranty (in months)18
EAN3606481906380