cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider ACTI9 C120H Circuit breaker - ACTI9 C120, 100A, 1P, B

Schneider Electric · Electrical Components · Moulded Case Circuit Breakers · France · se.com
Part Number
A9N18342  ·  HS 8536.20
Schneider ACTI9 C120H Circuit breaker - ACTI9 C120, 100A, 1P, B

Schneider Acti9 C120H Circuit breaker. Circuit breakers (Electrical Engineering / Components for panels and boxes). Principal data: series Acti9 C120, current rating 100 A, number of poles 1P, tripping characteristic B. Supplied under manufacturer part number A9N18342, EAN 3606480379161, HS code 8536.20, country of origin France.

Technical Specifications

Product typeCircuit breakers
Product groupComponents for panels and boxes
SeriesActi9 C120
Current rating100 A
Number of poles1P
Tripping characteristicB
Width27 mm
REACH SVHC substance above 0.1%Boric acid, Triphenyl phosphate
Carbon footprint (EPD)4.5100 kg CO2e per pcs
Environmental declarationPEP ECO Passport
Country of originFrance
Customs tariff code (EU CN)85362090
HS code8536.20
Manufacturer part numberA9N18342
GTIN (EAN)3606480379161
RangeActi9
Product nameActi9 C120
Product or component typeMiniature circuit-breaker
Device short nameC120N
Device applicationDistribution
Poles description1P
Number of protected poles1
[In] rated current100 A at 30 °C
Network typeAC
Trip unit technologyThermal-magnetic
Curve codeB
Breaking capacity3 kA Icu at 380...415 V AC 50/60 Hz IT conforming to EN/IEC 60947-2; 20 kA Icu at 130 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA Icu at 12 V DC conforming to EN/IEC 60947-2; 15 kA Icu at 125 V DC conforming to EN/IEC 60947-2; 10 kA Icu at <= 144 V DC conforming to EN/IEC 60947-2; 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 20 kA Icu at 12 V AC 50/60 Hz conforming to EN/IEC 60947-2; 10000 A Icn at 230/400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Suitability for isolationYes conforming to IEC 60947-2
StandardsEN/IEC 60898-1; EN/IEC 60947-2
Product certificationsEAC
Network frequency50/60 Hz
[Ue] rated operational voltage380...415 V AC 50/60 Hz; 125 V DC; <= 144 V DC; 12 V DC; 220...240 V AC 50/60 Hz; 230...400 V AC 50/60 Hz; 130 V AC 50/60 Hz; 12 V AC 50/60 Hz
Magnetic tripping limit3...5 x In
[Ics] rated service breaking capacity15 kA 75 % conforming to EN/IEC 60947-2 - 130 V AC 50/60 Hz; 15 kA 100 % conforming to EN/IEC 60947-2 - 125 V DC; 2.25 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz; 15 kA 100 % conforming to EN/IEC 60947-2 - 12 V DC; 10 kA 100 % conforming to EN/IEC 60947-2 - <= 144 V DC; 7.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz; 15 kA 75 % conforming to EN/IEC 60947-2 - 12 V AC 50/60 Hz; 7500 A 75 % conforming to EN/IEC 60898-1 - 230/400 V AC 50/60 Hz
Limitation class3 conforming to EN/IEC 60947-2
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
Contact position indicatorYes
Control typeToggle
Local signallingON/OFF indication
mounting modeClip-on
Mounting support35 mm symmetrical DIN rail
Comb busbar and distribution block compatibilityYES
9 mm pitches3
Height81 mm
Depth73 mm
Product weight0.205 kg
ColourWhite
Mechanical durability20000 cycles
Electrical durability5000 cycles conforming to IEC 60947-2
Locking options descriptionHandle sealable with cable diameter 0.7mm in OFF or ON position
Connections - terminalsTunnel type terminals1…50 mm² rigid; Tunnel type terminals1.5…35 mm² flexible
Wire stripping length15 mm
Tightening torque3.5 N.m
Earth-leakage protectionWithout
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-2
Overvoltage categoryIV
Tropicalisation2 conforming to IEC 60068-1
Relative humidity95 % at 55 °C
Operating altitude2000 m
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C
Warranty (in months)18

Properties

MOQ1

Cross-References