cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric IEM3310 energy meter - 125 A - 1 pulse O - MID A9MEM3310

Schneider Electric · Sensors & Instrumentation · Energy Meters · France · se.com
Part Number
A9MEM3310  ·  HS 9028.30
Schneider Electric IEM3310 energy meter - 125 A - 1 pulse O - MID A9MEM3310

Schneider Electric A9MEM3310 2P/3P/3P+N KWH METER DIRECT 125A with pulsutgang. MID-certified.

Technical Specifications

Manufacturer part number (MPN)A9MEM3310
EAN / GTIN3606480696398
Sales unitpcs
Package quantity18 pcs
Rated current125 A
RangeActi9
range of productActi9 iEM3000
Product or component typeEnergy meter
Device short nameiEM3310
Market segmentBuildings small building cost management: billing: main incomer; Buildings small building cost management: billing: sub feeder; Buildings small building cost management: billing: panelboard; Buildings medium building cost management: billing: main incomer; Buildings medium building cost management: billing: sub feeder; Buildings medium building cost management: billing: panelboard; Buildings large building cost management: billing: main incomer; Buildings large building cost management: billing: sub feeder; Buildings large building cost management: billing: panelboard; Buildings multi-site cost management: billing: main incomer; Buildings multi-site cost management: billing: sub feeder; Buildings multi-site cost management: billing: panelboard; Data center cost management: billing; Healthcare cost management: billing; Industry cost management: billing; Buildings small building cost management: cost allocation: main incomer; Buildings small building cost management: cost allocation: sub feeder; Buildings small building cost management: cost allocation: panelboard; Buildings medium building cost management: cost allocation: main incomer; Buildings medium building cost management: cost allocation: sub feeder; Buildings medium building cost management: cost allocation: panelboard; Buildings large building cost management: cost allocation: main incomer; Buildings large building cost management: cost allocation: sub feeder; Buildings large building cost management: cost allocation: panelboard; Buildings multi-site cost management: cost allocation: main incomer; Buildings multi-site cost management: cost allocation: sub feeder; Buildings multi-site cost management: cost allocation: panelboard; Data center cost management: cost allocation; Healthcare cost management: cost allocation; Industry cost management: cost allocation
Poles description3P; 1P + N; 3P + N
Type of measurementActive energy
Device applicationSub billing; Partial meter
Accuracy classClass 1 active energy conforming to IEC 62053-21; Class 1 active energy conforming to IEC 61557-12; Class B active energy conforming to EN 50470-3
input typeDirect connection
[In] rated current125 A
Rated voltage100…277 V; 173…480 V
Network frequency60 Hz; 50 Hz
Technology typeElectronic
Display typeLCD display
Sampling rate32 samples/cycle
Measurement current0…125 A
Maximum value measured99999999.9 kWh
Communication port protocol-
Communication port support-
Local signallingGreen indicator light: power ON; Yellow flashing LED: accuracy checking
Number of inputs0
Number of outputs1 pulse
mounting modeClip-on
Mounting supportDIN rail
Connections - terminalsScrew terminals 50 mm² cable(s)
Overvoltage categoryIII
StandardsBS EN 61557-12:2021; IEC 61557-12:2021; EN 61557-12:2021; BS EN 61326-1; IEC 61326-1; EN 61326-1; BS EN 62052-11:2020; IEC 62052-11:2020; EN 62052-11:2020; BS EN 62053-21; IEC 62053-21; EN 62053-21; BS EN 62052-23; IEC 62053-23:2020; EN 62052-23; BS EN 62052-31:2015; IEC 62052-31:2015; EN 62052-31:2015; BS EN 61010-1:2010; EN 61010-1:2010; IEC 61010-1:2010; UL 61010-1:2010; BS EN 61010-2-30; IEC 61010-2-30; EN 61010-2-30; UL 61010-2-30; BS EN 50470-3; EN 50470-3; BS EN 50470-1; EN 50470-1; ANSI C12.16
Product certificationsCE conforming to IEC 61010-1 (safety); CE conforming to EN 61557-12 (power monitor); CE conforming to EN/IEC 61326-1 (EMC); UKCA conforming to BS EN 61010-1 (safety); UKCA conforming to BS EN 61557-12 (power monitor); UKCA conforming to BS EN 61326-1 (EMC); CULus conforming to UL 61010-1 (safety); CULus conforming to EN 61010-1 (safety); EAC conforming to EN 50470-3 (sub-meter); RCM conforming to EN 62052 (sub-meter); KZ conforming to EN 50470-3 (sub-meter); METAS conforming to EN 50470-1 (sub-meter); MID conforming to EN 50470-3 (sub-meter); MID conforming to EN 50470-1 (sub-meter); NMI conforming to NMI M 6-1
Compatibility codeIEM3310
IP degree of protectionIP40 front panel: conforming to IEC 60529; IP20 body: conforming to IEC 60529
Pollution degree2
Relative humidity5…95 % at 50 °C
Ambient air temperature for operation-25…55 °C - MID; -25…70 °C - IEC; -25…60 °C - IEC
Ambient air temperature for storage-40…85 °C
Operating altitude< 3000 m
ColourWhite
9 mm pitches14
Width126 mm
Height103.2 mm
Depth69.3 mm
Number of Units in Package 11
Number of Units in Package 216
Number of Units in Package 3384
Warranty (in months)18
Mounting methodDRA (DIN-rail adaptor)
ModelDirect measurement
Suitable forPurchase
Type of indicationDigital
Frequency50–60 Hz
Max. current (Imax)125 A
Width in number of modular spacings7
Number of positions total (counter)9
Type of meterElectronic
Degree of protection (IP)IP20
Type of interfaceNone
Energy typeEffective power
Tariff typeOne-tariff
Tariff controlExternal
Escapement mechanismNo
CalibratedNo
ApprovalMeasuring Instruments Directive
Pulse outputElectrical
Pulse typeS0
Pulse rate0–1000 Imp/kWh (kvarh)
Pole typeThree conductor/four conductor
Measurement type load profileNo
EEC40 signatureNo
With lock codeNo
Nominal voltage (Un) N-L100–277 V
Nominal voltage (Un) L-L173–480 V
Nominal current (In)125 A
Country of originChina

Properties

MOQ1

Cross-References

Attached Documents