cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric PM3210 power meter - output digital and pulse METSEPM3210

Schneider Electric · Sensors & Instrumentation · Meters & Analysers · France · se.com
Part Number
METSEPM3210  ·  HS 9028.30
Schneider Electric PM3210 power meter - output digital and pulse METSEPM3210

Schneider Electric METSEPM3210 PM3210 Modular power analyser with pulsutgang.

Technical Specifications

Manufacturer part number (MPN)METSEPM3210
EAN / GTIN3606480481598
Sales unitpcs
Package quantity16 pcs
RangePowerLogic
Product namePowerLogic PM3000
Product or component typePower meter
Device short namePM3210
Market segmentBuildings small building cost management: billing: sub feeder; Buildings medium building cost management: billing: sub feeder; Buildings large building cost management: billing: sub feeder; Buildings multi-site cost management: billing: sub feeder; Data center cost management: billing: sub feeder; Healthcare cost management: billing: sub feeder; Industry cost management: billing: sub feeder; Buildings small building cost management: cost allocation: sub feeder; Buildings medium building cost management: cost allocation: sub feeder; Buildings large building cost management: cost allocation: sub feeder; Buildings multi-site cost management: cost allocation: sub feeder; Data center cost management: cost allocation: sub feeder; Healthcare cost management: cost allocation: sub feeder; Industry cost management: cost allocation: sub feeder
Power quality analysisup to the 15th harmonic
Device applicationPower monitoring; Multi-tariff; Sub billing
Type of measurementActive and reactive power; Apparent power; Current; Voltage; Energy; Power factor; Frequency; Total current harmonic distortion THD (I); Total voltage harmonic distortion THD (U)
supply voltage100...277 V AC 45...65 Hz; 173...480 V AC 45...65 Hz; 100...300 V DC
Network frequency50 Hz; 60 Hz
[In] rated current1 A; 5 A
type of network3P; 3P + N; 1P + N
Power consumption in VA5 VA
Display typeBacklit LCD
Display resolution128 x 96 pixels
Sampling rate32 samples/cycle
Measurement current0.05…6 A; 0.02…1.2 A
Analogue input typeCurrent 0...5 A; Current 0...1 A
Measurement voltage50…330 V AC 45...65 Hz direct; 50…330 V AC 45...65 Hz phase to neutral; 80…570 V AC 45...65 Hz direct; 80…570 V AC 45...65 Hz phase to phase; 570…999000 V AC 45...65 Hz with external VT
Frequency measurement range45…65 Hz
Number of inputs0
Measurement accuracyCurrent 0.3 % 0.5...6 A; Current 0.5 % 0.1...1.2 A; Voltage 0.3 % 50...330 V; Voltage 0.3 % 80...570 V
Accuracy classClass 0.5S active energy conforming to IEC 62053-22; Class 1 active energy conforming to IEC 62053-21; Class 2 reactive energy conforming to IEC 62053-23; Class C active energy conforming to EN 50470-3
Number of outputs1 pulse
Information displayedTariff (4)
Communication port protocol-
Communication port support-
Data recordingTime stamping; 5 alarms; Min/max of instantaneous values
mounting modeClip-on
Mounting supportDIN rail
StandardsBS EN 61557-12; IEC 61557-12; EN 61557-12; BS EN 61326-1; IEC 61326-1; EN 61326-1; BS EN 62052-11; IEC 62052-11; EN 62052-11; BS EN 62053-21; IEC 62053-21; EN 62053-21; BS EN 62053-22; IEC 62053-22; EN 62052-22; BS EN 62053-23; IEC 62053-23; EN 62052-23; BS EN 61010-1; EN 61010-1; IEC 61010-1; UL 61010-1; BS EN 61010-2-30; IEC 61010-2-30; EN 61010-2-30; UL 61010-2-30; ANSI C12.20
Product certificationsCE conforming to IEC 61010-1 (safety); CE conforming to EN 61557-12 (power monitor); CE conforming to EN/IEC 61326-1 (EMC); UKCA conforming to BS EN 61010-1 (safety); UKCA conforming to BS EN 61557-12 (power monitor); UKCA conforming to BS EN 61326-1 (EMC); CULus conforming to EN 61010-1 (safety); CULus conforming to UL 61010-1 (safety); EAC (sub-meter); RCM
Width90 mm
Depth70 mm
Height95 mm
Product weight0.26 kg
Electromagnetic compatibilityElectrostatic discharge level 4 conforming to IEC 61000-4-2; Susceptibility to electromagnetic fields level 3 conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; Surge immunity test level 4 conforming to IEC 61000-4-5; Conducted RF disturbances level 3 conforming to IEC 61000-4-6; Magnetic field at power frequency - test level: 0.5 mT conforming to IEC 61000-4-8; Conducted and radiated emissions class B conforming to EN 55022
Overvoltage categoryIII
IP degree of protectionIP40 front panel: conforming to IEC 60529; IP20 body: conforming to IEC 60529
Relative humidity5…95 % at 50 °C
Pollution degree2
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C
Operating altitude< 3000 m
Compatibility codePM3210
Number of Units in Package 11
Number of Units in Package 216
Country of originCN
Warranty (in months)18
Measured value memoryNo
Power factorYes
Suitable for RJ plugNo
Step angle (cos phi)No
Harmonics measurementNo
Pulse outputNone
CalibratedNo
Max. current (Imax)10 A
Measurement type load profileNo
With communication interface KNXNo
With communication interface M-BusNo
With communication interface RS-485No
ModelMeasurement transformer
Mounting methodDIN rail
Nominal current (In)5 A
Pole typeThree conductor/four conductor
Apparent powerYes
Ampere meterYes
Reactive power meterYes
With rotational speed meterNo
Frequency meterNo
Pulse counterNo
VoltmeterYes
Effective power measurement deviceYes
Sampling frequency3200 Hz
Number of voltage measurement inputs4
Number of current measurement inputs6
Voltage type (supply voltage)AC/DC
DisplayLCD
Remote displayNo
Number of digital outputs1
Supporting protocol for IEC 61850 EthernetNo
Supporting protocol for OPC UA PubSubNo
Supporting protocol for PROFIBUSNo
Supporting protocol for ModbusYes
Supporting protocol for PROFINET IONo
Supporting protocol for other bus systemsNo
With audit logging (audit log)No
With firmware signatureNo
With logging of security events (security event log)Yes
With Role Based Access Control (RBAC)No
Web server with HTTPS transfer protocolNo
Degree of protection (IP), front sideIP40

Properties

MOQ1

Cross-References