| Manufacturer part number (MPN) | ABL6TS100U |
| EAN / GTIN | 3389110880311 |
| Sales unit | pcs |
| Voltage | 230-400 V |
| Range of product | Modicon Transformer Optimized |
| rated power in VA | 1000 VA |
| Product or component type | Safety and isolation transformer |
| Input voltage | 230 V AC single phase, terminal(s): N-L1; 400 V AC phase to phase, terminal(s): L1-L2 |
| Output voltage | 230 V AC |
| Secondary winding | Single |
| Protective cover | Without |
| Ambient air temperature for operation | -20…50 °C |
| Input voltage limits | 207...253 V; 360...440 V |
| Network frequency limits | 47…63 Hz |
| Input voltage tolerance | +/- 15 V |
| Efficiency | 94 % |
| Power dissipation in W | 63.8 W |
| Output sustained overvoltage | 3 % (no load, hot state) |
| Maximum voltage drop at rated load | 5 % |
| No load losses | 26.5 W |
| Short-circuit voltage | 0,0324 |
| Output protection type | Against overload, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection; Against overvoltage, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection; Against short-circuits, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection |
| Connections - terminals | For input connection: screw type terminals, connection capacity: 5 x 4 mm² 11 AWG; For input ground connection: screw type terminals, connection capacity: 1 x 4 mm² 11 AWG; For output connection: screw type terminals, connection capacity: 2 x 4 mm² 11 AWG |
| Marking | CE |
| Fixing mode | By 4 screws diameter: 7 mm on vertical panel, operating position: horizontal; By 4 screws diameter: 7 mm on vertical panel, operating position: vertical; By 4 screws diameter: 7 mm on horizontal panel with derating to 90 % |
| Operating altitude | 3000 m |
| Electrical insulation class | Class B |
| Width | 174.0 mm |
| Height | 138.0 mm |
| Depth | 163.0 mm |
| Product weight | 14.48 kg |
| Product certifications | EAC; UR; DNV-GL |
| Standards | UL 506 |
| IP degree of protection | IP20 |
| Environmental characteristic | EMC conforming to IEC 62041; Safety conforming to EN 61558-1; Safety conforming to EN 61558-2-4 |
| Protective treatment | TC |
| Ambient air temperature for storage | -40…80 °C |
| Overvoltage category | Class I conforming to VDE 0106-1 |
| Dielectric strength | 2000 V between winding and ground; 4000 V between primary and secondary |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 24.000 cm |
| Package 1 Width | 28.000 cm |
| Package 1 Length | 30.000 cm |
| Package 1 Weight | 15.750 kg |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 4 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 71.500 kg |
| Country of origin | CZ |
| Warranty (in months) | 18 |
| Built as safety transformer | Yes |
| Built as isolating transformer | Yes |
| Built as energy saving transformer | No |
| Primary voltage 1 | 230–400 V |
| Primary voltage 2 | 385–415 V |
| Secondary voltage 1 | 230 V |
| Rated apparent power | 1000 VA |
| Type of insulation material according to IEC 85 | B |
| Short-circuit-proof | No |
| Relative short circuit voltage | 3.24 % |
| Degree of protection (IP) | IP20 |
| Ring core | No |
| Suitable for mounting on PCB | No |
| Suitable for distribution board | No |