Schneider Electric Regulated Power Supply, 100-240V AC, 24V 3.1 A, single phase, Optimized ABLS1A24031

Schneider Electric · Control & Automation · Power Supplies · France · se.com
Part Number
ABLS1A24031  ·  HS 8504.40
Schneider Electric Regulated Power Supply, 100-240V AC, 24V 3.1 A, single phase, Optimized ABLS1A24031

Schneider Electric ABLS1A24031 Switchmode power supply optimised for DIN-rail, 24VDC 75W-3,1A output and 100-240VAC supply.

Technical Specifications

Manufacturer part number (MPN)ABLS1A24031
EAN / GTIN3606481500205
Sales unitpcs
Package quantity22 pcs
Voltage24 V
Range of productModicon Power Supply
Product or component typePower supply
Power supply typeRegulated switch mode
Variant optionOptimized
Enclosure materialPlastic
Nominal input voltage100...240 V AC single phase; 100...240 V AC phase to phase; 140...340 V DC
Rated power in W75 W
Output voltage24 V DC
Power supply output current3.13 A
Input voltage limits85...264 V AC without temperature derating; 120...375 V DC without temperature derating
Nominal network frequency50…60 Hz
Network system compatibilityTN; TT; IT
Maximum leakage current1 mA 240 V AC
Input protection typeIntegrated fuse (not interchangeable) 5 A; External protection (recommended) 20 A Curve C; External protection (recommended) 13 A Curve B; External protection (recommended) 10 A Curve C
Inrush current40.0 A at 115 V; 80.0 A at 230 V
Power factor0.55 at 115 V AC; 0.45 at 230 V AC
Efficiency88 % at 230 V AC
Output voltage adjustment21.6...26.4 V
Power dissipation in W15 W
Current consumption< 1.8 A 115 V AC; < 1 A 230 V AC; < 0.8 A 140 V DC
Turn-on time< 1.2 s
Holding time> 20 ms 115 V AC; > 40 ms 230 V AC
Startup with capacitive loads5000 µF
Residual ripple< 120 mV
Meantime between failure [MTBF]700000 h at 25 °C, full load conforming to SR 332
Output protection typeAgainst overload and short-circuits, protection technology: automatic reset; Against over temperature, protection technology: manual reset; Against overvoltage, protection technology: manual reset
Connections - terminalsScrew connection: 0.5...2.5 mm², (20 AWG...14 AWG) for output; Screw connection: 0.75...2.5 mm², (18 AWG...14 AWG) for input
Line and load regulation< 0.5 % at 0 to 100 % load at 25 °C; < 1 % at full voltage range in line at 25 °C
Status LED1 LED (green) output voltage
Depth102 mm
Height123.6 mm
Width27 mm
Product weight0.22 kg
Output couplingParallel; Serial
Mounting supportTop hat type TH35-15 rail conforming to IEC 60715; Top hat type TH35-7.5 rail conforming to IEC 60715; Double-profile DIN rail
SupplySELV conforming to IEC 60950-1; SELV conforming to IEC 60204-1; SELV conforming to IEC 60364-4-41
Dielectric strength3000 V AC with input to output
Service life10 year(s)
Overvoltage categoryII
StandardsIEC 62368-1; EN/IEC 61010-1; EN 61010-2-201; EN/IEC 61204-3; IEC 61000-6-1; IEC 61000-6-2; IEC 61000-6-3; IEC 61000-6-4; IEC 61000-3-2; EN 61000-3-3; UL 62368-1; UL 61010-1; UL 61010-2-201; CSA C22.2 No 62368-1; CSA C22.2 No 61010-1; CSA C22.2 No 61010-2-201
Product certificationsCE; CUL listed; CUL recognized; RCM; CB Scheme; EAC; KC; NEC: class 2
Operating altitude< 5000 m
Shock resistance150 m/s² for 11 ms
IP degree of protectionIP20
Ambient air temperature for operation-20…-10 °C with current derating of 1 % per °C mounting position A < 2000 m; -10…40 °C without derating mounting position A 115 V AC < 2000 m; -10…50 °C without derating mounting position A 230 V AC < 2000 m; 40…70 °C with current derating of 1.67 % per °C mounting position A 115 V AC < 2000 m; 50…70 °C with current derating of 2.5 % per °C mounting position A 230 V AC < 2000 m
Electrical shock protection classClass I
Pollution degree2
Vibration resistance3 mm (f= 2…9 Hz) conforming to IEC 60068-2-6; 10 m/s² (f= 9…200 Hz) conforming to IEC 60068-2-6
Electromagnetic immunityImmunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to IEC 61000-4-2; Immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to IEC 61000-4-2; Immunity to conducted RF disturbances - test level: 15 V/m (80 MHz...2 GHz) conforming to IEC 61000-4-3; Immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to IEC 61000-4-3; Immunity to conducted RF disturbances - test level: 5 V/m (2.7...6 GHz) conforming to IEC 61000-4-3; Immunity to fast transients - test level: 4 kV (on input-output) conforming to IEC 61000-4-4; Surge immunity test - test level: 4 kV (between power supply and earth) conforming to IEC 61000-4-5; Surge immunity test - test level: 3 kV (between phases) conforming to IEC 61000-4-5; Immunity to conducted RF disturbances - test level: 15 V (0.15...80 MHz) conforming to IEC 61000-4-6; Immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8; Immunity to voltage dips conforming to IEC 61000-4-11; Disturbing field emission conforming to EN 55016-2-3; Limits for harmonic current emissions conforming to IEC 61000-3-2; conforming to EN 55016-1-2; conforming to EN 55016-2-1
Electromagnetic emissionConducted emissions conforming to IEC 61000-6-3; Radiated emissions conforming to IEC 61000-6-4
Number of Units in Package 11
Number of Units in Package 222
Number of Units in Package 3528
Country of originTH
Warranty (in months)18
Voltage type (supply voltage)AC
Max. output current 13.1 A
Nominal value output voltage 124 V
Nominal value output current 13.1 A
Power output75 W
Type of electric connectionScrew connection
Wall mounting possibleNo
Built-in width27 mm
Built-in height123.6 mm
SIL according to IEC 61508None
Performance level according to EN ISO 13849-1None
Degree of protection (IP)IP20

Properties

MOQ1

Cross-References

Attached Documents