cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Regulated Power Supply, 100-240V AC, 12V 1 A, single phase, Modular ABLM1A12010

Schneider Electric · Control & Automation · Power Supplies · France · se.com
Part Number
ABLM1A12010  ·  HS 8504.40
Schneider Electric Regulated Power Supply, 100-240V AC, 12V 1 A, single phase, Modular ABLM1A12010

Schneider Electric ABLM1A12010 Switchmode power supply modular for DIN-rail with 12 VDC 12W-1A output and 100-240 VAC supply.

Technical Specifications

Manufacturer part number (MPN)ABLM1A12010
EAN / GTIN3606481500113
Sales unitpcs
Package quantity28 pcs
Voltage12 V
Rated current1 A
Range of productModicon Power Supply
Product or component typePower supply
Power supply typeRegulated switch mode
Variant optionModular
Enclosure materialPlastic
Nominal input voltage100...240 V AC single phase; 100...240 V AC phase to phase
Rated power in W12 W
Output voltage12 V DC
Power supply output current1 A
Input voltage limits90...264 V AC
Nominal network frequency50…60 Hz
Network system compatibilityTN; TT; IT
Maximum leakage current0.25 mA 240 V AC
Input protection typeIntegrated fuse (not interchangeable) 3.15 A; External protection (recommended) 20 A Curve B; External protection (recommended) 20 A Curve C; External protection (recommended) 2 A Curve B; External protection (recommended) 2 A Curve C
Inrush current15 A at 115 V; 30 A at 230 V
Power factor0.51 at 115 V AC; 0.40 at 230 V AC
Efficiency80 % at 115 V AC; 80 % at 230 V AC
Power dissipation in W3 W
Current consumption< 0.4 A 115 V AC; < 0.25 A 230 V AC
Turn-on time< 2 s
Holding time> 10 ms 115 V AC; > 60 ms 230 V AC
Startup with capacitive loads3000 µF
Residual ripple< 100 mV
Meantime between failure [MTBF]3000000 h at 25 °C, full load; 1000000 h at 55 °C, 80 % load
Output protection typeAgainst overload and short-circuits, protection technology: automatic reset; Against over temperature, protection technology: manual reset; Against overvoltage, protection technology: manual reset
Connections - terminalsScrew connection: 0.5...1.5 mm², (20 AWG...16 AWG) without wire end ferrule for input/output; Screw connection: 0.5...1 mm², (20 AWG...18 AWG) with wire end ferrule for input/output
Line and load regulation< 0.5 % at in line; < 1 % at 0 to 100 % load
Status LED1 LED (green) output voltage
Depth55.6 mm
Height91 mm
Width18 mm
Product weight0.101 kg
Output couplingSerial
Mounting supportTop hat type TH35-15 rail conforming to IEC 60715; Top hat type TH35-7.5 rail conforming to IEC 60715; Double-profile DIN rail; panel mounting
SupplySELV conforming to IEC 60950-1; SELV conforming to IEC 60204-1; SELV conforming to IEC 60364-4-41
Dielectric strength3000 V AC input/output
Service life10 year(s)
Overvoltage categoryII
StandardsIEC 62368-1; EN/IEC 61010-1; EN 61010-2-201; EN/IEC 61204-3; IEC 61000-6-1; IEC 61000-6-2; IEC 61000-6-3; IEC 61000-6-4; IEC 61000-3-2; EN 61000-3-3; UL 62368-1; UL 61010-1; UL 61010-2-201; CSA C22.2 No 62368-1; CSA C22.2 No 61010-1; CSA C22.2 No 61010-2-201
Product certificationsCE; CUL listed; CUL recognized; RCM; CB Scheme; EAC; KC; NEC: class 2
Operating altitude< 2000 m overvoltage category III; 2000 m...5000 m overvoltage category II
Shock resistance150 m/s² for 11 ms
IP degree of protectionIP20
Ambient air temperature for operation-25…55 °C without current derating mounting position A < 2000 m; 55…70 °C with current derating of 2.67 % per °C mounting position A < 2000 m
Electrical shock protection classClass II without PE connection
Pollution degree2
Vibration resistance3 mm (f= 2…9 Hz) conforming to IEC 60721-3-3; 10 m/s² (f= 9…200 Hz) conforming to IEC 60721-3-3
Electromagnetic immunityImmunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to IEC 61000-4-2; Immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to IEC 61000-4-2; Electromagnetic field immunity test - test level: 15 V/m (80 MHz...2 GHz) conforming to IEC 61000-4-3; Electromagnetic field immunity test - test level: 5 V/m (2...2.7 GHz) conforming to IEC 61000-4-3; Electromagnetic field immunity test - test level: 5 V/m (2.7...6 GHz) conforming to IEC 61000-4-3; Immunity to fast transients - test level: 4 kV (on input-output) conforming to IEC 61000-4-4; Surge immunity test - test level: 4 kV (between power supply and earth) conforming to IEC 61000-4-5; Surge immunity test - test level: 3 kV (between phases) conforming to IEC 61000-4-5; Immunity to conducted disturbances - test level: 15 V (0.15...80 MHz) conforming to IEC 61000-4-6; Immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8; Immunity to voltage dips - test level: 100 % (1 cycle) conforming to IEC 61000-4-11; Immunity to voltage dips - test level: 60 % (10 cycles) conforming to IEC 61000-4-11; Immunity to voltage dips - test level: 30 % (25 cycles) conforming to IEC 61000-4-11; Disturbing field emission conforming to EN 55016-2-3; Limits for harmonic current emissions conforming to IEC 61000-3-2; conforming to EN 55016-1-2; conforming to EN 55016-2-1
Electromagnetic emissionConducted emissions conforming to IEC 61000-6-3; Radiated emissions conforming to IEC 61000-6-4
Country of originTH
Warranty (in months)18
Voltage type (supply voltage)AC
Max. output current 11 A
Nominal value output voltage 112 V
Nominal value output current 11 A
Power output12 W
Type of electric connectionScrew connection
Wall mounting possibleNo
Built-in width18 mm
Built-in height91 mm
SIL according to IEC 61508None
Performance level according to EN ISO 13849-1None
Degree of protection (IP)IP20

Properties

MOQ1

Cross-References