Schneider Electric Regulated Power Supply, 100...240V AC, 12V 8.5A, single phase, Panel Mount ABLP1A12085

Schneider Electric · Control & Automation · Power Supplies · France · se.com
Part Number
ABLP1A12085  ·  HS 8536.90
Schneider Electric Regulated Power Supply, 100...240V AC, 12V 8.5A, single phase, Panel Mount ABLP1A12085

Schneider Electric ABLP1A12085 Switchmode power supply for bottom mounting with 12 VDC 100W-8,5A output and 100-240 VAC supply.

Technical Specifications

Manufacturer part number (MPN)ABLP1A12085
EAN / GTIN3606481500274
Sales unitpcs
Package quantity19 pcs
Voltage12 V
Range of productModicon Power Supply
Product or component typePower supply
Power supply typeRegulated switch mode
Variant optionPanel mount
Enclosure materialAluminium
Nominal input voltage100...240 V AC single phase
Rated power in W100 W
Output voltage12 V DC
Power supply output current8.5 A
Input voltage limits90...264 V AC
Nominal network frequency50…60 Hz
Network system compatibilityTN; TT; IT
Maximum leakage current1 mA 240 V AC
Input protection typeIntegrated fuse (not interchangeable) 4 A
Inrush current45 A at 115 V; 85 A at 230 V
Power factor0.55 at 115 V AC; 0.45 at 230 V AC
Efficiency88 % at 230 V AC
Output voltage adjustment10.8...13.2 V
Power dissipation in W21 W
Current consumption< 2.3 A 115 V AC; < 1.5 A 230 V AC
Turn-on time< 500 ms
Holding time> 20 ms 115 V AC; > 40 ms 230 V AC
Startup with capacitive loads4000 µF
Residual ripple< 120 mV
Meantime between failure [MTBF]700000 h at 25 °C, full load conforming to SR 332
Output protection typeAgainst overload and short-circuits, protection technology: automatic reset; Against over temperature, protection technology: manual reset; Against overvoltage, protection technology: manual reset
Connections - terminalsScrew connection: 0.75...2.5 mm², (18 AWG...14 AWG) without wire end ferrule; Screw connection: 0.75...1.5 mm², (18 AWG...16 AWG) with wire end ferrule
Line and load regulation< 0.5 % at 0 to 100 % load at 25 °C; < 1 % at full voltage range in line at 25 °C
Status LED1 LED (green) output voltage
Depth129 mm
Height30 mm
Width97 mm
Product weight0.3 kg
Output couplingParallel; Serial
Mounting supportTop hat type TH35-15 rail conforming to IEC 60715; Top hat type TH35-7.5 rail conforming to IEC 60715; Double-profile DIN rail; panel mounting
SupplySELV conforming to IEC 60950-1; SELV conforming to IEC 60204-1; SELV conforming to IEC 60364-4-41
Dielectric strength3750 V AC with input to output
Service life10 year(s)
Overvoltage categoryII
StandardsIEC 62368-1; IEC 61010-1; EN 61010-2-201; EN 61204-3; IEC 61000-6-1; IEC 61000-6-2; IEC 61000-6-3; IEC 61000-6-4; IEC 61000-3-2; EN 61000-3-3; UL 62368-1; UL 61010-1; UL 61010-2-201; CSA C22.2 No 62368-1; CSA C22.2 No 61010-1; CSA C22.2 No 61010-2-201
Product certificationsCE; CULus; EAC; RCM; CB Scheme; KC
Operating altitude5000 m
Shock resistance150 m/s² for 11 ms
IP degree of protectionIP10
Ambient air temperature for operation-30…50 °C without derating mounting position A, B, F, G < 2000 m; 50…70 °C with current derating of 2 % per °C mounting position A, B, F, G < 2000 m
Electrical shock protection classClass I
Pollution degree2
Vibration resistance3 mm (f= 2…9 Hz) conforming to IEC 60068-2-6; 10 m/s² (f= 9…200 Hz) conforming to IEC 60068-2-6
Electromagnetic immunityImmunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to IEC 61000-4-2; Immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to IEC 61000-4-2; Immunity to conducted RF disturbances - test level: 15 V/m (80 MHz...2 GHz) conforming to IEC 61000-4-3; Immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to IEC 61000-4-3; Immunity to conducted RF disturbances - test level: 5 V/m (2.7...6 GHz) conforming to IEC 61000-4-3; Immunity to fast transients - test level: 4 kV (on input-output) conforming to IEC 61000-4-4; Surge immunity test - test level: 4 kV (between power supply and earth) conforming to IEC 61000-4-5; Surge immunity test - test level: 3 kV (between phases) conforming to IEC 61000-4-5; Immunity to conducted RF disturbances - test level: 15 V (0.15...80 MHz) conforming to IEC 61000-4-6; Immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8; Immunity to voltage dips conforming to IEC 61000-4-11; Disturbing field emission conforming to EN 55016-2-3; Limits for harmonic current emissions conforming to IEC 61000-3-2; conforming to EN 55016-1-2; conforming to EN 55016-2-1
Electromagnetic emissionConducted emissions conforming to IEC 61000-6-3; Radiated emissions conforming to IEC 61000-6-4
Number of Units in Package 11
Number of Units in Package 219
Country of originCN
Warranty (in months)18
Voltage type (supply voltage)AC
Max. output current 18.5 A
Nominal value output voltage 112 V
Nominal value output current 18.5 A
Power output21 W
Type of electric connectionScrew connection
Wall mounting possibleNo
Built-in width97 mm
Built-in height30 mm
SIL according to IEC 61508None
Performance level according to EN ISO 13849-1None
Degree of protection (IP)IP10

Properties

MOQ1

Cross-References