Schneider Electric Discrete input module X80 - 32 inputs - 12/24 V DC positive/negative - severe BMXDDI3232H

Schneider Electric · Control & Automation · I/O Modules · France · se.com
Part Number
BMXDDI3232H  ·  HS 8538.90
Schneider Electric Discrete input module X80 - 32 inputs - 12/24 V DC positive/negative - severe BMXDDI3232H

Schneider Electric BMXDDI3232H X80 32-channel input module, 12 / 24VDC Sink/Source Input. For rugged environments.

Technical Specifications

Manufacturer part number (MPN)BMXDDI3232H
EAN / GTIN3606481946720
Sales unitpcs
Package quantity10 pcs
Voltage12-24 V DC
Range of productModicon X80
Product or component typeDiscrete input module
Device applicationIndustrial application in severe environment
Discrete input number32
Discrete input voltage12 V DC for isolated; 24 V DC for isolated
Discrete input logicPositive or negative
Input wiring mode2 or 3 wires
Discrete input current3.3 mA at 12 V DC; 3.3 mA at 24 V DC
Voltage state 1 guaranteed>= 10 V; <= -10 V
Voltage state 0 guaranteed= -5 V
Current state 1 guaranteed>= 2 mA
Current state 0 guaranteed<= 1.5 mA
Input impedance7270 Ohm
Insulation resistance> 10 MOhm 500 V DC
DC typical response time4 ms
DC maximum response time7 ms
Paralleling of outputsYes
Sensor power supply: 19…30 V
Typical current consumption100 mA DC; 7.6 mA at 24 V DC
Current consumption130 mA at 3.3 V DC; at 24 V DC
Power dissipation in W4.7 W
Isolation between channels and bus1500 V for 1 minute
Hot swapping fallbackYes
MTBF reliability2200000 H
Voltage detection threshold19 V DC sensor OK
Local signalling1 LED (green) for module operating (RUN); 1 LED per channel (green) for channel diagnostic; 1 LED (red) for module error (ERR); 1 LED (red) for module I/O
Height134.6 mm
Width32 mm
Depth86 mm
Product weight0.138 kg
IP degree of protectionIP20
Protective treatmentConformal coating
MarkingCE; UKCA; CULus; RCM; EAC
Product certificationsATEX zone 2; IECEx zone 2; CCC Ex zone 2 (pending); CULus HazLoc
StandardsIEC 61131-2
Directives2014/35/EU - low voltage directive; 2014/30/EU - electromagnetic compatibility
Dielectric strength1500 V AC at 50/60 Hz 1 minute, primary/secondary; 1500 V AC at 50/60 Hz 1 minute, between group of channels
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C
Relative humidity5…95 % at -25…70 °C without condensation
Operating altitude0...2000 m; 2000...5000 m with derating
Pollution degree2
Environmental characteristicGas resistant class Gx; Gas resistant class 3C4; Dust resistant class 3S4; Sand resistant class 3S4; Salt resistant level 2; Mold growth resistant class 3B2; Fungal spore resistant class 3B2
Vibration resistance3 gn
Shock resistance30 gn
Number of Units in Package 11
Number of Units in Package 210
Country of originID
Warranty (in months)18
Supply voltage DC24 V
Voltage type (supply voltage)DC
Number of digital inputs32
Digital inputs configurableNo
Digital outputs configurableNo
Input current at signal 13.3 mA
Permitted voltage at input19–30 V
Type of voltage (input voltage)DC
Type of digital outputNone
Permitted voltage at output19–30 V
Type of output voltageDC
Short-circuit protection, outputs availableNo
RedundancyNo
Type of electric connectionPlug-in connection
Time delay at signal change4–7 ms
Suitable for safety functionsNo
SIL according to IEC 61508None
Performance level according to EN ISO 13849-1None
Appendant operation agent (Ex ia)No
Explosion safety category for gasATEX gas-ex-protection, Cat. 3G
Explosion safety category for dustNone