| Manufacturer part number (MPN) | SR3B101FU |
| EAN / GTIN | 3389110549911 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Package quantity | 30 pcs |
| Voltage | 240 V AC |
| Range of product | Zelio Logic |
| Product or component type | Modular smart relay |
| Local display | With |
| Number or control scheme lines | 0…500 with FBD programming; 0…240 with ladder programming |
| Cycle time | 6…90 ms |
| Backup time | 10 years at 25 °C |
| Clock drift | 12 min/year at 0…55 °C; 6 s/month at 25 °C |
| Checks | Program memory on each power up |
| [Us] rated supply voltage | 100...240 V |
| Supply voltage limits | 85…264 V |
| Supply frequency | 50/60 Hz |
| Maximum supply current | 30 mA at 240 V (without extension); 40 mA at 240 V (with extensions); 80 mA at 100 V (with extensions); 80 mA at 100 V (without extension) |
| Power consumption in VA | 12 VA with extensions; 7 VA without extension |
| Isolation voltage | 1780 V |
| Protection type | Against inversion of terminals (control instructions not executed) |
| Discrete input number | 6 |
| Discrete input voltage | 100...240 V AC |
| Discrete input current | 0.6 mA |
| Discrete input frequency | 57...63 Hz; 47...53 Hz |
| Voltage state 1 guaranteed | >= 79 V for discrete input |
| Voltage state 0 guaranteed | <= 40 V for discrete input |
| Current state 1 guaranteed | >= 0.17 mA (discrete input) |
| Current state 0 guaranteed | <= 0.5 mA (discrete input) |
| Input impedance | 350 kOhm for discrete input |
| Number of outputs | 4 relay |
| Output voltage limits | 5...30 V DC (relay output); 24...250 V AC |
| Contacts type and composition | NO for relay output |
| Output thermal current | 8 A for all 4 outputs for relay output |
| Electrical durability | AC-12: 500000 cycles at 230 V, 1.5 A for relay output conforming to IEC 60947-5-1; AC-15: 500000 cycles at 230 V, 0.9 A for relay output conforming to IEC 60947-5-1; DC-12: 500000 cycles at 24 V, 1.5 A for relay output conforming to IEC 60947-5-1; DC-13: 500000 cycles at 24 V, 0.6 A for relay output conforming to IEC 60947-5-1 |
| Switching capacity in mA | >= 10 mA at 12 V (relay output) |
| Operating rate in Hz | 0.1 Hz (at Ie) for relay output; 10 Hz (no load) for relay output |
| Mechanical durability | 10000000 cycles for relay output |
| [Uimp] rated impulse withstand voltage | 4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1 |
| Clock | With |
| Response time | 50 ms with ladder programming (from state 0 to state 1) for discrete input; 50 ms with ladder programming (from state 1 to state 0) for discrete input; 50...255 ms with FBD programming (from state 0 to state 1) for discrete input; 50...255 ms with FBD programming (from state 1 to state 0) for discrete input; 10 ms (from state 0 to state 1) for relay output; 5 ms (from state 1 to state 0) for relay output |
| Connections - terminals | Screw terminals, 1 x 0.2...1 x 2.5 mm² (25 AWG...14 AWG) semi-solid; Screw terminals, 1 x 0.2...1 x 2.5 mm² (25 AWG...14 AWG) solid; Screw terminals, 1 x 0.25...1 x 2.5 mm² (24 AWG...14 AWG) flexible with cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) solid; Screw terminals, 2 x 0.25...2 x 0.75 mm² (24 AWG...18 AWG) flexible with cable end |
| Tightening torque | 0.5 N.m |
| Overvoltage category | III conforming to IEC 60664-1 |
| Product weight | 0.25 kg |
| Immunity to microbreaks | 10 ms |
| Product certifications | GOST; C-Tick; CSA; UL; GL |
| Standards | IEC 61000-4-12; IEC 61000-4-4 level 3; IEC 61000-4-6 level 3; IEC 61000-4-3; IEC 61000-4-2 level 3; IEC 61000-4-5; IEC 61000-4-11; IEC 60068-2-6 Fc; IEC 60068-2-27 Ea |
| IP degree of protection | IP20 (terminal block) conforming to IEC 60529; IP40 (front panel) conforming to IEC 60529 |
| Environmental characteristic | EMC directive conforming to IEC 61000-6-2; EMC directive conforming to IEC 61000-6-3; EMC directive conforming to IEC 61000-6-4; EMC directive conforming to IEC 61131-2 zone B; Low voltage directive conforming to IEC 61131-2 |
| Disturbance radiated/conducted | Class B conforming to EN 55022-11 group 1 |
| Pollution degree | 2 conforming to IEC 61131-2 |
| Ambient air temperature for operation | -20…40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2; -20…55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2 |
| Ambient air temperature for storage | -40…70 °C |
| Operating altitude | 2000 m |
| Maximum altitude transport | 3048 m |
| Relative humidity | 95 % without condensation or dripping water |
| Country of origin | FR |
| Warranty (in months) | 18 |