| Manufacturer part number (MPN) | TM221ME16TG |
| EAN / GTIN | 3606480611322 |
| Sales unit | pcs |
| Package quantity | 24 pcs |
| Output type | PNP |
| Range of product | Modicon M221 |
| Product or component type | Logic controller |
| [Us] rated supply voltage | 24 V DC |
| Discrete input number | 8, discrete input 4 fast input conforming to IEC 61131-2 Type 1 |
| Analogue input number | 2 at 0...10 V |
| Discrete output type | Transistor |
| Discrete output number | 8 transistor 2 fast output |
| Discrete output voltage | 24 V DC |
| Discrete output current | 0.5 A |
| Discrete I/O number | 16 |
| Maximum number of I/O expansion module | 7 (local I/O-Architecture); 14 (remote I/O-Architecture) |
| Supply voltage limits | 20.4…28.8 V |
| Inrush current | 35 A |
| Maximum power consumption in W | 22.9 W at 24 V (with max number of I/O expansion module); 4 W at 24 V (without I/O expansion module) |
| Power supply output current | 0.52 A 5 V for expansion bus; 0.49 A 24 V for expansion bus |
| Discrete input logic | Sink or source (positive/negative) |
| Discrete input voltage | 24 V |
| Discrete input voltage type | DC |
| Analogue input resolution | 10 bits |
| LSB value | 10 mV |
| Conversion time | 1 ms per channel + 1 controller cycle time for analogue input analog input |
| Permitted overload on inputs | +/- 30 V DC for 5 min (maximum) for analog input; +/- 13 V DC (permanent) for analog input |
| Voltage state 1 guaranteed | >= 15 V for input |
| Voltage state 0 guaranteed | <= 5 V for input |
| Discrete input current | 7 mA for discrete input; 5 mA for fast input |
| Input impedance | 100 kOhm for analog input; 3.4 kOhm for input; 4.9 kOhm for fast input |
| Response time | 35 µs turn-off, I2...I5 terminal(s) for input; 5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input; 35 µs turn-on, other terminals terminal(s) for input; 5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input; 100 µs turn-off, other terminals terminal(s) for input; 5 µs turn-on, turn-off, Q0...Q1 terminal(s) for output; 50 µs turn-on, turn-off, Q2...Q3 terminal(s) for output; 300 µs turn-on, turn-off, other terminals terminal(s) for output |
| Configurable filtering time | 0 ms for input; 3 ms for input; 12 ms for input |
| Discrete output logic | Positive logic (source) |
| Maximum current per output common | 4 A |
| Output frequency | 100 kHz for fast output (PWM/PLS mode) at Q0...Q1; 5 kHz for output at Q2...Q3; 0.1 kHz for output at Q4...Q6 |
| Absolute accuracy error | +/- 1 % of full scale for analog input |
| Maximum leakage current | 0.1 mA for transistor output |
| Maximum voltage drop | <1 V |
| Mechanical durability | 20000000 cycles for transistor output |
| Maximum tungsten load | <12 W for output and fast output |
| Protection type | Short-circuit and overload protection with automatic reset; Short-circuit protection on output; Overload and short-circuit protection at 1 A |
| Reset time | 1 s automatic reset |
| Memory capacity | 256 kB for user application and data RAM with 10000 instructions; 256 kB for internal variables RAM |
| Data backed up | 256 kB built-in flash memory for backup of application and data |
| Data storage equipment | 2 GB SD card (optional) |
| Battery type | BR2032 or CR2032X lithium non-rechargeable |
| Backup time | 1 year at 25 °C (by interruption of power supply) |
| Execution time for 1 KInstruction | 0.3 ms for event and periodic task; 0.7 ms for other instruction |
| Execution time per instruction | 0.2 µs Boolean |
| Exct time for event task | 60 µs response time |
| Application structure | 1 cyclic auxiliary task; 8 interrupt tasks; 1 configurable freewheeling/cyclic master task |
| Maximum size of object areas | 512 %M memory bits; 255 %C counters; 8000 %MW memory words; 512 %KW constant words; 255 %TM timers |
| Realtime clock | With |
| Clock drift | <= 30 s/month at 25 °C |
| Regulation loop | Adjustable PID regulator up to 14 simultaneous loops |
| Positioning functions | Position PTO 2 axe(s)pulse/direction mode (100 kHz); Position PTO 1 axe(s)CW/CCW mode (100 kHz) |
| Function available | PLS; Frequency generator; PWM |
| Counting input number | 4 fast input (HSC mode) at 100 kHz 32 bits |
| counter function | Pulse/direction; A/B; Single phase |
| Integrated connection type | USB port with mini B USB 2.0 connector; Non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface ; Ethernet with RJ45 connector |
| Supply | (serial 1)serial link supply: 5 V, <200 mA |
| Transmission rate | 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485; 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232; 480 Mbit/s for USB |
| Communication port protocol | USB port: USB - SoMachine-Network; Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network; Ethernet |
| Port Ethernet | 10BASE-T/100BASE-TX 1 port with 100 m copper cable |
| Communication service | Ethernet/IP adapter; Modbus TCP server; Modbus TCP client; Modbus TCP slave device; DHCP client |
| Local signalling | 1 LED (green) for PWR; 1 LED (green) for RUN; 1 LED (red) for module error (ERR); 1 LED (green) for SD card access (SD); 1 LED (red) for BAT; 1 LED per channel (green) for I/O state; 1 LED (green) for SL; Ethernet network activity (green) for ACT; Ethernet network link (yellow) for Link (Link Status) |
| Electrical connection | terminal block, 3 terminal(s) for connecting the 24 V DC power supply; connector, 4 terminal(s) for analogue inputs; Mini B USB 2.0 connector for a programming terminal; removable spring terminal block, 10 terminal(s) for inputs; removable spring terminal block, 11 terminal(s) for outputs |
| Maximum cable distance between devices | Shielded cable: <10 m for fast input; Unshielded cable: <30 m for output; Unshielded cable: <30 m for digital input; Unshielded cable: <1 m for analog input; Shielded cable: <3 m for fast output |
| Insulation | Between input and internal logic at 500 V AC; Between fast input and internal logic at 500 V AC; Non-insulated between inputs; Between output and internal logic at 500 V AC; Non-insulated between analogue input and internal logic; Non-insulated between analogue inputs |
| Marking | CE |
| Mounting support | Top hat type TH35-15 rail conforming to IEC 60715; Top hat type TH35-7.5 rail conforming to IEC 60715; plate or panel with fixing kit |
| Height | 90 mm |
| Depth | 70 mm |
| Width | 70 mm |
| Product weight | 0.264 kg |
| Standards | IEC 61131-2; UL 508; CAN/CSA C22.2 No. 213; IACS E10; ANSI/ISA 12-12-01 |
| Product certifications | LR; ABS; cULus; DNV-GL; EAC; RCM; CE; UKCA; cULus HazLoc |
| Environmental characteristic | Ordinary and hazardous location |
| Resistance to electrostatic discharge | 8 kV in air conforming to IEC 61000-4-2; 4 kV on contact conforming to IEC 61000-4-2 |
| Resistance to electromagnetic fields | 10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3; 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3; 1 V/m 2...2.7 GHz conforming to IEC 61000-4-3 |
| Resistance to magnetic fields | 30 A/m 50/60 Hz conforming to IEC 61000-4-8 |
| Resistance to fast transients | 2 kV (power lines) conforming to IEC 61000-4-4; 2 kV (relay output) conforming to IEC 61000-4-4; 1 kV (I/O) conforming to IEC 61000-4-4; 1 kV (Ethernet line) conforming to IEC 61000-4-4; 1 kV (serial link) conforming to IEC 61000-4-4 |
| Surge withstand | 2 kV power lines (AC) common mode conforming to IEC 61000-4-5; 2 kV relay output common mode conforming to IEC 61000-4-5; 1 kV I/O common mode conforming to IEC 61000-4-5; 1 kV shielded cable common mode conforming to IEC 61000-4-5; 0.5 kV power lines (DC) differential mode conforming to IEC 61000-4-5; 1 kV power lines (AC) differential mode conforming to IEC 61000-4-5; 1 kV relay output differential mode conforming to IEC 61000-4-5; 0.5 kV power lines (DC) common mode conforming to IEC 61000-4-5 |
| Resistance to conducted disturbances | 10 V 0.15...80 MHz conforming to IEC 61000-4-6; 3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL); 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) |
| Electromagnetic emission | Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz conforming to IEC 55011; Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to IEC 55011; Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to IEC 55011; Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to IEC 55011; Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to IEC 55011; Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to IEC 55011; Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 200…1000 MHz conforming to IEC 55011 |
| Immunity to microbreaks | 10 ms |
| Ambient air temperature for operation | -10…55 °C (horizontal installation); -10…35 °C (vertical installation) |
| Ambient air temperature for storage | -25…70 °C |
| Relative humidity | 10…95 %, without condensation (in operation); 10…95 %, without condensation (in storage) |
| IP degree of protection | IP20 with protective cover in place |
| Pollution degree | <= 2 |
| Operating altitude | 0...2000 m |
| Storage altitude | 0…3000 m |
| Vibration resistance | 3.5 mm at 5…8.4 Hz on symmetrical rail; 3.5 mm at 5…8.4 Hz on panel mounting; 1 gn at 8.4…150 Hz on symmetrical rail; 1 gn at 8.4…150 Hz on panel mounting |
| Shock resistance | 147 m/s² for 11 ms |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 24 |
| Number of Units in Package 3 | 288 |
| Country of origin | TW |
| Warranty (in months) | 18 |
| Model | Compact |
| Number of digital inputs | 8 |
| Number of digital outputs | 8 |
| Number of analogue inputs | 2 |
| Voltage type (supply voltage) | DC |
| Type of memory | RAM |
| Memory size | 512 kByte |
| Processing time (1K, binary operation) | 0.2 ms |
| Max. number of addressable analogue I/O-ports | 114 |
| Max. number of addressable digital I/O-ports | 264 |
| Number of HW-interfaces industrial Ethernet | 1 |
| Number of HW-interfaces RS-232 | 1 |
| Number of HW-interfaces RS-485 | 1 |
| Number of HW-interfaces USB | 1 |
| Explosion safety category for gas | None |
| Explosion safety category for dust | None |
| Max. number of time switches | 255 |
| Performance level according to EN ISO 13849-1 | None |
| Long-Term Evolution (LTE) | No |
| SIL according to IEC 61508 | None |