cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Variable speed drive, Altivar Process ATV900, ATV930, 132 kW, 380...480 V, with braking unit, IP20 ATV930C13N4

Schneider Electric · Drives & Controllers · Variable Frequency Drives · France · se.com
Part Number
ATV930C13N4  ·  HS 8504.40
Schneider Electric Variable speed drive, Altivar Process ATV900, ATV930, 132 kW, 380...480 V, with braking unit, IP20 ATV930C13N4

Schneider Electric ATV930C13N4 — Altivar variable-frequency drive. IGBT variable-frequency drive for AC motor speed control. Variable-frequency drive for pump & ventilation IP00 132KW 400V.

Technical Specifications

Manufacturer part number (MPN)ATV930C13N4
EAN / GTIN3606481490391
HS code8504.40
Sales unitpcs
IP ratingIP00
Power132 kW
Range of productAltivar Process ATV900
Product specific applicationProcess for industrial
Product or component typeVariable speed drive
VariantStandard version; With braking chopper
Device applicationIndustrial application
Product destinationSynchronous motors; Asynchronous motors
Network number of phases3 phases; Single phase
mounting modeWall mount
Continuous output current250 A at 4 kHz for normal duty; 211 A at 4 kHz for heavy duty
Communication port protocolEthernet IP/Modbus TCP; Modbus
option moduleSlot A: communication module for Profibus DP V1; Slot A: communication module for PROFINET; Slot A: communication module for DeviceNet; Slot A: communication module for EtherCAT; Slot A: communication module for CANopen daisy chain RJ45; Slot A: communication module for CANopen SUB-D 9; Slot A: communication module for CANopen screw terminals; Slot A/slot B/slot C: digital and analog I/O extension module; Slot A/slot B/slot C: output relay extension module; Slot B: 5/12 V digital encoder interface module; Slot B: analog encoder interface module; Slot B: resolver encoder interface module
[Us] rated supply voltage380...480 V - 15...10 %
Relative symmetric mains voltage tolerance10 %
Relative symmetric network frequency tolerance5 %
nominal output current250.0 A
Motor power kW132.0 kW for normal duty; 110.0 kW for heavy duty
EMC filterIntegrated; With EMC plate option
IP degree of protectionIP21
Degree of protectionUL type 1
Electrical connectionLine side: screw terminal 2 x 70...3 x 120 mm²/2 x 2/0 AWG...2 x 300 kcmil; DC bus: screw terminal 0.5...1.5 mm²/20 AWG...16 AWG; Control: screw terminal 0.5...1.5 mm²/20 AWG...16 AWG
Transmission rate10/100 Mbit/s for Ethernet IP/Modbus TCP; 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial
Data format8 bits, configurable odd, even or no parity for Modbus serial
Type of polarizationNo impedance for Modbus serial
Number of addresses1…247 for Modbus serial
Local signallingLocal diagnostic: 3 LEDs (mono/dual colour); 5 LEDs (dual colour); 2 LEDs (dual colour); 1 LED (red)
IsolationBetween power and control terminals
Discrete input number10
Relay output typeConfigurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles; Configurable relay logic R2: sequence relay NO electrical durability 1000000 cycles; Configurable relay logic R3: sequence relay NO electrical durability 1000000 cycles
Physical interfaceEthernet; 2-wire RS 485
Connector type2 RJ45; 1 RJ45
Method of accessSlave Modbus TCP
Transmission frameRTU
4 quadrant operation possibleTrue
Asynchronous motor control profileConstant torque standard; Variable torque standard; Optimized torque mode
Synchronous motor control profilePermanent magnet motor; Synchronous reluctance motor
Maximum output frequency599 Hz
Acceleration and deceleration rampsLinear adjustable separately from 0.01...9999 s; S, U or customized
Motor slip compensationAdjustable; Automatic whatever the load; Can be suppressed; Not available in permanent magnet motor law
Switching frequency1...8 kHz adjustable; 2.5...8 kHz with derating factor
Nominal switching frequency2.5 kHz
Braking to standstillBy DC injection
Brake chopper integratedTrue
Line current237.0 A at 380 V (normal duty); 201.0 A at 380 V (heavy duty); 213.0 A at 480 V (normal duty); 165.0 A at 480 V (heavy duty)
Maximum input current237.0 A
Maximum output voltage480.0 V
Apparent power161.4 kVA at 380...480 V (normal duty); 121.8 kVA at 380...480 V (heavy duty)
Maximum transient current300 A during 60 s (normal duty); 317 A during 60 s (heavy duty)
Network frequency50...60 Hz
Prospective line Isc50 kA
Base load current at high overload211.0 A
Base load current at low overload250.0 A
With safety function Safely Limited Speed (SLS)True
With safety function Safe brake management (SBC/SBT)True
With safety function Safe Operating Stop (SOS)False
With safety function Safe Position (SP)False
With safety function Safe programmable logicFalse
With safety function Safe Speed Monitor (SSM)False
With safety function Safe Stop 1 (SS1)True
With sft fct Safe Stop 2 (SS2)False
With safety function Safe torque off (STO)True
With safety function Safely Limited Position (SLP)False
With safety function Safe Direction (SDI)False
Protection typeThermal protection: motor; Safe torque off: motor; Motor phase break: motor; Thermal protection: drive; Safe torque off: drive; Overheating: drive; Overcurrent between output phases and earth: drive; Overload of output voltage: drive; Short-circuit protection: drive; Motor phase break: drive; Overvoltages on the DC bus: drive; Line supply overvoltage: drive; Line supply undervoltage: drive; Line supply phase loss: drive; Overspeed: drive; Break on the control circuit: drive
Quantity per set1
Width320 mm
Height1205 mm
Depth393 mm
Product weight104 kg
Insulation resistance> 1 MOhm 500 V DC for 1 minute to earth
Noise level69.9 dB conforming to 86/188/EEC
Vibration resistance1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6; 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
Shock resistance6 gn for 11 ms conforming to IEC 60068-2-27
Environmental characteristicChemical pollution resistance class 3C3 conforming to IEC 60721-3-3; Dust pollution resistance class 3S3 conforming to IEC 60721-3-3
Relative humidity5…95 % without condensation conforming to IEC 60068-2-3
Ambient air temperature for operation-15…50 °C (without derating); 50…60 °C (with derating factor)
Operating positionVertical +/- 10 degree
Product certificationsUL; CSA; TÜV
MarkingCE
StandardsUL 508C; IEC 61800-3; IEC 61800-5-1; IEC 61000-3-12; IEC 60721-3; IEC 61508; IEC 13849-1
Maximum THDI<48 % full load conforming to IEC 61000-3-12
Assembly styleEnclosed
Electromagnetic compatibilityElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5; Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Environmental class (during operation)Class 3C3 according to IEC 60721-3-3; Class 3S3 according to IEC 60721-3-3
Maximum acceleration under shock impact (during operation)150 m/s² at 11 ms
Maximum deflection under vibratory load (during operation)1.5 mm at 2...13 Hz
Permitted relative humidity (during operation)Class 3K5 according to EN 60721-3
Overvoltage categoryIII
Regulation loopAdjustable PID regulator
Pollution degree2
Ambient air transport temperature-25…70 °C
Ambient air temperature for storage-25…70 °C
Country of originCN
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents