| Manufacturer part number (MPN) | ATV930C13N4 |
| EAN / GTIN | 3606481490391 |
| HS code | 8504.40 |
| Sales unit | pcs |
| IP rating | IP00 |
| Power | 132 kW |
| Range of product | Altivar Process ATV900 |
| Product specific application | Process for industrial |
| Product or component type | Variable speed drive |
| Variant | Standard version; With braking chopper |
| Device application | Industrial application |
| Product destination | Synchronous motors; Asynchronous motors |
| Network number of phases | 3 phases; Single phase |
| mounting mode | Wall mount |
| Continuous output current | 250 A at 4 kHz for normal duty; 211 A at 4 kHz for heavy duty |
| Communication port protocol | Ethernet IP/Modbus TCP; Modbus |
| option module | Slot A: communication module for Profibus DP V1; Slot A: communication module for PROFINET; Slot A: communication module for DeviceNet; Slot A: communication module for EtherCAT; Slot A: communication module for CANopen daisy chain RJ45; Slot A: communication module for CANopen SUB-D 9; Slot A: communication module for CANopen screw terminals; Slot A/slot B/slot C: digital and analog I/O extension module; Slot A/slot B/slot C: output relay extension module; Slot B: 5/12 V digital encoder interface module; Slot B: analog encoder interface module; Slot B: resolver encoder interface module |
| [Us] rated supply voltage | 380...480 V - 15...10 % |
| Relative symmetric mains voltage tolerance | 10 % |
| Relative symmetric network frequency tolerance | 5 % |
| nominal output current | 250.0 A |
| Motor power kW | 132.0 kW for normal duty; 110.0 kW for heavy duty |
| EMC filter | Integrated; With EMC plate option |
| IP degree of protection | IP21 |
| Degree of protection | UL type 1 |
| Electrical connection | Line side: screw terminal 2 x 70...3 x 120 mm²/2 x 2/0 AWG...2 x 300 kcmil; DC bus: screw terminal 0.5...1.5 mm²/20 AWG...16 AWG; Control: screw terminal 0.5...1.5 mm²/20 AWG...16 AWG |
| Transmission rate | 10/100 Mbit/s for Ethernet IP/Modbus TCP; 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial |
| Data format | 8 bits, configurable odd, even or no parity for Modbus serial |
| Type of polarization | No impedance for Modbus serial |
| Number of addresses | 1…247 for Modbus serial |
| Local signalling | Local diagnostic: 3 LEDs (mono/dual colour); 5 LEDs (dual colour); 2 LEDs (dual colour); 1 LED (red) |
| Isolation | Between power and control terminals |
| Discrete input number | 10 |
| Relay output type | Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles; Configurable relay logic R2: sequence relay NO electrical durability 1000000 cycles; Configurable relay logic R3: sequence relay NO electrical durability 1000000 cycles |
| Physical interface | Ethernet; 2-wire RS 485 |
| Connector type | 2 RJ45; 1 RJ45 |
| Method of access | Slave Modbus TCP |
| Transmission frame | RTU |
| 4 quadrant operation possible | True |
| Asynchronous motor control profile | Constant torque standard; Variable torque standard; Optimized torque mode |
| Synchronous motor control profile | Permanent magnet motor; Synchronous reluctance motor |
| Maximum output frequency | 599 Hz |
| Acceleration and deceleration ramps | Linear adjustable separately from 0.01...9999 s; S, U or customized |
| Motor slip compensation | Adjustable; Automatic whatever the load; Can be suppressed; Not available in permanent magnet motor law |
| Switching frequency | 1...8 kHz adjustable; 2.5...8 kHz with derating factor |
| Nominal switching frequency | 2.5 kHz |
| Braking to standstill | By DC injection |
| Brake chopper integrated | True |
| Line current | 237.0 A at 380 V (normal duty); 201.0 A at 380 V (heavy duty); 213.0 A at 480 V (normal duty); 165.0 A at 480 V (heavy duty) |
| Maximum input current | 237.0 A |
| Maximum output voltage | 480.0 V |
| Apparent power | 161.4 kVA at 380...480 V (normal duty); 121.8 kVA at 380...480 V (heavy duty) |
| Maximum transient current | 300 A during 60 s (normal duty); 317 A during 60 s (heavy duty) |
| Network frequency | 50...60 Hz |
| Prospective line Isc | 50 kA |
| Base load current at high overload | 211.0 A |
| Base load current at low overload | 250.0 A |
| With safety function Safely Limited Speed (SLS) | True |
| With safety function Safe brake management (SBC/SBT) | True |
| With safety function Safe Operating Stop (SOS) | False |
| With safety function Safe Position (SP) | False |
| With safety function Safe programmable logic | False |
| With safety function Safe Speed Monitor (SSM) | False |
| With safety function Safe Stop 1 (SS1) | True |
| With sft fct Safe Stop 2 (SS2) | False |
| With safety function Safe torque off (STO) | True |
| With safety function Safely Limited Position (SLP) | False |
| With safety function Safe Direction (SDI) | False |
| Protection type | Thermal protection: motor; Safe torque off: motor; Motor phase break: motor; Thermal protection: drive; Safe torque off: drive; Overheating: drive; Overcurrent between output phases and earth: drive; Overload of output voltage: drive; Short-circuit protection: drive; Motor phase break: drive; Overvoltages on the DC bus: drive; Line supply overvoltage: drive; Line supply undervoltage: drive; Line supply phase loss: drive; Overspeed: drive; Break on the control circuit: drive |
| Quantity per set | 1 |
| Width | 320 mm |
| Height | 1205 mm |
| Depth | 393 mm |
| Product weight | 104 kg |
| Insulation resistance | > 1 MOhm 500 V DC for 1 minute to earth |
| Noise level | 69.9 dB conforming to 86/188/EEC |
| Vibration resistance | 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6; 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 6 gn for 11 ms conforming to IEC 60068-2-27 |
| Environmental characteristic | Chemical pollution resistance class 3C3 conforming to IEC 60721-3-3; Dust pollution resistance class 3S3 conforming to IEC 60721-3-3 |
| Relative humidity | 5…95 % without condensation conforming to IEC 60068-2-3 |
| Ambient air temperature for operation | -15…50 °C (without derating); 50…60 °C (with derating factor) |
| Operating position | Vertical +/- 10 degree |
| Product certifications | UL; CSA; TÜV |
| Marking | CE |
| Standards | UL 508C; IEC 61800-3; IEC 61800-5-1; IEC 61000-3-12; IEC 60721-3; IEC 61508; IEC 13849-1 |
| Maximum THDI | <48 % full load conforming to IEC 61000-3-12 |
| Assembly style | Enclosed |
| Electromagnetic compatibility | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5; Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
| Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3; Class 3S3 according to IEC 60721-3-3 |
| Maximum acceleration under shock impact (during operation) | 150 m/s² at 11 ms |
| Maximum deflection under vibratory load (during operation) | 1.5 mm at 2...13 Hz |
| Permitted relative humidity (during operation) | Class 3K5 according to EN 60721-3 |
| Overvoltage category | III |
| Regulation loop | Adjustable PID regulator |
| Pollution degree | 2 |
| Ambient air transport temperature | -25…70 °C |
| Ambient air temperature for storage | -25…70 °C |
| Country of origin | CN |
| Warranty (in months) | 18 |