cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Complete selector switch, Harmony XB4, Explosive atmosphere, swith 3 positions spring return XB4BD53GEX

Schneider Electric · Control & Automation · Pushbuttons & Pilot Lights · France · se.com
Part Number
XB4BD53GEX  ·  HS 8536.90
Schneider Electric Complete selector switch, Harmony XB4, Explosive atmosphere, swith 3 positions spring return XB4BD53GEX

Schneider Electric XB4BD53GEX — Harmony XB4 22 mm command actuator. Metal or plastic 22 mm cutout push-button, selector or indicator.

Technical Specifications

Manufacturer part number (MPN)XB4BD53GEX
EAN / GTIN3606489485733
HS code8536.90
Sales unitpcs
Range of productHarmony XB4
Product or component typeComplete selector switch
Device short nameXB4
Bezel materialChromium plated metal
Fixing collar materialZamak
Mounting diameter22 mm
Sale per indivisible quantity1
Dust zoneZone 21 - 22
Gas zoneZone 1 - 2
Type of operatorTo centre spring return
Operator profileBlack standard handle
Contacts type and composition2 NO
Width46.2 mm
Height30 mm
Depth85 mm
Product weight0.114 kg
Device mountingFixing hole - diameter: 22.5 mm +/- 0.2 mm conforming to IEC 60947-1
Fixing center>= 30 x 40 mm (support panel) - thickness: 1…6 mm
Embedding depth58 mm
MarkingEx tb IIIC Db; Ex db eb IIC Gb; II 2 GD
Shape of signaling unit headRound
Operator position information3 positions +/- 45°
Contact operationSlow-break
Contacts usageStandard contacts
Positive openingWithout
Mechanical durability5000000 cycles
Connections - terminalsScrew clamp terminals, 2 x 1.5 mm² with cable end conforming to IEC 60947-1; Screw clamp terminals, 1 x 2.5 mm² without cable end conforming to IEC 60947-1
Tightening torque0.8…1.2 N.m conforming to IEC 60947-1
[Ith] conventional free air thermal current10 A conforming to IEC 60947-5-1
[Ui] rated insulation voltage415 V
[Ie] rated operational current1.9 A at 380 V, AC, A600 conforming to IEC 60947-5-1; 3 A at 240 V, AC, A600 conforming to IEC 60947-5-1; 6 A at 120 V, AC, A600 conforming to IEC 60947-5-1; 0.27 A at 250 V, DC, Q300 conforming to IEC 60947-5-1; 0.55 A at 125 V, DC, Q300 conforming to IEC 60947-5-1; 2.87 A at 24 V, DC, Q300 conforming to IEC 60947-5-1
Protective treatmentTH
Ambient air temperature for storage-40…70 °C
Ambient air temperature for operation-20…75 °C
IP degree of protectionIP65 conforming to IEC 60529
StandardsIEC 60079-0:2009; EN/IEC 60079-1:2009; IEC 60079-7:2009; IEC 60079-31:2009; UL 60079-0; UL 60079-1; UL 60079-31; ANSI/ISA 12.12.01; CSA C22.2 No 213
Product certificationsINERIS 04ATEX9004U
Number of Units in Package 11
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents