| Manufacturer part number (MPN) | LV429805 |
| EAN / GTIN | 3606480007569 |
| Sales unit | pcs |
| Lifecycle status | Phased out |
| Rated current | 100 A |
| Number of poles | 4P |
| Range | ComPact |
| Product name | ComPact NSX |
| Range of product | ComPact NSX100...250 |
| Device short name | NSX100N |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Protected poles description | 3t + N/2; 3t; 4t |
| Neutral position | Left |
| [In] rated current | 100 A at 40 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| [Icu] rated ultimate short-circuit breaking capacity | 85 kA at 240 V AC 50/60 Hz conforming to UL 508; 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 20 kA at 600 V AC 50/60 Hz conforming to UL 508; 50 kA at 480 V AC 50/60 Hz conforming to UL 508; 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| Performance level | N 50 kA 415 V AC |
| Trip unit name | MicroLogic 2.2 |
| Trip unit technology | Electronic |
| Trip unit protection functions | LSoI |
| Control type | Toggle |
| Circuit breaker mounting mode | Fixed |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Ics] rated service short-circuit breaking capacity | 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 50000 cycles |
| Electrical durability | 10000 cycles at 690 V In; 20000 cycles at 690 V In/2; 30000 cycles at 440 V In; 50000 cycles at 440 V In/2 |
| Mounting support | Backplate |
| Upside connection | Front |
| Downside connection | Front |
| Connection pitch | 35 mm |
| Protection type | L : for overload protection (long time); So : for short time short-circuit protection with fixed delay; I : for instantaneous short-circuit protection |
| Trip unit rating | 100 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 40...100 A |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 11 s at 7.2 x Ir; 16 s at 6 x Ir; 400 s at 1.5 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Fixed |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 1500 A |
| Earth-leakage protection | Without |
| Neutral protection settings | 0.5 x Ir (3t + N/2); 1 x Ir (4t); No protection (3t) |
| Zone selective interlocking ZSI | Without |
| Number of slots for electrical auxiliaries | 5 slot(s) |
| Local signalling | Flashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload |
| Width (W) | 140 mm |
| Height (H) | 161 mm |
| Depth (D) | 86 mm |
| Product weight | 2.4 kg |
| Standards | EN/IEC 60947 |
| Product certifications | CCC; EAC; Marine |
| Overvoltage category | Class II |
| Electrical shock protection class | Class II |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0...2000 m without derating; 2000 m...5000 m with derating |
| Country of origin | FR |
| Warranty (in months) | 18 |
| Rated permanent current Iu | 100 A |
| With integrated under voltage release | No |
| Overload release current setting | 40–100 A |
| Rated voltage | 690 V |
| Degree of protection (IP) | IP40 |
| Position of connection for main current circuit | Front side |
| Motor drive integrated | No |
| Type of electrical connection of main circuit | Screw connection |
| Type of control element | Wing knob |
| With switched-off indicator | Yes |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz | 50 kA |
| Adjustment range short-term delayed short-circuit release | 60–1000 A |
| Adjustment range undelayed short-circuit release | 1500 A |
| Suitable for DIN rail (top hat rail) mounting | No |
| Integrated earth fault protection | No |
| Motor drive optional | Yes |
| Device construction | Built-in device fixed built-in technique |
| DIN rail (top hat rail) mounting optional | Yes |
| Complete device with protection unit | Yes |