cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Trip unit MicroLogic Vigi 7.2E, ComPacT NSX100/160/250, 4 poles, basic and earth leakage protections, energy meter, 100A C1047E100

Schneider Electric · Electrical Components · Circuit Breaker Accessories · France · se.com
Part Number
C1047E100  ·  HS 8536.90
Schneider Electric Trip unit MicroLogic Vigi 7.2E, ComPacT NSX100/160/250, 4 poles, basic and earth leakage protections, energy meter, 100A C1047E100

Schneider Electric C1047E100 Protection for Circuit breaker ComPacT NSX100-250-electronic-energy metering-earth fault-Micrologic 7.2E 100A 4p.

Technical Specifications

Manufacturer part number (MPN)C1047E100
EAN / GTIN3606481993892
HS code8536.90
Sales unitpcs
Package quantity10 pcs
Rated current100 A
RangeComPacT
Range of productComPacT NSX100...250
Product or component typeTrip unit
Trip unit nameMicroLogic 7.2 E
Trip unit technologyElectronic
Range compatibilityComPacT NSX160; ComPacT NSX100; ComPacT NSX250
Device applicationDistribution
Poles description4P
Protected poles description3D + N/2; 4D; 3D + OSN; 3D
Neutral positionLeft
Trip unit protection functionsLSIR
Protection typeL : for overload protection (long time); S : for short time short-circuit protection; I : for instantaneous short-circuit protection; R : for earth-leakage protection
Trip unit rating100 A at 40 °C
[Ue] rated operational voltage440 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Circuit breaker mounting modeFixed
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range40...100 A
Long-time protection delay adjustment type trAdjustable
[tr] long-time protection delay adjustment range15…400 s at 1.5 x Ir; 0.35…11 s at 7.2 x Ir; 0.5…16 s at 6 x Ir
Neutral protection settings0.5 x Ir (3D + N/2); 1 x Ir (4D); 1.6 x Ir (3D + OSN); No protection (3D)
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdAdjustable
[tsd] Short-time protection delay adjustment range0…0.4 s I²t=off; 0.1…0.4 s I²t=on
Instantaneous protection pick-up adjustment type IiAdjustable
[Ii] instantaneous protection pick-up adjustment range1.5...15 x In
Earth-leakage protectionIntegrated
Earth-leakage protection classClass A
Earth-leakage protection sensitity adjustment type IΔnAdjustable
[IΔn] earth-leakage protection sensitivity adjustment range0.03 A; 0.1 A; 0.3 A; 0.5 A; 1 A; 3 A; 5 A
Earth-leakage protection specific modeOFF using the IΔn rotary switch
Earth-leakage protection time delay adjustement type ΔtAdjustable
[Δt] Earth-leakage protection time delay adjustment range0 ms; 60 ms; 150 ms; 500 ms; 1 s
Zone selective interlocking ZSIWithout
Local signallingFlashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload
Display typeLCD display
Type of measurementEnergy meter
Communication of dataMaximeters/minimeters; Maintenance indicators; Test reports; Demand current and power; Time-stamped histories and event tables; Earth leakage current; Energy metering; Protection and alarm settings; Power quality; Instantaneous and demand values
StandardsEN/IEC 60947-2
Electrical shock protection classClass II
Pollution degree3 conforming to IEC 60947-1
IP degree of protectionIP40 conforming to IEC 60529
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents