Schneider Electric Circuit breaker, ComPacT NSXm 63B, 25KA/415VAC, 3 poles, MicroLogic 4.1 trip unit 25A, EverLink lugs C11B34V025L

Schneider Electric · Electrical Components · Moulded Case Circuit Breakers · France · se.com
Part Number
C11B34V025L  ·  HS 8536.90
Schneider Electric Circuit breaker, ComPacT NSXm 63B, 25KA/415VAC, 3 poles, MicroLogic 4.1 trip unit 25A, EverLink lugs C11B34V025L

Schneider Electric C11B34V025L Circuit breaker ComPacT NSXmB 50kA/230V 25kA/400V-protection with residual current protection-Micrologic 4.1 25A 3p Everlink.

Technical Specifications

Manufacturer part number (MPN)C11B34V025L
EAN / GTIN3606481992529
HS code8536.90
Sales unitpcs
Rated current25 A
RangeComPacT
Product nameComPacT NSXm
Device short nameNSXm 63B
Product or component typeEarth leakage circuit breaker
Device applicationDistribution
Poles description3P
Protected poles description3D
[In] rated current25 A at 40 °C
[Ue] rated operational voltage440 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
[Icu] rated ultimate short-circuit breaking capacity25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2; 16 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
Performance levelB 25 kA 415 V AC
Trip unit nameMicroLogic 4.1
Trip unit technologyElectronic
Trip unit protection functionsLSoIR
Control typeToggle
Circuit breaker mounting modeFixed
[Ui] rated insulation voltage500 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service short-circuit breaking capacity25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2; 16 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability20000 cycles
Electrical durability20000 cycles at 440 V In/2; 10000 cycles at 440 V In
Power dissipation per pole1.5 W
Mounting supportBackplate
Mounting positionHorizontal and vertical; Flat on the back
Upside connectionFront
Downside connectionFront
Connection terminals1 Everlink lug wire size 2.5…70 mm², fine stranded copper; 1 Everlink lug wire size 2.5…95 mm², rigid or stranded aluminium/copper
Connection pitch35 mm with spreaders; 27 mm without spreaders
9 mm pitches9 module
Trip unit rating25 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range10...25 A
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range200 s at 1.5 x Ir; 8 s at 6 x Ir; 5 s at 7.2 x Ir
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range375 A
Earth-leakage protectionIntegrated
Earth-leakage protection classClass A; Class AC
Earth-leakage protection sensitity adjustment type IΔnAdjustable
[IΔn] earth-leakage protection sensitivity adjustment range30 mA; 100 mA; 300 mA; 500 mA; 1 A; 3 A; 5 A
Earth-leakage sensitivity30 mA for class A; 100 mA for class A; 300 mA for class A; 500 mA for class A; 1 A for class A; 30 mA for class AC; 100 mA for class AC; 300 mA for class AC; 500 mA for class AC; 1 A for class AC; 3 A for class AC; 5 A for class AC
Earth-leakage protection time delay adjustement type ΔtAdjustable
[Δt] Earth-leakage protection time delay adjustment range0 ms; 60 ms; 150 ms; 500 ms; 1000 ms
Number of slots for electrical auxiliaries1 slot(s) for auxiliary switch OF; 1 slot(s) for alarm switch SD; 1 slot(s) for voltage release MN or MX
Local signallingFlag (green) for presence of auxiliary contacts
Width (W)108 mm
Height (H)144 mm
Depth (D)80 mm
Product weight1.63 kg
ColourGrey (RAL 7016)
StandardsEN/IEC 60947-2
Overvoltage categoryIV
Electrical shock protection classClass II on front face
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C
Relative humidity0…95 %
Operating altitude2000 m without derating; 5000 m with derating
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents