Schneider Electric Circuit breaker, ComPacT NSXm 63B, 25KA/415VAC, 4 poles 4D (neutral fully protected), TMD trip unit 32A, lugs/busbars C11B4TM032B

Schneider Electric · Electrical Components · Moulded Case Circuit Breakers · France · se.com
Part Number
C11B4TM032B  ·  HS 8536.90
Schneider Electric Circuit breaker, ComPacT NSXm 63B, 25KA/415VAC, 4 poles 4D (neutral fully protected), TMD trip unit 32A, lugs/busbars C11B4TM032B

Schneider Electric C11B4TM032B Circuit breaker ComPacT NSXm B 50kA/230V 25kA/400V-with thermomagnetic protection-TM32D 4p bolt 32A.

Technical Specifications

Manufacturer part number (MPN)C11B4TM032B
EAN / GTIN3606481990488
HS code8536.90
Sales unitpcs
Trip unitTM32D
RangeComPacT
Product nameComPacT NSXm
Device short nameNSXm 63B
Product or component typeCircuit breaker
Device applicationDistribution
Poles description4P
Protected poles description4D
Neutral positionLeft
[In] rated current32 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
[Icu] rated ultimate short-circuit breaking capacity50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2; 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Performance levelB 25 kA 415 V AC
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Trip unit protection functionsLI
Control typeToggle
Circuit breaker mounting modeFixed
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service short-circuit breaking capacity50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2; 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability20000 cycles
Electrical durability20000 cycles at 440 V In/2; 10000 cycles at 440 V In; 10000 cycles at 690 V In/2; 5000 cycles at 690 V In
Power dissipation per pole3.3 W
Mounting supportBackplate
Mounting positionHorizontal and vertical; Flat on the back
Upside connectionFront
Downside connectionFront
Connection terminalscompression lug/busbar
Connection pitch35 mm with spreaders; 27 mm without spreaders
9 mm pitches12 module
Trip unit rating32 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Long-time protection delay adjustment type trFixed
Neutral protection settings1 x Ir (4D)
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range600 A
Earth-leakage protectionWithout
Number of slots for electrical auxiliaries1 slot(s) for auxiliary switch OF; 1 slot(s) for alarm switch SD; 1 slot(s) for voltage release MN or MX
Local signallingFlag (green) for presence of auxiliary contacts
Width (W)108 mm
Height (H)137 mm
Depth (D)80 mm
Product weight1.42 kg
ColourGrey (RAL 7016)
StandardsEN/IEC 60947-2
Overvoltage categoryIII
Electrical shock protection classClass I on front face
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Relative humidity0…95 %
Operating altitude2000 m without derating; 5000 m with derating
Number of Units in Package 11
Number of Units in Package 26
Number of Units in Package 348
Warranty (in months)18

Properties

MOQ1

Cross-References