| Manufacturer part number (MPN) | C63R36M500 |
| EAN / GTIN | 3606481988881 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Rated current | 500 A |
| Number of poles | 3P |
| Range | ComPacT |
| Product name | ComPacT NSX |
| Device short name | NSX630R |
| Product or component type | Circuit breaker |
| Device application | Motor protection |
| Poles description | 3P |
| Protected poles description | 3D |
| [In] rated current | 500 A at 65 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| Breaking capacity | 200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity code | R 200 kA 415 V AC |
| Trip unit name | MicroLogic 6.3 E-M |
| Trip unit technology | Electronic |
| Trip unit protection functions | LSIG |
| Control type | Toggle |
| Circuit breaker mounting mode | Fixed |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Ics] rated service breaking capacity | 200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 15000 cycles |
| Electrical durability | 8000 cycles at 440 V In/2; 4000 cycles at 440 V In; 6000 cycles at 690 V In/2; 2000 cycles at 690 V In |
| Power dissipation per pole | 39.7 W |
| Mounting support | Backplate |
| Mounting position | Horizontal and vertical; Flat on the back |
| Upside connection | Front |
| Downside connection | Front |
| Connection pitch | 45 mm |
| Protection type | L : for overload protection (long time); So : for short time short-circuit protection; I : for instantaneous short-circuit protection; G : for ground fault protection |
| Trip unit rating | 500 A at 65 °C |
| Motor tripping class | 5; 30; 20; 10 |
| Complementary motor protection | Stalled rotor; Phase unbalance; Protracted starting time; Underload |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 250...500 A |
| Long-time protection delay adjustment type tr | Adjustable |
| [tr] long-time delay adjustment range | 120 s at 1.5 x Ir for trip class 5; 6.5 s at 6 x Ir for trip class 5; 5 s at 7.2 x Ir for trip class 5; 240 s at 1.5 x Ir for trip class 10; 13.5 s at 6 x Ir for trip class 10; 10 s at 7.2 x Ir for trip class 10; 480 s at 1.5 x Ir for trip class 20; 26 s at 6 x Ir for trip class 20; 20 s at 7.2 x Ir for trip class 20; 720 s at 1.5 x Ir for trip class 30; 38 s at 6 x Ir for trip class 30; 30 s at 7.2 x Ir for trip class 30 |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable |
| [Isd] Short-time protection pick-up adjustment range | 5...13 x Ir |
| Short-time protection delay adjustment type tsd | Fixed |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 6500 A |
| Ground-fault protection pick-up adjustment type Ig | Adjustable 9 settings |
| [Ig] ground-fault pick-up adjustment range | 0.6...1 x In for In = 25 A; 0.3...1 x In for In = 50 A; 0.2...1 x In for In > 50 A; Ig enable on/off |
| Ground-fault protection time delay adjustment type tg | Adjustable 5 settings |
| [tg] Ground-fault time delay adjustment range | 0…0.4 s |
| Earth-leakage protection | Without |
| Zone selective interlocking ZSI | With |
| Number of slots | 6 slot(s) |
| Local signalling | Flashing LED (green) for ready to operate; LED 95 % Ith (red) for temperature over set point |
| Display type | LCD display |
| Type of measurement | Energy meter |
| Communication of data | Demand current and power; Time-stamped histories and event tables; Maintenance indicators; Maximeters/minimeters; Protection and alarm settings; Instantaneous and demand values; Energy metering; Phase sequence; Thermal image function; Power quality |
| Width (W) | 140 mm |
| Height (H) | 255 mm |
| Depth (D) | 110 mm |
| Product weight | 6.2 kg |
| Standards | EN/IEC 60947-2 |
| Overvoltage category | III |
| Electrical shock protection class | Class II on front face |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0...2000 m without derating; 2000 m...5000 m with derating |
| Warranty (in months) | 18 |