cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Circuit breaker, ComPacT NSX250HB1, 75KA/690VAC, 4 poles, MicroLogic 2.2 trip unit 100A C25V42D100

Schneider Electric · Electrical Components · Moulded Case Circuit Breakers · France · se.com
Part Number
C25V42D100  ·  HS 8536.90
Schneider Electric Circuit breaker, ComPacT NSX250HB1, 75KA/690VAC, 4 poles, MicroLogic 2.2 trip unit 100A C25V42D100

Schneider Electric C25V42D100 Circuit breaker ComPacT NSX250HB1 with electronic protection-Micrologic 2.2 100A 4P 75kA/690VAC.

Technical Specifications

Manufacturer part number (MPN)C25V42D100
EAN / GTIN3606482001831
HS code8536.90
Sales unitpcs
Trip unitMicrologic2.2
RangeComPacT
Product nameComPacT NSX
Device short nameNSX250HB1
Product or component typeCircuit breaker
Device applicationDistribution
Poles description4P
Protected poles description4D; 3D + N/2; 3D
Neutral positionLeft
[In] rated current100 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Breaking capacity85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeHB1 75 kA 690 V AC
Trip unit nameMicroLogic 2.2
Trip unit technologyElectronic
Trip unit protection functionsLSoI
Control typeToggle
Circuit breaker mounting modeFixed
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service breaking capacity85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability20000 cycles
Electrical durability20000 cycles at 440 V In/2; 10000 cycles at 440 V In; 10000 cycles at 690 V In/2; 5000 cycles at 690 V In
Power dissipation per pole17.6 W
Mounting supportBackplate
Mounting positionHorizontal and vertical; Flat on the back
Upside connectionFront
Downside connectionFront
Connection pitch35 mm
Protection typeL : for overload protection (long time); So : for short time short-circuit protection with fixed delay; I : for instantaneous short-circuit protection
Trip unit rating100 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range40...100 A
Long-time protection delay adjustment type trFixed
[tr] long-time delay adjustment range400 s at 1.5 x Ir; 16 s at 6 x Ir; 11 s at 7.2 x Ir
Neutral protection setting0.5 x Ir (3D + N/2); 1 x Ir (4D); No protection (3D)
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range1500 A
Earth-leakage protectionWithout
Zone selective interlocking ZSIWithout
Number of slots5 slot(s)
Local signallingFlashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload
Width (W)140 mm
Height (H)161 mm
Depth (D)86 mm
Product weight2.8 kg
StandardsEN/IEC 60947-2
Overvoltage categoryIII
Electrical shock protection classClass II on front face
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Relative humidity0…95 %
Operating altitude0...2000 m without derating; 2000 m...5000 m with derating
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents