cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Circuit breaker, ComPacT NSX250R, 200KA/415VAC, 3 poles, MicroLogic 2.2M trip unit 220A C25R32M220

Schneider Electric · Electrical Components · Motor Protection Circuit Breakers · France · se.com
Part Number
C25R32M220  ·  HS 8536.90
Schneider Electric Circuit breaker, ComPacT NSX250R, 200KA/415VAC, 3 poles, MicroLogic 2.2M trip unit 220A C25R32M220

Schneider Electric C25R32M220 Circuit breaker NSX250R with electronic motor protection-Micrologic 2.2M 220A 3P 200kA/440VAC - 45kA/690VAC.

Technical Specifications

Manufacturer part number (MPN)C25R32M220
EAN / GTIN3606482001428
HS code8536.90
Sales unitpcs
Number of poles3P
Trip unitMicrologic2.2M
RangeComPacT
Product nameComPacT NSX
Device short nameNSX250R
Product or component typeCircuit breaker
Device applicationMotor protection
Poles description3P
Protected poles description3D
[In] rated current220 A at 65 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Breaking capacity200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeR 200 kA 415 V AC
Trip unit nameMicroLogic 2.2 M
Trip unit technologyElectronic
Trip unit protection functionsLSoI
Control typeToggle
Circuit breaker mounting modeFixed
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service breaking capacity200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability20000 cycles
Electrical durability20000 cycles at 440 V In/2; 10000 cycles at 440 V In; 10000 cycles at 690 V In/2; 5000 cycles at 690 V In
Power dissipation per pole17.6 W
Mounting supportBackplate
Mounting positionHorizontal and vertical; Flat on the back
Upside connectionFront
Downside connectionFront
Connection pitch35 mm
Protection typeL : for overload protection (long time); So : for short time short-circuit protection with fixed delay; I : for instantaneous short-circuit protection
Trip unit rating220 A at 65 °C
Motor tripping class20; 5; 10
Complementary motor protectionPhase unbalance
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range100...220 A
Long-time protection delay adjustment type trFixed
[tr] long-time delay adjustment range120 s at 1.5 x Ir for trip class 5; 6.5 s at 6 x Ir for trip class 5; 5 s at 7.2 x Ir for trip class 5; 240 s at 1.5 x Ir for trip class 10; 13.5 s at 6 x Ir for trip class 10; 10 s at 7.2 x Ir for trip class 10; 480 s at 1.5 x Ir for trip class 20; 26 s at 6 x Ir for trip class 20; 20 s at 7.2 x Ir for trip class 20
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range5...13 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range3300 A
Earth-leakage protectionWithout
Zone selective interlocking ZSIWithout
Number of slots5 slot(s)
Local signallingFlashing LED (green) for ready to operate; LED 95 % Ith (red) for temperature over set point
Width (W)105 mm
Height (H)161 mm
Depth (D)86 mm
Product weight2.4 kg
StandardsEN/IEC 60947-2
Overvoltage categoryIII
Electrical shock protection classClass II on front face
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Relative humidity0…95 %
Operating altitude0...2000 m without derating; 2000 m...5000 m with derating
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents