Schneider Electric Trip unit MicroLogic 6.2EM, ComPacT NSX100-250, 3 poles, basic and ground fault protections, motor, energy meter, 80A C1036M080

Schneider Electric · Electrical Components · Circuit Breaker Accessories · France · se.com
Part Number
C1036M080  ·  HS 8536.30
Schneider Electric Trip unit MicroLogic 6.2EM, ComPacT NSX100-250, 3 poles, basic and ground fault protections, motor, energy meter, 80A C1036M080

Schneider Electric C1036M080 Electronic motor protection with measurement for ComPacT NSX-Micrologic 6.2 E-M 3P 80A.

Technical Specifications

Manufacturer part number (MPN)C1036M080
EAN / GTIN3606482000452
Sales unitpcs
Package quantity11 pcs
Rated current80 A
Number of poles3P
RangeComPacT
Range of productComPacT NSX100...250
Product or component typeTrip unit
Trip unit nameMicroLogic 6.2 E-M
Trip unit technologyElectronic
Range compatibilityComPacT NSX100; ComPacT NSX160; ComPacT NSX250
Device applicationMotor
Poles description3P
Protected poles description3D
Trip unit protection functionsLSIG
Protection typeL : for overload protection (long time); S : for short time short-circuit protection with fixed delay; I : for instantaneous short-circuit protection; G : for ground fault protection
Trip unit rating80 A at 65 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Circuit breaker mounting modeFixed
Motor tripping class10; 30; 5; 20
Complementary motor protectionProtracted starting time; Stalled rotor; Current unbalance; Underload
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range35...80 A
Long-time protection delay adjustment type trAdjustable
[tr] long-time protection delay adjustment range120 s at 1.5 x Ir for trip class 5; 6.5 s at 6 x Ir for trip class 5; 5 s at 7.2 x Ir for trip class 5; 240 s at 1.5 x Ir for trip class 10; 13.5 s at 6 x Ir for trip class 10; 10 s at 7.2 x Ir for trip class 10; 480 s at 1.5 x Ir for trip class 20; 26 s at 6 x Ir for trip class 20; 20 s at 7.2 x Ir for trip class 20; 720 s at 1.5 x Ir for trip class 30
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range5...13 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range1200 A
Ground-fault protection pick-up adjustment type IgAdjustable
[Ig] ground-fault protection pick-up adjustment range0.2...1 x In for In = 50 A; Ig enable on/off
Ground-fault protection time delay adjustment type tgAdjustable
[tg] ground-fault protection time delay adjustment range0…0.4 s
Earth-leakage protectionWithout
Zone selective interlocking ZSIWith
Local signallingFlashing LED (green) for ready to operate; LED 95 % Ith (red) for temperature over set point
Display typeLCD display
Type of measurementEnergy meter
Communication of dataEnergy metering; Protection and alarm settings; Time-stamped histories and event tables; Instantaneous and demand values; Maintenance indicators; Demand current and power; Power quality; Maximeters/minimeters
Electrical data recordingMaintenance indicators
StandardsEN/IEC 60947-2
Electrical shock protection classClass II
Pollution degree3 conforming to IEC 60947-1
IP degree of protectionIP40 conforming to IEC 60529
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C
Warranty (in months)18
Width104.7 mm
Height96.9 mm
Depth90.3 mm
Rated permanent current Iu80 A
Short-circuit release functionDelayed
Overload release current setting35–80 A
Voltage type (supply voltage)DC
External power supply requiredYes
Rated control supply voltage DC24 V
With ground fault protection functionYes
Rated switch current80 A
Supply voltage DC24 V
End value adjustment range undelayed short-circuit release1040 A
Operating voltage AC 50 Hz690 V
Operating voltage AC 60 Hz690 V
Type of motor protectionElectronic release
Voltage type for actuatingAC
Current setting undelayed short-circuit release1200 A
Current setting delayed short-circuit release175–1040 A
Country of originFrance

Properties