cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Trip unit MicroLogic 2.2M, ComPacT NSX100/160/250, 3 poles, electronic basic protections, motor protection, 50A rating C1032M050

Schneider Electric · Electrical Components · Circuit Breaker Accessories · France · se.com
Part Number
C1032M050  ·  HS 8536.90
Schneider Electric Trip unit MicroLogic 2.2M, ComPacT NSX100/160/250, 3 poles, electronic basic protections, motor protection, 50A rating C1032M050

Schneider Electric C1032M050 Electronic motor protection for ComPacT NSX circuit breaker-Micrologic 2.2 M 3P 50A.

Technical Specifications

Manufacturer part number (MPN)C1032M050
EAN / GTIN3606482000391
HS code8536.90
Sales unitpcs
Package quantity24 pcs
Rated current50 A
Number of poles3P
RangeComPacT
Range of productComPacT NSX100...250
Product or component typeTrip unit
Trip unit nameMicroLogic 2.2 M
Trip unit technologyElectronic
Range compatibilityComPacT NSX100; ComPacT NSX160; ComPacT NSX250
Device applicationMotor
Poles description3P
Protected poles description3D
Trip unit protection functionsLSoI
Protection typeL : for overload protection (long time); So : for short time short-circuit protection with fixed delay; I : for instantaneous short-circuit protection
Trip unit rating50 A at 65 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Circuit breaker mounting modeFixed
Motor tripping class20; 5; 10
Complementary motor protectionPhase unbalance
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range25...50 A
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range120 s at 1.5 x Ir for trip class 5; 6.5 s at 6 x Ir for trip class 5; 5 s at 7.2 x Ir for trip class 5; 240 s at 1.5 x Ir for trip class 10; 13.5 s at 6 x Ir for trip class 10; 10 s at 7.2 x Ir for trip class 10; 480 s at 1.5 x Ir for trip class 20; 26 s at 6 x Ir for trip class 20; 20 s at 7.2 x Ir for trip class 20
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range5...13 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range750 A
Earth-leakage protectionWithout
Zone selective interlocking ZSIWithout
Local signallingFlashing LED (green) for ready to operate; LED 95 % Ith (red) for temperature over set point
StandardsEN/IEC 60947-2
Electrical shock protection classClass II
Pollution degree3 conforming to IEC 60947-1
IP degree of protectionIP40 conforming to IEC 60529
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents