cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Circuit breaker basic frame, ComPacT NSX160H, 70KA/415VAC, 4 poles, 160A frame rating, without trip unit C16H4

Schneider Electric · Electrical Components · Moulded Case Circuit Breakers · France · se.com
Part Number
C16H4  ·  HS 8536.90
Schneider Electric Circuit breaker basic frame, ComPacT NSX160H, 70KA/415VAC, 4 poles, 160A frame rating, without trip unit C16H4

Schneider Electric C16H4 Circuit breaker ComPacT NSX switch base NSX160H 4P without protection 160A 70kA/415VAC - 100kA/230VAC.

Technical Specifications

Manufacturer part number (MPN)C16H4
EAN / GTIN3606481999832
HS code8536.90
Sales unitpcs
Package quantity6 pcs
Number of poles4P
RangeComPacT
Product nameComPacT NSX
Device short nameNSX160H
Product or component typeBasic frame
Device applicationDistribution
Poles description4P
Neutral positionLeft
[In] rated current160 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Breaking capacity10 kA at 600 V AC 50/60 Hz conforming to UL 508; 85 kA at 240 V AC 50/60 Hz conforming to UL 508; 65 kA at 480 V AC 50/60 Hz conforming to UL 508; 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH 70 kA 415 V AC
Control typeToggle
mounting modeFixed
[Ui] rated insulation voltage800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
[Ics] rated service breaking capacity10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability40000 cycles conforming to IEC 60947-2
Electrical durability40000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2; 15000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2; 20000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2; 7500 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
Mounting supportBackplate
Upside connectionFront
Downside connectionFront
Connection pitch35 mm
Protection typeWithout protection
Width (W)140 mm
Height (H)161 mm
Depth (D)86 mm
StandardsEN/IEC 60947-2; UL 60947-4-1
Overvoltage categoryIII
Electrical shock protection classClass II on front face
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents