| Manufacturer part number (MPN) | C2535E250 |
| EAN / GTIN | 3606481999696 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Package quantity | 11 pcs |
| Rated current | 250 A |
| Number of poles | 3P |
| Range | ComPacT |
| Range of product | ComPacT NSX100...250 |
| Product or component type | Trip unit |
| Trip unit name | MicroLogic 5.2 E |
| Trip unit technology | Electronic |
| Range compatibility | ComPacT NSX250 |
| Device application | Distribution |
| Poles description | 3P |
| Protected poles description | 3D |
| Trip unit protection functions | LSI |
| Protection type | L : for overload protection (long time); S : for short time short-circuit protection; I : for instantaneous short-circuit protection |
| Trip unit rating | 250 A at 40 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Circuit breaker mounting mode | Fixed |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 100...250 A |
| Long-time protection delay adjustment type tr | Adjustable |
| [tr] long-time protection delay adjustment range | 15…400 s at 1.5 x Ir; 0.35…11 s at 7.2 x Ir; 0.5…16 s at 6 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Adjustable |
| [tsd] Short-time protection delay adjustment range | 0…0.4 s I²t=off; 0.1…0.4 s I²t=on |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | 1.5...12 x In |
| Earth-leakage protection | Without |
| Zone selective interlocking ZSI | With |
| Local signalling | Flashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload |
| Display type | LCD display |
| Type of measurement | Energy meter |
| Communication of data | Energy metering; Protection and alarm settings; Time-stamped histories and event tables; Instantaneous and demand values; Maintenance indicators; Demand current and power; Power quality; Maximeters/minimeters |
| Electrical data recording | Maintenance indicators |
| Standards | EN/IEC 60947-2 |
| Electrical shock protection class | Class II |
| Pollution degree | 3 conforming to IEC 60947-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Warranty (in months) | 18 |