cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Trip unit MicroLogic 2.2, ComPacT NSX250, 3 poles, electronic basic protections, 250A rating C2532D250

Schneider Electric · Electrical Components · Circuit Breaker Accessories · France · se.com
Part Number
C2532D250  ·  HS 8536.90
Schneider Electric Trip unit MicroLogic 2.2, ComPacT NSX250, 3 poles, electronic basic protections, 250A rating C2532D250

Schneider Electric C2532D250 Electronic protection for ComPacT NSX circuit breaker-Micrologic 2.2 3P 250A.

Technical Specifications

Manufacturer part number (MPN)C2532D250
EAN / GTIN3606481999658
HS code8536.90
Sales unitpcs
Package quantity24 pcs
Rated current250 A
Number of poles3P
RangeComPacT
Range of productComPacT NSX100...250
Product or component typeTrip unit
Trip unit nameMicroLogic 2.2
Trip unit technologyElectronic
Range compatibilityComPacT NSX250
Device applicationDistribution
Poles description3P
Protected poles description3D
Trip unit protection functionsLSoI
Protection typeL : for overload protection (long time); So : for short time short-circuit protection with fixed delay; I : for instantaneous short-circuit protection
Trip unit rating250 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Circuit breaker mounting modeFixed
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range100...250 A
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range11 s at 7.2 x Ir; 16 s at 6 x Ir; 400 s at 1.5 x Ir
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range3000 A
Earth-leakage protectionWithout
Zone selective interlocking ZSIWithout
Local signallingFlashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload
StandardsEN/IEC 60947-2
Electrical shock protection classClass II
Pollution degree3 conforming to IEC 60947-1
IP degree of protectionIP40 conforming to IEC 60529
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Warranty (in months)18