cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Trip unit MicroLogic 2.2, ComPacT NSX160/250, 3 poles, electronic basic protections, 160A rating C1632D160

Schneider Electric · Electrical Components · Circuit Breaker Accessories · France · se.com
Part Number
C1632D160  ·  HS 8536.90
Schneider Electric Trip unit MicroLogic 2.2, ComPacT NSX160/250, 3 poles, electronic basic protections, 160A rating C1632D160

Schneider Electric C1632D160 Electronic protection for ComPacT NSX circuit breaker-Micrologic 2.2 3P 160A.

Technical Specifications

Manufacturer part number (MPN)C1632D160
EAN / GTIN3606481999641
HS code8536.90
Sales unitpcs
Package quantity24 pcs
Rated current160 A
Number of poles3P
RangeComPacT
Range of productComPacT NSX100...250
Product or component typeTrip unit
Trip unit nameMicroLogic 2.2
Trip unit technologyElectronic
Range compatibilityComPacT NSX160; ComPacT NSX250
Device applicationDistribution
Poles description3P
Protected poles description3D
Trip unit protection functionsLSoI
Protection typeL : for overload protection (long time); So : for short time short-circuit protection with fixed delay; I : for instantaneous short-circuit protection
Trip unit rating160 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Circuit breaker mounting modeFixed
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range63...160 A
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range11 s at 7.2 x Ir; 16 s at 6 x Ir; 400 s at 1.5 x Ir
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range2400 A
Earth-leakage protectionWithout
Zone selective interlocking ZSIWithout
Local signallingFlashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload
StandardsEN/IEC 60947-2
Electrical shock protection classClass II
Pollution degree3 conforming to IEC 60947-1
IP degree of protectionIP40 conforming to IEC 60529
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents