cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Circuit breaker, ComPacT NSX100N, 50KA/415VAC, 4 poles 4D (neutral fully protected), TMD trip unit 40A C10N4TM040

Schneider Electric · Electrical Components · Moulded Case Circuit Breakers · France · se.com
Part Number
C10N4TM040  ·  HS 8536.90
Schneider Electric Circuit breaker, ComPacT NSX100N, 50KA/415VAC, 4 poles 4D (neutral fully protected), TMD trip unit 40A C10N4TM040

Schneider Electric C10N4TM040 Circuit breaker ComPacT NSX with thermomagnetic protection NSX100N-TM40D 4P4T 40A 50kA/415VAC - 90kA/230VAC.

Technical Specifications

Manufacturer part number (MPN)C10N4TM040
EAN / GTIN3606481998132
HS code8536.90
Sales unitpcs
Package quantity4 pcs
Trip unitTM40D
RangeComPacT
Product nameComPacT NSX
Device short nameNSX100N
Product or component typeCircuit breaker
Device applicationDistribution
Poles description4P
Protected poles description4D
Neutral positionLeft
[In] rated current40 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1; 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1; 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Breaking capacity codeN 50 kA 415 V AC
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Trip unit protection functionsLI
Control typeToggle
Circuit breaker mounting modeFixed
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service breaking capacity90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability50000 cycles
Electrical durability50000 cycles at 440 V In/2; 30000 cycles at 440 V In; 20000 cycles at 690 V In/2; 10000 cycles at 690 V In
Power dissipation per pole5.47 W
Mounting supportBackplate
Mounting positionHorizontal and vertical; Flat on the back
Upside connectionFront
Downside connectionFront
Connection pitch35 mm
Protection typeL : for overload protection (thermal); I : for short-circuit protection (magnetic)
Trip unit rating40 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Long-time protection delay adjustment type trFixed
[tr] long-time delay adjustment range120…400 s at 1.5 x In; 15 s at 6 x Ir
Neutral protection setting1 x Ir (4D)
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range500 A
Earth-leakage protectionWithout
Number of slots5 slot(s)
Width (W)140 mm
Height (H)161 mm
Depth (D)86 mm
Product weight2.4 kg
StandardsEN/IEC 60947-2
Overvoltage categoryIII
Electrical shock protection classClass II on front face
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Relative humidity0…95 %
Operating altitude0...2000 m without derating; 2000 m...5000 m with derating
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents