cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Control unit MicroLogic 2.0, ComPacT NS630B to NS3200 fixed and manually operated, basic protections C20FM

Schneider Electric · Electrical Components · Circuit Breaker Accessories · France · se.com
Part Number
C20FM  ·  HS 8536.90
Schneider Electric Control unit MicroLogic 2.0, ComPacT NS630B to NS3200 fixed and manually operated, basic protections C20FM

Schneider Electric C20FM Protection-Micrologic 2.0 for Circuit breaker ComPacT NS630b for NS3200-manual-fixed-mounted.

Technical Specifications

Manufacturer part number (MPN)C20FM
EAN / GTIN3606482098220
HS code8536.90
Sales unitpcs
RangeComPacT
Range of productComPacT NS630b...1600 new generation; ComPacT NS1600b...3200 new generation
Product or component typeControl unit
Trip unit nameMicroLogic 2.0
Trip unit technologyElectronic
Range compatibilityComPacT NS630b...1600; ComPacT NS1600b...3200
Device applicationDistribution
Number of poles3P; 4P
Protected poles description4t; 3t; 3t + N/2
Trip unit protection functionsBasic protection
Protection typeL : for overload protection (long time); I : for instantaneous short-circuit protection
Trip unit rating630 A at 50 °C; 800 A at 50 °C; 1000 A at 50 °C; 1250 A at 50 °C; 1600 A at 50 °C; 2000 A at 50 °C; 2500 A at 50 °C; 3200 A at 50 °C
Network typeAC
Network frequency50/60 Hz
Circuit breaker mounting modeFixed
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Long-time protection delay adjustment type trAdjustable 9 settings
[tr] long-time protection delay adjustment range0.7…16.6 s at 7.2 x Ir; 0.5…24 s at 6 x Ir; 12.5…600 s at 1.5 x Ir
Thermal memory20 mn
Instantaneous protection pick-up adjustment type IiAdjustable 9 settings
[Ii] instantaneous protection pick-up adjustment range1.5...10 x Ir
Earth-leakage protectionWithout
Zone selective interlocking ZSIWithout
Local signalling3 LEDs (red) for electrical fault; 1 LED (red) for internal error; 1 LED (yellow) for overload
StandardsIEC 60947-4-2
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height2.0 cm
Package 1 Width1.0 cm
Package 1 Length2.0 cm
Package 1 Weight10.0 g
Country of originIT
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents