Schneider Electric Altivar ATV12 VFD 0.37 kW 1x100-120 V IP20 (ATV12P037F1)

Schneider Electric · Drives & Controllers · Variable Frequency Drives · France · se.com
Part Number
ATV12P037F1  ·  HS 8504.40
Schneider Electric Altivar ATV12 VFD 0.37 kW 1x100-120 V IP20 (ATV12P037F1)

Schneider Electric ATV12P037F1 Altivar 12 variable-frequency drive for AC motor speed control, 0.37 kW at 1x100-120 V, 50/60 Hz. IGBT technology with Modbus RS-485 communication, without heatsink; cabinet mount, IP20.

Technical Specifications

Manufacturer part number (MPN)ATV12P037F1
EAN / GTIN3606480071041
HS code8504.40
Sales unitpcs
IP ratingIP20
Power0.37 kW
Range of productAltivar 12
Product or component typeVariable speed drive
Product specific applicationSimple machine
mounting modeCabinet mount
Communication port protocolModbus
Supply frequency50/60 Hz +/- 5 %
[Us] rated supply voltage100...120 V - 15...10 %
nominal output current2.4 A
Motor power kW0.37 kW
Motor power hp0.55 hp
EMC filterWithout EMC filter
IP degree of protectionIP20
Discrete input number4
Discrete output number2
Analogue input number1
Analogue output number1
Relay output number1
Physical interface2-wire RS 485
Connector type1 RJ45
Continuous output current2.4 A at 4 kHz
Method of accessServer Modbus serial
Speed drive output frequency0.5…400 Hz
Speed range1…20
Sampling duration20 ms, tolerance +/- 1 ms for logic input; 10 ms for analogue input
Linearity error+/- 0.3 % of maximum value for analogue input
Frequency resolutionAnalog input: converter A/D, 10 bits; Display unit: 0.1 Hz
Time constant20 ms +/- 1 ms for reference change
Transmission rate9.6 kbit/s; 19.2 kbit/s; 38.4 kbit/s
Transmission frameRTU
Number of addresses1…247
Data format8 bits, configurable odd, even or no parity
Communication serviceRead holding registers (03) 29 words; Write single register (06) 29 words; Write multiple registers (16) 27 words; Read/write multiple registers (23) 4/4 words; Read device identification (43)
Type of polarizationNo impedance
4 quadrant operation possibleFalse
Asynchronous motor control profileQuadratic voltage/frequency ratio; Voltage/frequency ratio (V/f); Sensorless flux vector control
Maximum output frequency4 kHz
Transient overtorque150…170 % of nominal motor torque depending on drive rating and type of motor
Acceleration and deceleration rampsS; Linear from 0 to 999.9 s; U
Motor slip compensationAdjustable; Preset in factory
Switching frequency2...16 kHz adjustable; 4...16 kHz with derating factor
Nominal switching frequency4 kHz
Braking to standstillBy DC injection
Brake chopper integratedFalse
Line current11.4 A at 100 V (heavy duty); 9.3 A at 120 V (heavy duty)
Maximum input current9.3 A
Maximum output voltage240 V
Apparent power1.1 kVA at 240 V (heavy duty)
Maximum transient current3.6 A during 60 s (heavy duty); 4.0 A during 2 s (heavy duty)
Network frequency50...60 Hz
Relative symmetric network frequency tolerance5 %
Prospective line Isc1 kA
Base load current at high overload2.4 A
Power dissipation in WNatural: 29.0 W
With safety function Safely Limited Speed (SLS)False
With safety function Safe brake management (SBC/SBT)False
With safety function Safe Operating Stop (SOS)False
With safety function Safe Position (SP)False
With safety function Safe programmable logicFalse
With safety function Safe Speed Monitor (SSM)False
With safety function Safe Stop 1 (SS1)False
With sft fct Safe Stop 2 (SS2)False
With safety function Safe torque off (STO)False
With safety function Safely Limited Position (SLP)False
With safety function Safe Direction (SDI)False
Protection typeLine supply overvoltage; Line supply undervoltage; Overcurrent between output phases and earth; Overheating protection; Short-circuit between motor phases; Against input phase loss in three-phase; Thermal motor protection via the drive by continuous calculation of I²t
Tightening torque0.8 N.m
InsulationElectrical between power and control
Quantity per setSet of 1
Width72 mm
Height143 mm
Depth102.2 mm
Product weight0.7 kg
Operating altitude> 1000...2000 m with current derating 1 % per 100 m; <= 1000 m without derating
Operating positionVertical +/- 10 degree
Product certificationsNOM; CSA; C-Tick; UL; GOST; RCM; KC
MarkingCE
StandardsUL 508C; UL 618000-5-1; IEC 61800-5-1; IEC 61800-3
Assembly styleOn base plate
Electromagnetic compatibilityElectrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Immunity to conducted disturbances level 3 conforming to IEC 61000-4-6; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Surge immunity test level 3 conforming to IEC 61000-4-5; Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Environmental class (during operation)Class 3C3 according to IEC 60721-3-3; Class 3S2 according to IEC 60721-3-3
Maximum acceleration under shock impact (during operation)150 m/s² at 11 ms
Maximum deflection under vibratory load (during operation)1.5 mm at 2...13 Hz
Overvoltage categoryClass III
Regulation loopAdjustable PID regulator
Electromagnetic emissionRadiated emissions environment 1 category C2 conforming to IEC 61800-3 2...16 kHz shielded motor cable; Conducted emissions with additional EMC filter environment 1 category C1 conforming to IEC 61800-3 4...12 kHz shielded motor cable <5 m; Conducted emissions with additional EMC filter environment 1 category C2 conforming to IEC 61800-3 4...12 kHz shielded motor cable <20 m; Conducted emissions with additional EMC filter environment 2 category C3 conforming to IEC 61800-3 4...12 kHz shielded motor cable <20 m
Vibration resistance1 gn (f = 13…200 Hz) conforming to IEC 60068-2-6; 1.5 mm peak to peak (f = 3…13 Hz) - drive unmounted on symmetrical DIN rail - conforming to IEC 60068-2-6
Shock resistance15 gn conforming to IEC 60068-2-27 for 11 ms
Relative humidity5…95 % without condensation conforming to IEC 60068-2-3; 5…95 % without dripping water conforming to IEC 60068-2-3
Noise level0 dB
Pollution degree2
Ambient air transport temperature-25…70 °C
Ambient air temperature for operation-10…40 °C without derating; 40…60 °C with current derating 2.2 % per °C
Ambient air temperature for storage-25…70 °C
Country of originID
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents