| XCST Safety level | Can reach PL e/category 3 for normally open relay contact conforming to ISO 13849-1; Can reach SILCL 3 for normally open relay contact conforming to IEC 62061; Can reach SIL 3 for normally open relay contact conforming to IEC 61508 Safety reliability data: MTTFd > 30 years conforming to ISO 13849-1; Dcavg = 98.9 % conforming to ISO 13849-1; PFHd = 2.39E-9 1/h conforming to ISO 13849-1; HFT = 1 conforming to IEC 62061; PFHd = 2.39E-9 1/h conforming to IEC 62061; SFF > 99% conforming to IEC 62061; HFT = 1 conforming to IEC 61508-1; PFHd = 2.39E-9 1/h conforming to IEC 61508-1; SFF > 99% conforming to IEC 61508-1; Type = B conforming to IEC 61508-1 Product certifications: TÜV; cULus [Us] rated supply voltage: 24 V AC - 15...10 %; 24 V DC - 20...20 % Output type: Relay, 1 NO circuit(s), volt-free Number of additional circuits: 2 solid state outputs Power consumption in W: 2.0 W Power consumption in VA: 5.5 VA input voltage: 690 V Input detection threshold: 50 mV; 65 mV; 85 mV; 110 mV; 140 mV; 180 mV; 230 mV; 300 mV; 400 mV; 500 mV Time delay: 0.5 s; 1 s; 2 s; 3 s; 5 s; 8 s; 12 s; 20 s; 35 s; 60 s [Ie] rated operational current: 5 A AC-1 for normally open relay contact; 3 A AC-15 for normally open relay contact; 5 A DC-1 for normally open relay contact; 3 A DC-13 for normally open relay contact [Ith] conventional free air thermal current: 6 A for NO relay output circuit Associated fuse rating: 6 A gG for relay output conforming to IEC 60947-1 Standards: IEC 60947-5-1; IEC 61508-1 functional safety standard; IEC 61508-2 functional safety standard; IEC 61508-3 functional safety standard; IEC 61508-4 functional safety standard; IEC 61508-5 functional safety standard; IEC 61508-6 functional safety standard; IEC 61508-7 functional safety standard; ISO 13849-1 functional safety standard; IEC 62061 functional safety standard minimum output current: 10 mA for relay output minimum output voltage: 5 V for relay output [Ui] rated insulation voltage: 690 V phase to phase (pollution degree 2) conforming to IEC 60947-1; 400 V phase to earth (pollution degree 2) conforming to IEC 60947-1 [Uimp] rated impulse withstand voltage: 4 kV overvoltage category II conforming to IEC 60947-1 Local signalling: LED green with power marking for power ON; LED red with error marking for error; LED yellow with state marking for status; LED yellow with L12 marking for input line comparison; LED yellow with L32 marking for input line comparison Connections - terminals: Removable screw terminal block solid or flexible cable: 0.2...2.5 mm²; Removable screw terminal block flexible with ferrule cable: 0.25...2.5 mm² single conductor; Removable screw terminal block solid or flexible cable: 0.2...1.5 mm² twin conductor; Removable screw terminal block flexible with ferrule cable: 2 x 0.25...1 mm² without cable end, with bezel; Removable screw terminal block flexible with ferrule cable: 2 x 0.5...1.5 mm² with cable end, with bezel Mounting support: 35 mm symmetrical DIN rail Depth: 120 mm Height: 100 mm Width: 22.5 mm Product weight: 0.2 kg IP degree of protection: IP20 (terminals) conforming to IEC 60529; IP40 (housing) conforming to IEC 60529; IP54 (mounting area) conforming to IEC 60529 Ambient air temperature for operation: -25…55 °C Ambient air temperature for storage: -40…70 °C Relative humidity: 5…95 % non-condensing Number of Units in Package 1: 1 Number of Units in Package 2: 16 Country of origin: ID Warranty (in months): 18 Type of electric connection: Screw connection Voltage type for actuating: AC/DC With detachable clamps: Yes Evaluation inputs: 2-channel Function rotational speed monitoring: No Function standstill monitoring: Yes With feedback circuit: No Number of outputs, safety related, undelayed, with contact: 1 Number of outputs, safety related, delayed, with contact: 1 Suitable for safety functions: Yes SIL according to IEC 61508: 3 Performance level according to EN ISO 13849-1: Level e With approval for BG BIA: Yes With approval according to UL: Yes |