| Manufacturer part number (MPN) | SSD1A335BDC2 |
| EAN / GTIN | 3606489807917 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Package quantity | 24 pcs |
| Voltage | 48-600 V AC |
| Range of product | Harmony Solid State Relays |
| Product or component type | Modular DIN rail relay |
| Device short name | SSD1 |
| Number of channels | 1 |
| Number of phases | 1 phase |
| Product configuration type | Contactor configuration with pluggable screw input |
| Mounting support | 35 mm symmetrical DIN rail conforming to IEC 60715 |
| rated current | 35 A |
| Output switching mode | Zero voltage switching |
| operating frequency | 47...440 Hz |
| Rated duty | Uninterrupted |
| Output voltage | 48...600 V AC |
| control circuit voltage | 4...32 V DC |
| Tightening torque | 0.5 N.m for control input; 5 lb.in for control input; 2...2.2 N.m for load output; 18...20 lb.in for load output |
| Connections - terminals | Plug-in screw terminals, clamping connection capacity:0.08...3.30 mm², 28 AWG...12 AWG for input; telescopic screw, clamping connection capacity:0.75...10 mm², 20 AWG...8 AWG for output |
| Dielectric strength | 4 kV AC for input/output circuit; 4 kV AC for input or output to case |
| rated impulse withstand voltage | 6 kV for input/output circuit; 6 kV for input or output to case |
| Insulation resistance | 1000 MOhm at 500 V DC |
| Local signalling | LED (green) for control voltage |
| pick-up voltage | 4 V DC turn-on |
| drop-out voltage | 1 V DC turn-off |
| input current range | 10…15 mA |
| solid state switching type | Zero voltage switching |
| Load current | 0.2…35 A |
| transient overvoltage | 1200 V |
| Inrush current | 1350 A at 60 Hz |
| Maximum voltage drop | <1.15 V on-state |
| motor controller rating | 1.5 kW/2 hp at 120 V AC; 3.73 kW/5 hp at 240 V AC; 7.46 kW/10 hp at 480 V AC |
| Electromagnetic compatibility | Electrostatic discharge 6 kV criteria A contact discharge conforming to IEC 61000-4-2; Electrostatic discharge 8 kV criteria A air discharge conforming to IEC 61000-4-2; Conducted RF disturbances 10 V, 0.15...80 MHz criteria A level 3 conforming to IEC 61000-4-6; Electrical fast transient/burst immunity test 2 kV, 5/100 kHz criteria B output ports conforming to IEC 61000-4-4; Electrical fast transient/burst immunity test 1 kV, 5/100 kHz criteria B input ports conforming to IEC 61000-4-4; Radiated radio-frequency electromagnetic field immunity test 10 V/m, 80 MHz...1 GHz criteria A conforming to IEC 61000-4-3; Radiated radio-frequency electromagnetic field immunity test 3 V/m, 1.4...2 GHz criteria A conforming to IEC 61000-4-3; Radiated radio-frequency electromagnetic field immunity test 1 V/m, 2...2.7 GHz criteria A conforming to IEC 61000-4-3; Surge immunity test 1 kV criteria A output ports line to line conforming to IEC 61000-4-5; Surge immunity test 2 kV criteria B output ports line to earth conforming to IEC 61000-4-5; Radiated emission environment B for DC input supply conforming to IEC 60947-4-3; Conducted emission environment B for DC input supply conforming to IEC 60947-4-3 |
| device form designation | Form 5 semiconductor output DOL contactor |
| Maximum I²t for fusing | 8320 A².s for 10 ms; 7593 A².s for 8.33 ms |
| Maximum leakage current | 1 mA off-state |
| DV/dt | 500 V/µs off-state at maximum rated voltage |
| Response time | 0.5 cycle (turn-on); 0.5 cycle (turn-off) |
| Power factor | 0.5 with maximum load |
| short circuit protection coordination | Type 1; Type 2 |
| Overvoltage category | III |
| Width | 22.5 mm |
| Height | 94.6 mm |
| Depth | 134.7 mm |
| test button | Without test button |
| Product weight | 0.301 kg |
| Device presentation | Complete product |
| [Ui] rated insulation voltage | 600 V |
| Flammability rating | V-0 conforming to UL 94 |
| Vibration resistance | 0.75 mm (f = 10…150 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 50 gn for 11 ms (peak acceleration) , longitudinal position conforming to IEC 60068-2-27; 30 gn for 11 ms (peak acceleration) , vertical position conforming to IEC 60068-2-27 |
| Pollution degree | 2 |
| Standards | IEC 61373:class B: category 1; IEC 60947-4-3; IEC 62314; IEC 60950-1 |
| IP degree of protection | IP20 |
| Ambient air temperature for operation | -40…80 °C |
| Ambient air temperature for storage | -40…100 °C |
| Country of origin | MX |
| Warranty (in months) | 18 |