| Manufacturer part number (MPN) | 47284 |
| EAN / GTIN | 3606480344770 |
| Sales unit | pcs |
| Trip unit | Micrologic 5.0E |
| Width | 53.6 mm |
| Height | 199.5 mm |
| Depth | 67.5 mm |
| Rated permanent current Iu | 1600 A |
| Number of poles | 4 |
| Short-circuit release function | Delayed |
| Overload release current setting | 252–1600 A |
| Voltage type (supply voltage) | DC |
| External power supply required | Yes |
| Rated control supply voltage DC | 24 V |
| With ground fault protection function | No |
| Rated switch current | 1600 A |
| Supply voltage DC | 24 V |
| End value adjustment range undelayed short-circuit release | 24000 A |
| Operating voltage AC 50 Hz | 690 V |
| Operating voltage AC 60 Hz | 690 V |
| Type of motor protection | Electronic release |
| Voltage type for actuating | Self powered |
| Current setting undelayed short-circuit release | 3200–24000 A |
| Current setting delayed short-circuit release | 378–16000 A |
| Country of origin | France |