cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Motor circuit breaker, TeSys GV4, 3P, 50A, Icu 50KA, thermal magnetic, lugs terminals GV4PE50N6

Schneider Electric · Electrical Components · Motor Protection Circuit Breakers · France · se.com
Part Number
GV4PE50N6  ·  HS 8536.90
Schneider Electric Motor circuit breaker, TeSys GV4, 3P, 50A, Icu 50KA, thermal magnetic, lugs terminals GV4PE50N6

Schneider Electric GV4PE50N6 Motor protection circuit breaker GV4PE Therm/Mag 50A 50kA lug.

Technical Specifications

Manufacturer part number (MPN)GV4PE50N6
EAN / GTIN3606481310446
HS code8536.90
Sales unitpcs
Package quantity9 pcs
Rated current50 A
RangeTeSys Deca
Range of productTeSys GV4
Device short nameGV4PE
Product nameTeSys GV4
Product or component typeMotor circuit breaker
Device applicationMotor protection
Trip unit technologyThermal-magnetic; Electronic
Poles description3P
Utilisation categoryCategory A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1
Operating positionAny position
Motor power kW11 kW at 400...415 V AC 50/60 Hz; 15 kW at 500 V AC 50/60 Hz; 18.5 kW at 660...690 V AC 50/60 Hz; 15 kW at 400...415 V AC 50/60 Hz; 18.5 kW at 400...415 V AC 50/60 Hz; 22 kW at 400...415 V AC 50/60 Hz; 18.5 kW at 500 V AC 50/60 Hz; 22 kW at 500 V AC 50/60 Hz; 30 kW at 500 V AC 50/60 Hz; 22 kW at 660...690 V AC 50/60 Hz; 30 kW at 660...690 V AC 50/60 Hz; 37 kW at 660...690 V AC 50/60 Hz; 45 kW at 660...690 V AC 50/60 Hz
Breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA at 208Y/120 V AC 50/60 Hz conforming to UL 60947; 65 kA at 240 V AC 50/60 Hz conforming to UL 60947; 35 kA at 480Y/277 V AC 50/60 Hz conforming to UL 60947; 8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 18 kA at 600Y/347 V AC 50/60 Hz conforming to UL 60947
Control typeToggle
[In] rated current50 A
Magnetic tripping current850 A
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage800 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current115 A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
Power dissipation per pole4.6 W
Mechanical durability40000 cycles
Electrical durability5000 cycles for AC-3 at 415 V opening; 5000 cycles for AC-3 at 415 V closing
maximum operating rate25 cyc/h
Rated dutyContinuous conforming to IEC 60947-4-1
Connection pitch27 mm without spreaders; 35 mm with spreaders
Connections - terminalsLugs-ring terminals
Tightening torque9 N.m for cable 16…95 mm²; 5 N.m for cable 1.5…10 mm²
Mechanical robustnessVibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6; Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6; Shocks: 15 gn 11 ms conforming to IEC 60068-2-27
Phase failure sensitivityYes conforming to IEC 60947-4-1
Height155 mm
Width81 mm
Depth116 mm
Product weight1.45 kg
ColourGrey (RAL 7016)
Suitability for isolationYes conforming to IEC 60947-1
StandardsCSA C22.2 No 60947-4-1; UL 60947-4-1; EN/IEC 60947-4-1; EN/IEC 60947-2
Product certificationsIEC; UL; CSA; CCC; EAC; ATEX; EU-RO MR
Climatic withstandconforming to IACS E10
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3
IP degree of protectionIP40 conforming to IEC 60529
Ambient air temperature for storage-50…85 °C
Fire resistance960 °C conforming to IEC 60695-2-11
Operating altitude5000 m
Ambient air temperature for operation-25…70 °C
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents