Key switch, flush 2-Pos 1NO (XB4FG61)

Schneider Electric · Control & Automation · Pushbuttons & Pilot Lights · France · se.com
Part Number
XB4FG61  ·  HS 8536.50
Key switch, flush 2-Pos 1NO (XB4FG61)

Schneider Electric XB4FG61 — Harmony XB4 22 mm command actuator. Metal or plastic 22 mm cutout push-button, selector or indicator. Key switch flush 2 pos. with spring return from H-for-V and key (455) out in V 1xNO.

Technical Specifications

Manufacturer part number (MPN)XB4FG61
EAN / GTIN3606489580247
Sales unitpcs
Contact configuration1 NO
Range of productHarmony XB4
Product or component typeSelector switch
Device short nameXB4F
Bezel materialChromium plated metal
Fixing collar materialZamak
Mounting diameter30.5 mm
Sale per indivisible quantity1
Head typeBuilt-in-flush
Shape of signaling unit headRound
Type of operatorRight to left spring return
Operator profileBlack key switch
Operator position information2 positions 90°
Contacts type and composition1 NO
Contact operationSlow-break
Connections - terminalsScrew clamp terminals, = 1 x 0.22 mm² without cable end conforming to IEC 60947-1
Height47 mm
Width36.6 mm
Depth100 mm
Terminals description ISO n°1(13-14)NO
Product weight0.117 kg
Resistance to high pressure washer7000000 Pa at 55 °C, distance : 0.1 m
Device mountingBuilt-in
Fixing center40 x 50 mm (1...6 mm thick panel)
Fixing modeBy screws
Type of keylockKey 455
Key withdrawal positionLeft-hand
Contacts usageStandard contacts
Positive openingWithout
Torque value0.14 N.m NO changing electrical state
Mechanical durability1000000 cycles
Tightening torque0.8…1.2 N.m conforming to IEC 60947-1
Shape of screw headCross compatible with Philips no 1 screwdriver; Cross compatible with pozidriv No 1 screwdriver; Slotted compatible with flat Ø 4 mm screwdriver; Slotted compatible with flat Ø 5.5 mm screwdriver
Contacts materialSilver alloy (Ag/Ni)
Short-circuit protection10 A cartridge fuse type gG conforming to IEC 60947-5-1
[Ith] conventional free air thermal current10 A conforming to IEC 60947-5-1
[Ui] rated insulation voltage600 V (pollution degree 3) conforming to IEC 60947-1
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-1
[Ie] rated operational current3 A at 240 V, AC-15, A600 conforming to IEC 60947-5-1; 6 A at 120 V, AC-15, A600 conforming to IEC 60947-5-1; 0.1 A at 600 V, DC-13, Q600 conforming to IEC 60947-5-1; 0.27 A at 250 V, DC-13, Q600 conforming to IEC 60947-5-1; 0.55 A at 125 V, DC-13, Q600 conforming to IEC 60947-5-1; 1.2 A at 600 V, AC-15, A600 conforming to IEC 60947-5-1
Electrical durability1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN 60947-5-1 appendix C; 1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN 60947-5-1 appendix C; 1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN 60947-5-1 appendix C; 1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN 60947-5-1 appendix C; 1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN 60947-5-1 appendix C
Electrical reliabilityΛ < 10exp(-6) at 5 V and 1 mA in clean environment conforming to IEC 60947-5-4; Λ < 10exp(-8) at 17 V and 5 mA in clean environment conforming to IEC 60947-5-4
Device presentationComplete product
Protective treatmentTH
Ambient air temperature for storage-40…70 °C
Ambient air temperature for operation-40…70 °C
Overvoltage categoryClass I conforming to IEC 60536
IP degree of protectionIP66 conforming to IEC 60529; IP67 conforming to IEC 60529; IP69 conforming to IEC 60529; IP69K conforming to ISO 20653; Type 13 conforming to UL 50 E; Type 12 conforming to UL 50 E; Type 4 conforming to UL 50 E; Type 4X conforming to UL 50 E
IK degree of protectionIK04 conforming to IEC 50102
StandardsCSA C22.2 No 14; IEC 60947-5-1; IEC 60947-5-4; UL 508; IEC 60947-1; JIS C8201-5-1; CE; JIS C8201-1
Product certificationsUL listed; CSA; CCC; EAC
Vibration resistance5 gn (f= 10…500 Hz) conforming to IEC 60068-2-6; 2 mm peak to peak (f= 2…10 Hz) conforming to IEC 60068-2-6
Shock resistance30 gn (duration = 18 ms) for half its wave acceleration conforming to IEC 60068-2-27; 50 gn (duration = 11 ms) for half its wave acceleration conforming to IEC 60068-2-27; 25 gn (duration = 6 ms) for 1000 shocks on each axis conforming to IEC 60068-2-27
Number of Units in Package 11
Country of originFR
Warranty (in months)18
Hole diameter30.5 mm
Colour buttonBlack
Number of switch positions2
Suitable for lightingNo
Spring-returnYes
Colour front ringChrome
Type of electric connectionScrew connection
Degree of protection (IP)IP66
With light sourceNo
Material front ringMetal
With front ringYes
Type of control elementKey
Switching function latchingNo
Number of contacts as normally open contact1

Properties

MOQ1

Cross-References