cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric spring return contact block - 1 NC + 1 NO - front mounting, 30 or 40 mm centres XACS415

Schneider Electric · Control & Automation · Pushbuttons & Pilot Lights · France · se.com
Part Number
XACS415  ·  HS 8536.50
Schneider Electric spring return contact block - 1 NC + 1 NO - front mounting, 30 or 40 mm centres XACS415

Schneider Electric XACS415 Contact Block f/frontmon.1no/nc.

Technical Specifications

Manufacturer part number (MPN)XACS415
EAN / GTIN3389110647556
Sales unitpcs
Package quantity30 pcs
Range of productHarmony XAC
Product or component typeContact block
Component nameXACS
Electrical circuit typeControl circuit
Contact block typeSingle
Type of operatorSpring return
Product compatibilityXACA; ZA2B... head
Mechanical interlockingWithout mechanical interlock
Contacts type and composition1 NC + 1 NO
Mounting of blockFront mounting
Contact operationSlow-break
Connections - terminalsScrew clamp terminals, 1 x 2.5 mm² with or without cable end; Screw clamp terminals, 2 x 1.5 mm² with or without cable end
Horizontal fixing centres40 mm
Vertical fixing centres30 mm
Mechanical durability1000000 cycles
Contact code designationA300 AC-15, Ue = 240 V, Ie = 3 A conforming to IEC 60947-5-1 appendix A; Q300 DC-13, Ue = 250 V, Ie = 0.27 A conforming to IEC 60947-5-1 appendix A
[Ithe] conventional enclosed thermal current10 A
[Ui] rated insulation voltage500 V (pollution degree 3) conforming to IEC 60947-1
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-1
Maximum resistance across terminals25 MOhm
Short-circuit protection10 A fuse protection by cartridge fuse type gG
Rated operational power in W42 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 120 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C; 45 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 48 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C; 60 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 24 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C
Rated operational power in VA140 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 24 V 50/60 Hz, load factor = 0.5 (inductive load); 385 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 48 V 50/60 Hz, load factor = 0.5 (inductive load); 455 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 230 V 50/60 Hz, load factor = 0.5 (inductive load); 525 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 127 V 50/60 Hz, load factor = 0.5 (inductive load)
Terminals description ISO n°1(23-24)NO; (11-12)NC
Terminal identifier(11-12)NC; (13-14)NO
Product weight0.07 kg
StandardsCSA C22.2 No 14; IEC 60947-5-1; IEC 60947-5-1
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…70 °C
Vibration resistance15 gn (f= 10…500 Hz) conforming to IEC 60068-2-6
Shock resistance100 gn conforming to IEC 60068-2-27
Number of Units in Package 11
Number of Units in Package 230
Country of originCZ
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents