Contact element 1 NO (ZENL1111)

Schneider Electric · Control & Automation · Pushbuttons & Pilot Lights · France · se.com
Part Number
ZENL1111  ·  HS 8536.50
Contact element 1 NO (ZENL1111)

Schneider Electric ZENL1111 Contact Element 1 NO.

Technical Specifications

Manufacturer part number (MPN)ZENL1111
EAN / GTIN3389110115079
Sales unitpcs
Package quantity5 pcs
Contact configuration1 NO
Range of productHarmony XAL; Harmony XAPS
Product or component typeContact block
Device short nameZENL
Product destinationFor XB5 Ø 22 mm control and signalling units; For XAPS control station
Mounting of blockRear mounting
Sale per indivisible quantity5
Contacts type and composition1 NO
Assembly styleFor customer assembly
Product weight0.015 kg
Contact operationSlow-break
Positive openingWithout
Operating travel2.6 mm (NO changing electrical state); 4.3 mm (total travel)
Operating force2.3 N NO changing electrical state
Operating torque0.05 N.m NO changing electrical state
Mechanical durability10000000 cycles
Connections - terminalsScrew clamp terminals, = 1 x 0.22 mm² without cable end conforming to IEC 60947-1
Tightening torque0.8…1.2 N.m conforming to IEC 60947-1
Shape of screw headCross compatible with Philips no 1 screwdriver; Cross compatible with pozidriv No 1 screwdriver; Slotted compatible with flat Ø 4 mm screwdriver; Slotted compatible with flat Ø 5.5 mm screwdriver
Contacts materialSilver alloy (Ag/Ni)
Maximum resistance across terminals25 MOhm
Short-circuit protection10 A cartridge fuse type gG conforming to IEC 60947-5-1
[Ith] conventional free air thermal current10 A conforming to IEC 60947-5-1
[Ui] rated insulation voltage600 V (pollution degree 3) conforming to IEC 60947-1
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-1
[Ie] rated operational current3 A at 240 V, AC-15, A600 conforming to IEC 60947-5-1; 6 A at 120 V, AC-15, A600 conforming to IEC 60947-5-1; 0.1 A at 600 V, DC-13, Q600 conforming to IEC 60947-5-1; 0.27 A at 250 V, DC-13, Q600 conforming to IEC 60947-5-1; 0.55 A at 125 V, DC-13, Q600 conforming to IEC 60947-5-1; 1.2 A at 600 V, AC-15, A600 conforming to IEC 60947-5-1
Electrical durability1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C; 1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C; 1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C; 1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C; 1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
Electrical reliabilityΛ < 10exp(-6) at 5 V and 1 mA in clean environment conforming to IEC 60947-5-4; Λ < 10exp(-8) at 17 V and 5 mA conforming to IEC 60947-5-4
Additional informationMounting on integrated plate in the box
Electrical composition codeSR1 (quantity <= 3); SR2 (quantity <= 2); MR1 (quantity <= 2)
Protective treatmentTH
Ambient air temperature for storage-40…70 °C
Ambient air temperature for operation-40…70 °C
IP degree of protectionIP20 conforming to IEC 60529
StandardsIEC 60947-5-1; CSA C22.2 No 14; IEC 60947-1; UL 508; IEC 60947-5-5; JIS C8201-5-1; IEC 60947-5-4; JIS C8201-1
Vibration resistance5 gn (f= 12…500 Hz) conforming to IEC 60068-2-6
Shock resistance30 gn (duration = 18 ms) for half its wave acceleration conforming to IEC 60068-2-27; 50 gn (duration = 11 ms) for half its wave acceleration conforming to IEC 60068-2-27
Number of Units in Package 11
Number of Units in Package 25
Number of Units in Package 35
Country of originFR
Warranty (in months)18

Properties

MOQ1

Cross-References