Schneider Electric impulse relay iTL - 1P - 1NO - 32A - coil 110 VDC - 230...240 VAC 50/60Hz A9C30831

Schneider Electric · Control & Automation · Relays & Timers · France · se.com
Part Number
A9C30831  ·  HS 8536.49
Schneider Electric impulse relay iTL - 1P - 1NO - 32A - coil 110 VDC - 230...240 VAC 50/60Hz A9C30831

Schneider Electric A9C30831 Impulse relay iTL 32A 1NO 230VAC/110VDC.

Technical Specifications

Manufacturer part number (MPN)A9C30831
EAN / GTIN3606480088988
Sales unitpcs
Package quantity12 pcs
Voltage230 V AC
Contact configuration1 NO
range of productActi9
Product nameActi9 iTL
Product or component typeImpulse relay
Device short nameiTL
Device applicationStandard
Poles1P
Pole contact composition1 NO
[In] rated current32 A
Network typeAC
[Uc] control circuit voltage230...240 V AC 50/60 Hz; 110 V DC
Network frequency50/60 Hz
[Ue] rated operational voltage250 V AC 50/60 Hz
Control typeCoil disconnection; Remote and manual control
Control signal typeImpulse
Switching frequency100 switching operations/day; 5 switching operations/minute
Impulse duration50 ms...1 s
Remote control typeIlluminated push-button
Local signallingON/OFF indication
mounting modeFixed
Mounting supportDIN rail
9 mm pitches2
Height84 mm
Width18 mm
Depth60 mm
Electrical durabilityAC-21: 50000 cycles; AC-22: 20000 cycles
Connections - terminalsControl circuit: tunnel type terminals 1 cable(s) 0.5…4 mm² rigid; Control circuit: tunnel type terminals 1 cable(s) 0.5…4 mm² rigid with cable end; Control circuit: tunnel type terminals 1 cable(s) 1…4 mm² flexible; Control circuit: tunnel type terminals 1 cable(s) 1…4 mm² flexible with ferrule; Control circuit: tunnel type terminals 1 cable(s) 1.5…10 mm² rigid; Control circuit: tunnel type terminals 1 cable(s) 1.5…10 mm² rigid with cable end; Control circuit: tunnel type terminals 1 cable(s) 1.5…10 mm² flexible; Control circuit: tunnel type terminals 1 cable(s) 1.5…10 mm² flexible with ferrule
Wire stripping length11 mm
Tightening torque1.2 N.m
Range compatibilityActi9 iATEt; Acti9 iATL4; Acti9 iATLc; Acti9 iATLc+s; Acti9 iATLm; Acti9 iATLs; Acti9 iATLz; Acti9 iATLc+c; Acti9 iATL24; Acti9 iETL iTL 32
StandardsEN 669-1; EN 669-2-2
Product certificationsGOST
Quality labelsVDE; IMQ; KEMA; NF; CEBEC
Noise level60 dB
IP degree of protectionIP20 conforming to IEC 60529 (on opening); IP40 conforming to IEC 60529 (in enclosure)
Pollution degree3
Tropicalisation2
Relative humidity95 % at 55 °C
Ambient air temperature for operation-20…50 °C
Ambient air temperature for storage-40…70 °C
Warranty (in months)18
Mounting methodDIN rail
FunctionMechanical switch
Built-in depth43.5 mm
Width in number of modular spacings1
Control voltage 1230–240 V
Control voltage 2110 V
Type of control voltage 1AC
Type of control voltage 2DC
Frequency control voltage 150–60 Hz
Suitable for manual operationYes
Voltage type (supply voltage)AC
Supply voltage24–250 V
Max. switching current (cos phi = 0.6)32 A
Max. incandescent lamp load4200 W
Max. load fluorescent lamp3350 VA
Rated switch current32 A
Number of contacts as normally open contact1
Country of originBelgium