cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric impulse relay iTL - 4P - 4 NO - 16A - coil 110 VDC - 230...240 VAC 50/60Hz A9C30814

Schneider Electric · Control & Automation · Relays & Timers · France · se.com
Part Number
A9C30814  ·  HS 8536.49
Schneider Electric impulse relay iTL - 4P - 4 NO - 16A - coil 110 VDC - 230...240 VAC 50/60Hz A9C30814

Schneider Electric A9C30814 Impulse relay iTL 16A 4NO 230VAC/110VDC.

Technical Specifications

Manufacturer part number (MPN)A9C30814
EAN / GTIN3606480091902
Sales unitpcs
Package quantity6 pcs
Voltage230 V AC
Contact configuration4 NO
range of productActi9
Product nameActi9 iTL
Product or component typeImpulse relay
Device short nameiTL
Device applicationStandard
Poles4P
Pole contact composition4 NO
[In] rated current16 A
Network typeAC
[Uc] control circuit voltage230...240 V AC 50/60 Hz; 110 V DC
Network frequency50/60 Hz
[Ue] rated operational voltage415 V AC 50/60 Hz
Control typeRemote and manual control
Control signal typeImpulse
Switching frequency5 switching operations/minute; 100 switching operations/day
Impulse duration50 ms...1 s
Remote control typeIlluminated push-button 3 mA
Local signallingON/OFF indication
mounting modeFixed
Mounting supportDIN rail
9 mm pitches4
Height84 mm
Width36 mm
Depth60 mm
Electrical durabilityAC-21: 200000 cycles; AC-22: 100000 cycles
Connections - terminalsControl circuit: tunnel type terminals 1 cable(s) 0.5…4 mm² rigid; Control circuit: tunnel type terminals 1 cable(s) 0.5…4 mm² rigid with cable end; Control circuit: tunnel type terminals 1 cable(s) 1…4 mm² flexible; Control circuit: tunnel type terminals 1 cable(s) 1…4 mm² flexible with ferrule; Power circuit: tunnel type terminals 1 cable(s) 1.5…4 mm² rigid; Power circuit: tunnel type terminals 1 cable(s) 1.5…4 mm² rigid with cable end; Power circuit: tunnel type terminals 1 cable(s) 1.5…4 mm² flexible; Power circuit: tunnel type terminals 1 cable(s) 1.5…4 mm² flexible with ferrule
Wire stripping length11 mm
Tightening torque1 N.m
Range compatibilityActi9 iATEt; Acti9 iATL4; Acti9 iATLc; Acti9 iATLc+s; Acti9 iATLm; Acti9 iATLs; Acti9 iATLz; Acti9 iETL iTL 16; Acti9 iATLc+c; Acti9 iATL24
StandardsEN 669-1; EN 669-2-2
Product certificationsGOST; CCC
Quality labelsKEMA; CEBEC; NF; VDE; IMQ
Noise level60 dB
IP degree of protectionIP20 conforming to IEC 60529 (on opening); IP40 conforming to IEC 60529 (in enclosure)
Pollution degree3
Tropicalisation2
Relative humidity95 % at 55 °C
Ambient air temperature for operation-20…50 °C
Ambient air temperature for storage-40…70 °C
Country of originBE
Warranty (in months)18
Mounting methodDIN rail
FunctionMechanical switch
Built-in depth43.5 mm
Width in number of modular spacings2
Control voltage 1230–240 V
Control voltage 2110 V
Type of control voltage 1AC
Type of control voltage 2DC
Frequency control voltage 150–60 Hz
Suitable for manual operationYes
Voltage type (supply voltage)AC
Supply voltage24–415 V
Max. switching current (cos phi = 0.6)16 A
Max. incandescent lamp load4800 W
Max. load fluorescent lamp3900 VA
Rated switch current16 A
Number of contacts as normally open contact4

Properties

MOQ1

Cross-References

Attached Documents