cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Standard control unit, TeSys U, 9.5-38A, 3P motors, magnetic protection, coil 110-240V AC/DC LUCL38FU

Schneider Electric · Electrical Components · Circuit Breaker Accessories · France · se.com
Part Number
LUCL38FU  ·  HS 8536.30
Schneider Electric Standard control unit, TeSys U, 9.5-38A, 3P motors, magnetic protection, coil 110-240V AC/DC LUCL38FU

Schneider Electric LUCL38FU Protection U kortsluttnig 38A 110-240V AC/CD.

Technical Specifications

Manufacturer part number (MPN)LUCL38FU
EAN / GTIN3606481493774
Sales unitpcs
Voltage110-240 V
Rated current38 A
RangeTeSys
Range of productTeSys Ultra
Product nameTeSys Ultra
Device short nameLUCL
Product or component typeMagnetic control unit
Device applicationMotor control; Motor protection
Product specific applicationProtection of variable speed drive or soft startsoft stop unit
main function availableShort-circuit protection; Manual reset
Product compatibilityPower base LUB38; Power base LUB380; Reversing contactor breaker LU2B38FU
[Ue] rated operational voltage690 V AC
Network frequency40...60 Hz
Load type3-phase motor - cooling: self-cooled
Utilisation categoryAC-43
Motor power kW18.5 kW at 400...440 V AC 50/60 Hz; 18.5 kW at 500 V AC 50/60 Hz; 22 kW at 690 V AC 50/60 Hz
rated motor current adjustment range9.5…38 A
Tripping threshold14.2 x Ir +/- 20 %
[Uc] control circuit voltage110...240 V AC; 110...220 V DC
Control circuit voltage limits88...264 V for AC circuit 110...240 V in operation; 88...242 V for DC circuit 110...220 V in operation; 55 V for AC circuit 110...240 V drop-out; 55 V for DC circuit 110...220 V drop-out
Typical current consumption280 mA at 110...240 V AC I maximum while closing with LUB32; 280 mA at 110...240 V AC I maximum while closing with LUB38; 280 mA at 110...220 V DC I maximum while closing with LUB32; 280 mA at 110...220 V DC I maximum while closing with LUB38; 25 mA at 110...240 V AC I rms sealed with LUB32; 25 mA at 110...240 V AC I rms sealed with LUB38; 25 mA at 110...220 V DC I rms sealed with LUB32; 25 mA at 110...220 V DC I rms sealed with LUB38
Heat dissipation3 W for control circuit with LUB38
Operating time35 ms opening with LUB38 for control circuit; 50 ms closing with LUB38 for control circuit
StandardsEN 60947-6-2; IEC 60947-6-2; UL 60947-4-1, with phase barrier; CSA C22.2 No 60947-4-1, with phase barrier
Product certificationsCE; EAC; ATEX
[Ui] rated insulation voltage690 V conforming to IEC 60947-6-2; 600 V conforming to UL 60947-4-1; 600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-6-2
Safe separation of circuit400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1; 400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1
Fixing modePlug-in (front face)
Width45 mm
Height66 mm
Depth60 mm
Product weight0.135 kg
Compatibility codeLUCL
IP degree of protectionIP20 front panel and wired terminals conforming to IEC 60947-1; IP20 other faces conforming to IEC 60947-1; IP40 front panel outside connection zone conforming to IEC 60947-1
Protective treatmentTH conforming to IEC 60068
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C
Operating altitude2000 m
Fire resistance960 °C parts supporting live components conforming to IEC 60695-2-12; 650 °C conforming to IEC 60695-2-12
Shock resistance10 gn power poles open conforming to IEC 60068-2-27; 15 gn power poles closed conforming to IEC 60068-2-27
Vibration resistance2 gn, 5…300 Hz, power poles open conforming to IEC 60068-2-6; 4 gn, 5…300 Hz, power poles closed conforming to IEC 60068-2-6
Resistance to electrostatic discharge8 kV level 3 in open air conforming to IEC 61000-4-2; 8 kV level 4 on contact conforming to IEC 61000-4-2
Non-dissipating shock wave1 kV serial mode conforming to IEC 60947-6-2; 2 kV common mode conforming to IEC 60947-6-2
Resistance to radiated fields10 V/m 3 conforming to IEC 61000-4-3
Resistance to fast transients2 kV class 3 serial link conforming to IEC 61000-4-4; 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4
Immunity to radioelectric fields10 V conforming to IEC 61000-4-6
Immunity to microbreaks3 ms
Immunity to voltage dips70 % / 500 ms conforming to IEC 61000-4-11
Number of Units in Package 11
Number of Units in Package 223
Country of originFR
Warranty (in months)18
Rated permanent current Iu38 A
Number of poles3
Short-circuit release functionUndelayed
Voltage type (supply voltage)AC/DC
End value adjustment range undelayed short-circuit release540 A
Voltage type for actuatingAC/DC

Properties

MOQ1

Cross-References

Attached Documents