cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Motor circuit breaker, TeSys Deca, 3P, AC-3/AC-3E, 6 to 10A, thermal magnetic, snap-in terminals, push button GV2ME14A

Schneider Electric · Electrical Components · Motor Protection Circuit Breakers · France · se.com
Part Number
GV2ME14A  ·  HS 8536.90
Schneider Electric Motor circuit breaker, TeSys Deca, 3P, AC-3/AC-3E, 6 to 10A, thermal magnetic, snap-in terminals, push button GV2ME14A

Schneider Electric GV2ME14A — TeSys motor protection circuit breaker. Manual motor starter with thermal and magnetic protection. Motor protection circuit breaker, TeSys Deca, 3P, AC-3/AC-3e, 6 for 10A, thermal-magnetic, Snap-In, push-button.

Technical Specifications

Manufacturer part number (MPN)GV2ME14A
EAN / GTIN3606487541875
HS code8536.90
Sales unitpcs
Package quantity20 pcs
Rated current10 A
RangeTeSys Deca
Product nameTeSys GV2
Product or component typeMotor circuit breaker
Device short nameGV2ME
Device applicationMotor protection
Trip unit technologyThermal-magnetic
Poles description3P
Network typeAC
Utilisation categoryCategory A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1; AC-3e conforming to IEC 60947-4-1
Network frequency50/60 Hz conforming to IEC 60947-2
Motor power kW3 kW at 400/415 V AC 50/60 Hz; 4 kW at 400/415 V AC 50/60 Hz; 4 kW at 500 V AC 50/60 Hz; 5.5 kW at 500 V AC 50/60 Hz; 5.5 kW at 690 V AC 50/60 Hz; 7.5 kW at 690 V AC 50/60 Hz
Breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 15 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2; 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
Control typePush-button
[In] rated current10 A
Thermal protection adjustment range6…10 A conforming to IEC 60947-2
Magnetic tripping current149 A
[Ith] conventional free air thermal current10 A conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2
Phase failure sensitivityYes conforming to IEC 60947-4-1
Suitability for isolationYes conforming to IEC 60947-1
Power dissipation per pole2.5 W
Mechanical durability100000 cycles
Electrical durability100000 cycles for AC-3 at 415 V In; 100000 cycles for AC-3e at 415 V In
Rated dutyUninterrupted conforming to IEC 60947-4-1
Connections - terminalsPower circuit: snap-in terminal 2 cable(s) 0.5…2.5 mm² - solid; Power circuit: snap-in terminal 2 cable(s) 0.5…4 mm² - flexible without cable end; Power circuit: snap-in terminal 2 cable(s) 0.5…2.5 mm² - flexible with cable end; Power circuit: snap-in terminal 2 cable(s) (20 AWG...12 AWG) - solid; Power circuit: snap-in terminal 2 cable(s) (20 AWG...10 AWG) - stranded
Fixing mode35 mm symmetrical DIN rail: clipped; Panel: screwed (with adaptor plate)
Mounting positionHorizontal; Vertical
Width45 mm
Height101 mm
Depth78.5 mm
Product weight258 g
ColourDark grey
StandardsEN/IEC 60947-2; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; IEC/EN 60335-2-40:Annex JJ; IEC/EN 60335-1:Clause 30.2
Product certificationsCB Scheme; CE; UKCA; CCC; cULus
IK degree of protectionIK04
IP degree of protectionIP20 conforming to IEC 60529 (on front face)
Climatic withstandconforming to IACS E10
Ambient air temperature for storage-40…80 °C
Fire resistance960 °C conforming to IEC 60695-2-11
Ambient air temperature for operation-20…60 °C
Mechanical robustnessShocks: 30 Gn for 11 ms; Vibrations: 5 Gn, 5...150 Hz
Operating altitude<= 2000 m
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents