Coil 100-250V Std 4P G400-500 (LX1G4SKUEN)

Schneider Electric · Electrical Components · Contactors · France · se.com
Part Number
LX1G4SKUEN  ·  HS 8505.90
Coil 100-250V Std 4P G400-500 (LX1G4SKUEN)

Schneider Electric LX1G4SKUEN Coil 100-250V AC / DC for 4-pole TeSys G400 / 500, standard.

Technical Specifications

Manufacturer part number (MPN)LX1G4SKUEN
EAN / GTIN3606481946539
Sales unitpcs
Package quantity2 pcs
Number of poles4P
RangeTeSys
Product or component typeContactor coil
Device short nameLX1G
Poles description4P
Range compatibilityTeSys G LX1G contactor coil
Product compatibilityLC1G400...500
[Uc] control circuit voltage100...250 V AC/DC 50/60 Hz
Operating time20...35 ms opening; 40...55 ms closing
Mechanical durability5 Mcycles
Maximum operating rate600 cyc/mn 60 °C
Coil technologyBuilt-in bidirectional peak limiting
Control circuit voltage limitsOperational: 0.8...1.1 Uc (at 60 °C); Drop-out: 0...0.45 Uc (at 60 °C)
Connections - terminalsControl circuit: push-in termination 1 cable(s) 0.2…2.5 mm² solid stranded without cable end sleeve 26 AWG...12 AWG; Control circuit: push-in termination 1 cable(s) 0.25…2.5 mm² flexible with cable end sleeve 24 AWG...14 AWG; Control circuit: push-in termination 2 cable(s) 0.5…1.0 mm² rigid or stranded with cable end sleeve 20 AWG...18 AWG
Inrush power in VA880 VA at 240 V AC, 60 Hz
Inrush power in W690.0 W DC
Hold-in power consumption in VA11.0 VA at 240 V AC, 60 Hz
Hold-in power consumption in W6.2 W for DC network
IP degree of protectionIP20 conforming to IEC 60529
Operating altitude3000 m without derating; 5000 m with derating factor
Electromagnetic compatibilityEMC immunity conforming to IEC 60947-4-1; Emission tests criteria A conforming to IEC 60947-4-1; Immunity to radiated radio-electrical interference - test level: 20 V/m conforming to EN/IEC 61000-4-3; Voltage dips and interruptions immunity test conforming to SEMI F47
StandardsEN/IEC 60947-4-1; UL 60947-4-1A; CSA C22.2 No 60947-4-1
Pollution degree3 conforming to IEC 60947-1
Ambient air temperature for operation-25…60 °C
Ambient air temperature for storage-60…80 °C
Permissible ambient air temperature around the device-40…70 °C at Uc
Height167.0 mm
Width185.0 mm
Depth93.0 mm
Quantity per set1
Number of Units in Package 11
Number of Units in Package 22
Number of Units in Package 316
Warranty (in months)18
Voltage type for actuatingAC/DC
Country of originChina

Properties