| Manufacturer part number (MPN) | LC1G1854EHEN |
| EAN / GTIN | 3606481922045 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Package quantity | 6 pcs |
| Number of poles | 4P |
| Range | TeSys |
| Range of product | TeSys Giga |
| Product or component type | Contactor |
| Device short name | LC1G |
| Contactor application | Power switching |
| Utilisation category | AC-3; AC-3e; AC-1; AC-5a; AC-5b; AC-6a; AC-6b; DC-1; DC-3; DC-5 |
| Poles description | 4P |
| [Ue] rated operational voltage | <= 1000 V AC 50/60 Hz; <= 460 V DC |
| [Ie] rated operational current | 185 A (at <60 °C) at <= 440 V AC-3; 305 A (at <40 °C) at <= 1000 V AC-1 |
| [Uc] control circuit voltage | 48...130 V AC 50/60 Hz; 48...130 V DC |
| Control circuit voltage limits | Operational: 0.8 Uc Min...1.1 Uc Max (at <60 °C); Drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C) |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 305 A (at 40 °C) |
| Rated breaking capacity | 1610 A at 440 V |
| [Icw] rated short-time withstand current | 1.5 kA - 10 s; 0.92 kA - 30 s; 0.74 kA - 1 min; 0.5 kA - 3 min; 0.4 kA - 10 min |
| Associated fuse rating | 200 A aM at <= 440 V for motor; 160 A aM at <= 690 V for motor; 315 A gG at <= 690 V; 300 A UL Type J at <= 600 V |
| Average impedance | 0.00017 Ohm |
| [Ui] rated insulation voltage | 1000 V |
| Power dissipation per pole | 20 W AC-1 - Ith 305 A; 6 W AC-3 - Ith 185 A |
| Compatibility code | LC1G |
| Pole contact composition | 4 NO |
| Auxiliary contact composition | 1 NO + 1 NC |
| Irms rated making capacity | 2310 A at 440 V |
| Coil technology | Built-in bidirectional peak limiting |
| Safety reliability level | B10d = 400000 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 3000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 8 Mcycles |
| inrush power in VA (50/60 Hz |
| AC) | 640 VA |
| inrush power in W (DC) | 445 W |
| hold-in power consumption in VA (50/60 Hz |
| AC) | 18.7 VA |
| hold-in power consumption in W (DC) | 7.8 W |
| Operating time | 40...70 ms closing; 15...50 ms opening |
| Maximum operating rate | 600 cyc/h AC-3; 600 cyc/h AC-3e; 300 cyc/h AC-1 |
| Connections - terminals | Power circuit: bar 2 - busbar cross section: 25 x 6 mm; Power circuit: lugs-ring terminals 1 185 mm²; Control circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable end; Control circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: push-in 2 0.5…1.0 mm² with cable end; Control circuit: push-in 0.75…2.5 mm² - cable stiffness: solid stranded without cable end; Control circuit: push-in 0.75…2.5 mm² - cable stiffness: flexible with cable end |
| Connection pitch | 35 mm |
| Mounting support | Plate |
| Standards | EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1; JIS C8201-5-1; UL 60335-1; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CCC; cULus; EAC; CE; UKCA; EU-RO-MR by DNV-GL |
| Tightening torque | 18 N.m |
| Height | 193 mm |
| Width | 143 mm |
| Depth | 193 mm |
| Product weight | 4.2 kg |
| IP degree of protection | IP2X front face with shrouds conforming to IEC 60529; IP2X front face with shrouds conforming to VDE 0106 |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -60…80 °C |
| Mechanical robustness | Vibrations 5…300 Hz 2 gn contactor open; Vibrations 5…300 Hz 4 gn contactor closed; Shocks 10 gn 11 ms contactor open; Shocks 15 gn 11 ms contactor closed |
| Colour | Dark grey |
| Protective treatment | TH |
| Permissible ambient air temperature around the device | -40…70 °C at Uc |
| Warranty (in months) | 18 |