| Manufacturer part number (MPN) | LC1G330KUEN |
| EAN / GTIN | 3606481921970 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Number of poles | 3P |
| Range | TeSys |
| Range of product | TeSys Giga |
| Product or component type | Contactor |
| Device short name | LC1G |
| Contactor application | Power switching; Motor control |
| Utilisation category | AC-1; AC-3; AC-3e; AC-4; AC-5a; AC-5b; AC-6a; AC-6b; AC-8a; AC-8b; DC-1; DC-3; DC-5 |
| Poles description | 3P |
| [Ue] rated operational voltage | <= 1000 V AC 50/60 Hz; <= 460 V DC |
| [Ie] rated operational current | 440 A (at <40 °C) at <= 1000 V AC-1; 330 A (at <60 °C) at <= 440 V AC-3 |
| [Uc] control circuit voltage | 100...250 V AC 50/60 Hz; 100...250 V DC |
| Control circuit voltage limits | Operational: 0.8 Uc Min...1.1 Uc Max (at <60 °C); Drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C) |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 440 A (at 40 °C) |
| Rated breaking capacity | 2940 A at 440 V |
| [Icw] rated short-time withstand current | 2.65 kA - 10 s; 1.8 kA - 30 s; 1.3 kA - 1 min; 0.9 kA - 3 min; 0.75 kA - 10 min |
| Associated fuse rating | 400 A aM at <= 440 V for motor; 250 A aM at <= 690 V for motor; 500 A gG at <= 690 V; 600 A UL Type L at <= 600 V |
| Average impedance | 0.000144 Ohm |
| [Ui] rated insulation voltage | 1000 V |
| Power dissipation per pole | 30 W AC-1 - Ith 440 A; 16 W AC-3 - Ith 330 A |
| Compatibility code | LC1G |
| Pole contact composition | 3 NO |
| Auxiliary contact composition | 1 NO + 1 NC |
| Motor power kW | 90 kW at 230 V AC 50/60 Hz (AC-3e); 160 kW at 400 V AC 50/60 Hz (AC-3e); 160 kW at 415 V AC 50/60 Hz (AC-3e); 185 kW at 440 V AC 50/60 Hz (AC-3e); 200 kW at 500 V AC 50/60 Hz (AC-3e); 220 kW at 690 V AC 50/60 Hz (AC-3e); 185 kW at 1000 V AC 50/60 Hz (AC-3e); 90 kW at 230 V AC 50/60 Hz (AC-3); 160 kW at 400 V AC 50/60 Hz (AC-3); 160 kW at 415 V AC 50/60 Hz (AC-3); 200 kW at 440 V AC 50/60 Hz (AC-3); 200 kW at 500 V AC 50/60 Hz (AC-3); 220 kW at 690 V AC 50/60 Hz (AC-3); 185 kW at 1000 V AC 50/60 Hz (AC-3); 90 kW at 230 V AC 50/60 Hz (AC-4); 160 kW at 400 V AC 50/60 Hz (AC-4); 160 kW at 415 V AC 50/60 Hz (AC-4); 185 kW at 440 V AC 50/60 Hz (AC-4); 200 kW at 500 V AC 50/60 Hz (AC-4); 220 kW at 690 V AC 50/60 Hz (AC-4); 185 kW at 1000 V AC 50/60 Hz (AC-4) |
| Motor power hp | 100 hp at 200/208 V 60 Hz; 125 hp at 230/240 V 60 Hz; 250 hp at 460/480 V 60 Hz; 300 hp at 575/600 V 60 Hz |
| Irms rated making capacity | 3830 A at 440 V |
| Coil technology | Built-in bidirectional peak limiting |
| Safety reliability level | B10d = 400000 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 3000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 8 Mcycles |
| inrush power in VA (50/60 Hz |
| AC) | 700 VA |
| inrush power in W (DC) | 645 W |
| hold-in power consumption in VA (50/60 Hz |
| AC) | 15.0 VA |
| hold-in power consumption in W (DC) | 9.1 W |
| Operating time | 40...70 ms closing; 15...50 ms opening |
| Maximum operating rate | 600 cyc/h AC-3; 600 cyc/h AC-3e; 300 cyc/h AC-1; 150 cyc/h AC-4 |
| Connections - terminals | Power circuit: bar 2 - busbar cross section: 32 x 10 mm; Power circuit: lugs-ring terminals 1 185 mm²; Power circuit: bolted connection; Control circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable end; Control circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: push-in 2 0.5…1.0 mm² with cable end; Control circuit: push-in 0.75…2.5 mm² - cable stiffness: solid stranded without cable end; Control circuit: push-in 0.75…2.5 mm² - cable stiffness: flexible with cable end |
| Connection pitch | 45 mm |
| Mounting support | Plate |
| Standards | EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1; JIS C8201-5-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-1; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CCC; cULus; EAC; CE; UKCA; EU-RO-MR by DNV-GL |
| Tightening torque | 35 N.m |
| Height | 225 mm |
| Width | 140 mm |
| Depth | 226 mm |
| Product weight | 7 kg |
| IP degree of protection | IP2X front face with shrouds conforming to IEC 60529; IP2X front face with shrouds conforming to VDE 0106 |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -60…80 °C |
| Mechanical robustness | Vibrations 5…300 Hz 2 gn contactor open; Vibrations 5…300 Hz 4 gn contactor closed; Shocks 10 gn 11 ms contactor open; Shocks 15 gn 11 ms contactor closed |
| Colour | Dark grey |
| Protective treatment | TH |
| Permissible ambient air temperature around the device | -40…70 °C at Uc |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 8 |
| Warranty (in months) | 18 |