cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric High power contactor, TeSys Giga, 3 pole (3NO), AC-3 ≤440V 630A, standard version, 48…130V wide band AC/DC coil LC1G630EHEN

Schneider Electric · Electrical Components · Contactors · France · se.com
Part Number
LC1G630EHEN  ·  HS 8536.90
Schneider Electric High power contactor, TeSys Giga, 3 pole (3NO), AC-3 ≤440V 630A, standard version, 48…130V wide band AC/DC coil LC1G630EHEN

Schneider Electric LC1G630EHEN Contactor TeSys LC1G 630A 440V 3P AC3 standard 48-130V AC-DC coil.

Technical Specifications

Manufacturer part number (MPN)LC1G630EHEN
EAN / GTIN3606481921901
HS code8536.90
Sales unitpcs
Package quantity2 pcs
Number of poles3P
RangeTeSys
Range of productTeSys Giga
Product or component typeContactor
Device short nameLC1G
Contactor applicationPower switching; Motor control
Utilisation categoryAC-1; AC-3; AC-3e; AC-4; AC-5a; AC-5b; AC-6a; AC-6b; AC-8b; AC-8a; DC-1; DC-3; DC-5
Poles description3P
[Ue] rated operational voltage<= 1000 V AC 50/60 Hz; <= 460 V DC
[Ie] rated operational current1050 A (at <40 °C) at <= 1000 V AC-1; 630 A (at <60 °C) at <= 440 V AC-3
[Uc] control circuit voltage48...130 V AC 50/60 Hz; 48...130 V DC
Control circuit voltage limitsOperational: 0.8 Uc Min...1.1 Uc Max (at <60 °C); Drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)
[Uimp] rated impulse withstand voltage8 kV
Overvoltage categoryIII
[Ith] conventional free air thermal current1050 A (at 40 °C)
Rated breaking capacity5550 A at 440 V
[Icw] rated short-time withstand current5.05 kA - 10 s; 4.4 kA - 30 s; 3.4 kA - 1 min; 2.2 kA - 3 min; 1.6 kA - 10 min
Associated fuse rating630 A aM at <= 440 V for motor; 500 A aM at <= 690 V for motor; 1250 A gG at <= 690 V; 1000 A UL Type L at <= 600 V
Average impedance0.000065 Ohm
[Ui] rated insulation voltage1000 V
Power dissipation per pole70 W AC-1 - Ith 1050 A; 26 W AC-3 - Ith 630 A
Compatibility codeLC1G
Pole contact composition3 NO
Auxiliary contact composition1 NO + 1 NC
Motor power kW180 kW at 230 V AC 50/60 Hz (AC-3e); 315 kW at 400 V AC 50/60 Hz (AC-3e); 335 kW at 415 V AC 50/60 Hz (AC-3e); 355 kW at 440 V AC 50/60 Hz (AC-3e); 375 kW at 500 V AC 50/60 Hz (AC-3e); 500 kW at 690 V AC 50/60 Hz (AC-3e); 450 kW at 1000 V AC 50/60 Hz (AC-3e); 200 kW at 230 V AC 50/60 Hz (AC-3); 335 kW at 400 V AC 50/60 Hz (AC-3); 375 kW at 415 V AC 50/60 Hz (AC-3); 400 kW at 440 V AC 50/60 Hz (AC-3); 400 kW at 500 V AC 50/60 Hz (AC-3); 500 kW at 690 V AC 50/60 Hz (AC-3); 450 kW at 1000 V AC 50/60 Hz (AC-3); 180 kW at 230 V AC 50/60 Hz (AC-4); 315 kW at 400 V AC 50/60 Hz (AC-4); 335 kW at 415 V AC 50/60 Hz (AC-4); 355 kW at 440 V AC 50/60 Hz (AC-4); 375 kW at 500 V AC 50/60 Hz (AC-4); 450 kW at 690 V AC 50/60 Hz (AC-4); 355 kW at 1000 V AC 50/60 Hz (AC-4)
Motor power hp250 hp at 200/208 V 60 Hz; 300 hp at 230/240 V 60 Hz; 600 hp at 460/480 V 60 Hz; 700 hp at 575/600 V 60 Hz
Irms rated making capacity7220 A at 440 V
Coil technologyBuilt-in bidirectional peak limiting
Safety reliability levelB10d = 100000 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 1800000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability5 Mcycles
inrush power in VA (50/60 Hz
AC)990 VA
inrush power in W (DC)790 W
hold-in power consumption in VA (50/60 Hz
AC)18.7 VA
hold-in power consumption in W (DC)9.5 W
Operating time40...70 ms closing; 15...50 ms opening
Maximum operating rate600 cyc/h AC-3; 600 cyc/h AC-3e; 300 cyc/h AC-1; 150 cyc/h AC-4
Connections - terminalsPower circuit: bar 2 - busbar cross section: 52 x 20 mm; Power circuit: lugs-ring terminals 1 185 mm²; Power circuit: bolted connection; Control circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable end; Control circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: push-in 2 0.5…1.0 mm² with cable end; Control circuit: push-in 0.75…2.5 mm² - cable stiffness: solid stranded without cable end; Control circuit: push-in 0.75…2.5 mm² - cable stiffness: flexible with cable end
Connection pitch70 mm
Mounting supportPlate
StandardsEN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1; JIS C8201-5-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-1; UL 60335-2-40:Annex JJ
Product certificationsCB Scheme; CCC; cULus; EAC; CE; UKCA; EU-RO-MR by DNV-GL
Tightening torque58 N.m
Height284 mm
Width211 mm
Depth266 mm
Product weight14.2 kg
IP degree of protectionIP2X front face with shrouds conforming to IEC 60529; IP2X front face with shrouds conforming to VDE 0106
Ambient air temperature for operation-25…60 °C
Ambient air temperature for storage-60…80 °C
Mechanical robustnessVibrations 5…300 Hz 2 gn contactor open; Vibrations 5…300 Hz 4 gn contactor closed; Shocks 10 gn 11 ms contactor open; Shocks 15 gn 11 ms contactor closed
ColourDark grey
Protective treatmentTH
Permissible ambient air temperature around the device-40…70 °C at Uc
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents