| Manufacturer part number (MPN) | TPRPM009 |
| EAN / GTIN | 3606489832841 |
| Sales unit | pcs |
| Package quantity | 14 pcs |
| Power | 4 kW |
| Range of product | TeSys |
| Product name | TeSys island |
| Device short name | TPRPM |
| Product or component type | Power module |
| Device presentation | Power module connected to an automation controller through a bus coupler; Operational only when connected to a bus coupler |
| Function available | Upstream voltage presence detection; Electronic thermal overload protection; Monitoring of currents; Control of third party power devices when associated to TPRDG IO module |
| Product compatibility | TPRBC bus coupler; TPRDG digital IO module; TPRAN analog IO module |
| Poles description | 3P |
| Motor power kW | 2.2 kW at 230 V AC 50 Hz; 4 kW at 380...415 V AC 50 Hz; 4 kW at 440 V AC 50 Hz; 5.5 kW at 500 V AC 50 Hz; 5.5 kW at 690 V AC 50 Hz |
| motor power HP (UL / CSA) | 0.33 hp at 120 V AC 60 Hz for 1 phase motors; 1 hp at 240 V AC 60 Hz for 1 phase motors; 2 hp at 208 V AC 60 Hz for 3 phases motors; 2 hp at 240 V AC 60 Hz for 3 phases motors; 5 hp at 480 V AC 60 Hz for 3 phases motors; 7.5 hp at 600 V AC 60 Hz for 3 phases motors |
| [Ue] rated operational voltage | <= 690 V AC 47...63 Hz |
| [Ie] rated operational current | 9 A (at <50 °C) at <= 440 V AC-3; 15 A (at <50 °C) at <= 440 V AC-1; 15 A (at <50 °C) AC-3e |
| [Ith] conventional free air thermal current | 15 A (at 50 °C) |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-4-1; 600 V conforming to UL 60947-4-1; 600 V conforming to CSA C22.2 No 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Overvoltage category | III |
| Thermal protection adjustment range | 0.18…9 A |
| Thermal overload class | Class 5…30 |
| Reset | Remotely or automatically |
| [Uc] control circuit voltage | 24 V DC supplied by the bus coupler |
| Current consumption | 60 mA |
| Power dissipation in W | 0.6 W at Ie AC-3 |
| Protection type | Thermal overload protection; Motor overheat; Overcurrent; Undercurrent; Jam; Long start; Stall; Rapid cycle lockout; Phase loss; Rapid restart lockout; Phase reversal; Phase unbalance; Phase sequence; Ground current |
| Monitoring type | Time device ON; Number of faults; Number of device power cycles; Average current Iavg; Average voltage Vavg; Max current Imax; Max voltage Vmax |
| Local signalling | 1 LED (green/red) for DS (device status); 1 LED (green/red) for LS (load status) |
| Standards | EN/IEC 60947-1; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1 |
| Product certifications | CCC; CSA; EAC; UL |
| Mounting mode | Horizontal and vertical (35 mm symmetrical DIN rail) |
| Connections - terminals | Screw-clamp terminals 1 cable(s) 1…4 mm² (16 AWG...12 AWG) rigid; Screw-clamp terminals 2 cable(s) 1…4 mm² (16 AWG...12 AWG) rigid; Screw-clamp terminals 1 cable(s) 1.5…4 mm² (16 AWG...12 AWG) flexible without cable end; Screw-clamp terminals 2 cable(s) 1.5…4 mm² (16 AWG...12 AWG) flexible without cable end; Screw-clamp terminals 1 cable(s) 1…4 mm² (16 AWG...12 AWG) flexible with cable end; Screw-clamp terminals 2 cable(s) 1…2.5 mm² (16 AWG...14 AWG) flexible with cable end |
| Tightening torque | 1.7 N.m - with screwdriver flat Ø 6 mm; 1.7 N.m - with screwdriver Philips No 2 |
| Width | 45 mm |
| Height | 121 mm |
| Depth | 115 mm |
| Product weight | 0.255 kg |
| Ambient air temperature for storage | -25…70 °C |
| Ambient air temperature for operation | -10…50 °C without derating; 50…60 °C with current derating |
| Relative humidity | 5…95 % |
| Operating altitude | 0...2000 m without derating |
| IP degree of protection | IP20 |
| Pollution degree | 2 |
| Protective treatment | TC |
| Fire resistance | 960 °C conforming to UL 94; 850 °C conforming to IEC 60695-2-1; 650 °C conforming to IEC 60695-2-12 |
| Shock resistance | 15 gn (duration = 11 ms) conforming to IEC 60068-2-27 |
| Vibration resistance | 1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6; 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
| Electromagnetic compatibility | Electrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2; Radiated RF field immunity test, level 3, 10 V/m, conforming to EN/IEC 61000-4-3; Fast transient immunity test, level 4, 4 kV, conforming to EN/IEC 61000-4-4; Surge immunity test (differential mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5; Surge immunity test (common mode), level 4, 4 kV, conforming to EN/IEC 61000-4-5; Conducted RF disturbance immunity test, 20 V, conforming to EN/IEC 61000-4-6 |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 14 |
| Country of origin | FR |
| Warranty (in months) | 18 |
| Certified for UL hazardous location division 1 | No |
| Certified for UL hazardous location division 2 | No |
| Certified for UL hazardous location group A (acetylene) | No |
| Certified for UL hazardous location group B (hydrogen) | No |
| Certified for UL hazardous location group C (ethylene) | No |
| Certified for UL hazardous location group D (propane) | No |
| Certified for UL hazardous location group E (metal dusts) | No |
| Certified for UL hazardous location class I | No |
| Certified for UL hazardous location class II | No |
| Certified for UL hazardous location class III | No |
| Supporting protocol for EtherCAT | No |
| Voltage type (supply voltage) | DC |
| Number of inputs | 1 |
| Type of voltage (input voltage) | AC |
| Type of digital output | None |
| Type of output voltage | AC |
| Short-circuit protection, outputs available | No |
| Number of motor outlets | 1 |
| With motor current parameter setting | No |
| Type of electrical connection at the motor output | Screw connection |
| With brake output | No |
| With thermal motor protection | Yes |
| Number of HW-interfaces other | 2 |
| With optical interface | No |
| Supporting protocol for TCP/IP | No |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for CAN | No |
| Supporting protocol for INTERBUS | No |
| Supporting protocol for ASI | No |
| Supporting protocol for KNX | No |
| Supporting protocol for Modbus | No |
| Supporting protocol for Data-Highway | No |
| Supporting protocol for DeviceNet | No |
| Supporting protocol for SUCONET | No |
| Supporting protocol for LON | No |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFINET CBA | No |
| Supporting protocol for SERCOS | No |
| Supporting protocol for Foundation Fieldbus | No |
| Supporting protocol for EtherNet/IP | No |
| Supporting protocol for AS-Interface Safety at Work | No |
| Supporting protocol for DeviceNet Safety | No |
| Supporting protocol for INTERBUS-Safety | No |
| Supporting protocol for PROFIsafe | No |
| Supporting protocol for SafetyBUS p | No |
| Supporting protocol for other bus systems | Yes |
| Radio standard Bluetooth | No |
| Radio standard WLAN 802.11 | No |
| Radio standard GPRS | No |
| Radio standard GSM | No |
| Mobile communications standard 3G (UMTS) | No |
| IO link master | No |
| System accessory | Yes |
| Degree of protection (IP) | IP20 |
| Type of electric connection | Plug-in connection |
| Fieldbus connection over separate bus coupler possible | Yes |
| Suitable for rail mounting | Yes |
| Wall mounting/direct mounting | No |
| Front built-in possible | No |
| Rack-assembly possible | No |
| Suitable for safety functions | No |
| SIL according to IEC 61508 | None |
| Performance level according to EN ISO 13849-1 | None |
| Appendant operation agent (Ex ia) | No |
| Explosion safety category for gas | None |
| Explosion safety category for dust | None |