cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Direct online SIL starter, TeSys island, 30A AC-1, 25A AC-3, 11kW / 15hp TPRSS025

Schneider Electric · Electrical Components · France · se.com
Part Number
TPRSS025  ·  HS 8536.50
Schneider Electric Direct online SIL starter, TeSys island, 30A AC-1, 25A AC-3, 11kW / 15hp TPRSS025

Schneider Electric TPRSS025 Direct SIL-start TeSys island 30A AC-1, 25A AC-3, 11kW/15hk.

Technical Specifications

Manufacturer part number (MPN)TPRSS025
EAN / GTIN3606489832803
Sales unitpcs
Package quantity14 pcs
Power11 kW
Rated current25 A
RangeTeSys
Product nameTeSys island
Device short nameTPRSS
Product or component typeSIL motor starter
Motor starter typeDirect on line
Device presentationDirect starter connected to an automation controller through a bus coupler; Operational only when connected to a bus coupler
Function availableUpstream voltage presence detection; Electrical line and load protection; Power and energy monitoring when connected with TPRVM voltage module; Safe stop function available when connected with a TPRSM module
Product compatibilityTPRBC bus coupler; TPRVM voltage interface module; TPRSM SIL interface module
Poles description3P (3 NO)
Utilisation categoryAC-1; AC-2; AC-3; AC-4; AC-3e
Motor power kW5.5 kW at 230 V 50 Hz (AC-3); 11 kW at 380...415 V 50 Hz (AC-3); 11 kW at 440 V 50 Hz (AC-3); 15 kW at 500 V 50 Hz (AC-3); 15 kW at 690 V 50 Hz (AC-3)
motor power HP (UL / CSA)2 hp at 120 V AC 60 Hz for 1 phase motors; 3 hp at 240 V AC 60 Hz for 1 phase motors; 7.5 hp at 208 V AC 60 Hz for 3 phases motors; 7.5 hp at 240 V AC 60 Hz for 3 phases motors; 15 hp at 480 V AC 60 Hz for 3 phases motors; 20 hp at 600 V AC 60 Hz for 3 phases motors
[Ue] rated operational voltage<= 480 V AC 47...63 Hz for overvoltage cat. III; <= 690 V AC 47...63 Hz for overvoltage cat. II
[Ie] rated operational current25 A (at <50 °C) at <= 440 V AC-3; 30 A (at <50 °C) at <= 440 V AC-1
[Ith] conventional free air thermal current30 A (at 50 °C)
[Ui] rated insulation voltage690 V conforming to IEC 60947-4-1; 600 V conforming to UL 60947-4-1; 600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-1
Overvoltage categoryIII for Ue <= 480 V; II for Ue <= 690 V
Thermal protection adjustment range0.5…25 A
Thermal overload classClass 5…30
ResetRemotely or automatically
Irms rated making capacity450 A at 440 V conforming to IEC 60947
Rated breaking capacity450 A at 440 V conforming to IEC 60947
[Icw] rated short-time withstand current380 A 40 °C - 1 s; 240 A 40 °C - 10 s; 120 A 40 °C - 1 min; 50 A 40 °C - 10 min
Average impedance2 mOhm - Ith 30 A 50 Hz
Power dissipation per pole1.25 W AC-3 - Ith 25 A; 1.8 W AC-1 - Ith 30 A
[Uc] control circuit voltage24 V DC supplied by the bus coupler
Current consumption160 mA contactor sealed; 160 mA contactor closing
Power dissipation in W6.6 W at Ie AC-3
Mechanical durability30 Mcycles
Electrical durability1.65 Mcycles 25 A AC-3 at Ue 440 V; 2 Mcycles 30 A AC-1 at Ue 440 V
Maximum operating rate3600 cyc/mn AC-3
Operating time< 100 ms closing; < 30 ms opening
Safety functionSafe stop: category 0 conforming to IEC 60204-1 when associated with a TPRSM module; Safe stop: category 1 conforming to IEC 60204-1 when associated with a TPRSM module
Safety integrity levelSIL 2 conforming to IEC 61508 in single channel system architecture; SILCL 2 conforming to IEC 62061 in single channel system architecture; PL = d category 2 conforming to ISO 13849-1 in single channel system architecture
Safety performance levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Protection typeThermal overload protection; Motor overheat; Overcurrent; Undercurrent; Jam; Long start; Stall; Rapid cycle lockout; Phase sequence; Rapid restart lockout; Phase reversal; Phase loss; Phase unbalance; Ground current
Monitoring typeTime device ON; Time device switch ON; Number of faults; Number of switching cycles; Number of device power cycles; Average current Iavg; Average voltage Vavg; Max current Imax; Max voltage Vmax; Active and reactive power with voltage module; Active and reactive energy with voltage module; True power factor with voltage module
Local signalling1 LED (green/red) for DS (device status); 1 LED (green/red) for LS (load status)
StandardsEN/IEC 60947-1; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1
Product certificationsCCC; EAC; UL; CSA
Mounting modeHorizontal and vertical (35 mm symmetrical DIN rail)
Connections - terminalsScrew-clamp terminals 1 cable(s) 1.5…10 mm² (16 AWG...8 AWG) rigid; Screw-clamp terminals 2 cable(s) 1.5…10 mm² (16 AWG...8 AWG) rigid; Screw-clamp terminals 1 cable(s) 2.5…10 mm² (14 AWG...8 AWG) flexible without cable end; Screw-clamp terminals 2 cable(s) 2.5…10 mm² (14 AWG...8 AWG) flexible without cable end; Screw-clamp terminals 1 cable(s) 1.5…10 mm² (16 AWG...10 AWG) flexible with cable end; Screw-clamp terminals 2 cable(s) 1.5…6 mm² (16 AWG...10 AWG) flexible with cable end
Tightening torque2.5 N.m - with screwdriver flat Ø 6 mm; 2.5 N.m - with screwdriver Philips No 3
Width45 mm
Height121 mm
Depth115 mm
Product weight0.718 kg
Ambient air temperature for storage-25…70 °C
Ambient air temperature for operation-10…50 °C without derating; 50…60 °C with current derating
Relative humidity5…95 %
Operating altitude0...2000 m without derating
IP degree of protectionIP20
Pollution degree2
Protective treatmentTC
Fire resistance960 °C conforming to UL 94; 850 °C conforming to IEC 60695-2-1; 650 °C conforming to IEC 60695-2-12
Shock resistance15 gn (duration = 11 ms) conforming to IEC 60068-2-27
Vibration resistance1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6; 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
Electromagnetic compatibilityElectrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2; Radiated RF field immunity test, level 3, 10 V/m, conforming to EN/IEC 61000-4-3; Fast transient immunity test, level 4, 4 kV, conforming to EN/IEC 61000-4-4; Surge immunity test (differential mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5; Surge immunity test (common mode), level 4, 4 kV, conforming to EN/IEC 61000-4-5; Conducted RF disturbance immunity test, 20 V, conforming to EN/IEC 61000-4-6
Country of originFR
Warranty (in months)18
Certified for UL hazardous location division 1No
Certified for UL hazardous location division 2No
Certified for UL hazardous location group A (acetylene)No
Certified for UL hazardous location group B (hydrogen)No
Certified for UL hazardous location group C (ethylene)No
Certified for UL hazardous location group D (propane)No
Certified for UL hazardous location group E (metal dusts)No
Certified for UL hazardous location class INo
Certified for UL hazardous location class IINo
Certified for UL hazardous location class IIINo
Supporting protocol for EtherCATNo
Voltage type (supply voltage)DC
Number of inputs1
Type of voltage (input voltage)AC
Type of digital outputNone
Type of output voltageAC
Short-circuit protection, outputs availableNo
Number of motor outlets1
With motor current parameter settingNo
Type of electrical connection at the motor outputScrew connection
With brake outputNo
With thermal motor protectionYes
Number of HW-interfaces other2
With optical interfaceNo
Supporting protocol for TCP/IPNo
Supporting protocol for PROFIBUSNo
Supporting protocol for CANNo
Supporting protocol for INTERBUSNo
Supporting protocol for ASINo
Supporting protocol for KNXNo
Supporting protocol for ModbusNo
Supporting protocol for Data-HighwayNo
Supporting protocol for DeviceNetNo
Supporting protocol for SUCONETNo
Supporting protocol for LONNo
Supporting protocol for PROFINET IONo
Supporting protocol for PROFINET CBANo
Supporting protocol for SERCOSNo
Supporting protocol for Foundation FieldbusNo
Supporting protocol for EtherNet/IPNo
Supporting protocol for AS-Interface Safety at WorkNo
Supporting protocol for DeviceNet SafetyNo
Supporting protocol for INTERBUS-SafetyNo
Supporting protocol for PROFIsafeNo
Supporting protocol for SafetyBUS pNo
Supporting protocol for other bus systemsYes
Radio standard BluetoothNo
Radio standard WLAN 802.11No
Radio standard GPRSNo
Radio standard GSMNo
Mobile communications standard 3G (UMTS)No
IO link masterNo
System accessoryYes
Degree of protection (IP)IP20
Type of electric connectionPlug-in connection
Fieldbus connection over separate bus coupler possibleYes
Suitable for rail mountingYes
Wall mounting/direct mountingNo
Front built-in possibleNo
Rack-assembly possibleNo
Suitable for safety functionsYes
SIL according to IEC 615082
Performance level according to EN ISO 13849-1Level d
Appendant operation agent (Ex ia)No
Explosion safety category for gasNone
Explosion safety category for dustNone

Properties

MOQ1

Cross-References

Attached Documents